1 / 27

Reactive power injection strategies for wind energy regarding its statistical nature

Reactive power injection strategies for wind energy regarding its statistical nature . Joaquín Mur M.P. Comech joako@unizar.es mcomech@unizar.es. Wind site resource Turbine power curve Farm power curve Farm electric model Nearby wind farms Limits on reactive power. Reactive Power Policy

Pat_Xavi
Télécharger la présentation

Reactive power injection strategies for wind energy regarding its statistical nature

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Reactive power injection strategies for wind energy regarding its statistical nature Joaquín Mur M.P. Comech joako@unizar.esmcomech@unizar.es

  2. Wind site resource Turbine power curve Farm power curve Farm electric model Nearby wind farms Limits on reactive power Reactive Power Policy Constant power factor Automatic voltage control Scheduled Reactive control Reactive power under centralized control Effect on power losses Uncertainty Analysis Conclusions I. Introduction: presentation layout

  3. II. Wind site resource (Weibull distribution) Chart for shape parameter = 2 Solid red => wind speed = 5 m/s Dashed pink=>wind speed = 5,5 m/s Dark blue => wind speed = 6 m/s Light blue => wind speed = 6,5 m/s Dotted green=>wind speed = 7 m/s Yellow => wind speed = 7,5 m/s

  4. III. Wind turbine (IEC 61400-12-1) Power curve measured at a pitch regulated turbine (from IEC 61400-12-1)

  5. III. Snapshoot of turbines in a farm Power curve measured at a pitch regulated turbine (from IEC 61400-12-1)

  6. IV. Wind farm curve (IEC 61400-12-3) Declared (calculated) wind farm power curve by directional sector (from IEC 61400-12-3, annex C)

  7. IV. Wind farm (4 parameters adjusted curve) woff wf is the farm mean efficiency factor(referred to “unperturbated wind” of the site). w25% w75% woff

  8. IV. Farm power distribution

  9. IV. Farm power distribution Chart for shape factor k = 2 Solid red => wind speed = 5 m/s Dashed pink=>wind speed = 5,5 m/s Dark blue => wind speed = 6 m/s Light blue => wind speed = 6,5 m/s Dotted green=>wind speed = 7 m/s Yellow => wind speed = 7,5 m/s Dashed red => wind speed = 8 m/s

  10. V. Model of the wind farm with one medium voltage circuit

  11. V. Model of the wind farm with several medium voltage circuits

  12. V. Approximated equivalent model of the wind farm • Averaged model

  13. V. Fourth pole model & parameters of the farm

  14. Nearby wind farms are supposed to be closely correlated  a linear regression can be precise enough VI. Power of nearby farms • Pi and Pj are the average power output in park “j” (estimated farm) and “i” (reference farm); • rijis the experimental correlation coefficient; • si and sjare the standard deviation of power in farms i and j. • Qi and Qj must be estimated based on each farm reactive control

  15. VII. Limits on reactive power • Limits provided by the turbine manufacturer. • Second edition of IEC 61400-21 will include a section devoted to the reactive power capability and the ability to participate in an automatic voltage control scheme. • Allowable voltage at the turbines. • The wind turbine that is electrically farer from PCC will suffer the greatest voltage deviations of the wind farm. • Voltage at turbines is dependent on UPCC • Current limit in series elements (lines, transformers, etc) and grid bottlenecks. • Slow thermal dynamics, grid congestion… • Usually, some degree of overload is allowed.

  16. VII. Voltage at electrically farer turbine • Estimation of parameters from power flows:

  17. VII. Loci of allowable power

  18. Centralized control: stabilize voltage, power losses, balance reactive power flows… Constant power factor regulation Automatic voltage control Scheduled reactive control Current model in Spain, power factor depending on hours Improvement if weekdays and holidays would be considered Improvement if target is based on reactive power, not on power factor VIII. Reactive power policy

  19. Medium hours 12 h/day (unity power factor) Valley hours 8 h/day Peak hours 4 h/day (Capacitive behaviour) VIII. Voltage deviation due to scheduled power factor (Spain)

  20. VIII. Reactive power injection due to scheduled power factor (Spain) Peak hours 4 h/day (Capacitive behaviour) Valley hours 8 h/day

  21. VIII. Reactive power under centralized control • Simplistic example of realizable reactive power at a wind turbine

  22. VIII. Availability of reactive power INJECTION for the example • Probability of being able to INJECT capacitive power up to Qwt Chart for shape parameter = 2 Solid red => wind speed = 5 m/s Dashed pink=>wind speed = 5,5 m/s Dark blue => wind speed = 6 m/s Light blue => wind speed = 6,5 m/s Dotted green=>wind speed = 7 m/s Yellow => wind speed = 7,5 m/s

  23. VIII. Availability of reactive power ABSORPTION for the example • Probability of being able to ABSORB inductive power up to Qwt Chart for shape parameter = 2 Solid red => wind speed = 5 m/s Dashed pink=>wind speed = 5,5 m/s Dark blue => wind speed = 6 m/s Light blue => wind speed = 6,5 m/s Dotted green=>wind speed = 7 m/s Yellow => wind speed = 7,5 m/s

  24. IX. Effect on power losses • Parameters aP, aQ, bP and bQ can be obtained from power flow runs • An analogue relationship can be established for losses on reactive power

  25. X. Uncertainty of the results The main source of errors are: • Adjustment of wind resource to a Weibull distribution. • The uncertainty of the farm power curve. • Simplistic model of the power curve with only two or four parameters. • Approximations done in the model of the grid (for example, considering U0 constant). • Availability of turbines and network.

  26. Conclusions • This work shows a statistical model of wind farms and a methodology for adjusting its parameters. This model has been used to assess the grid impact of a wind farm reactive power during normal operation. • Several reactive power control strategies are analyzed. • The uncertainty of the final data due to the approximations made is studied. The accuracy can be increased if non-parametric models of farm power curve and wind resource is employed.

  27. Questions?

More Related