An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. EVALUAREA PERFORMANTELOR INSTALAŢIILORRETEHNOLOGIZATE DIN CADRUL CN TRANSELECTRICA PRIVIND RISCURILE PROFESIONALE ing. Camelia Suvergel – SC Filiala ICEMENERG SA drd. ing. Alice Raducanu – CNTEE Transelectrica SA ing. Marin Stefan – CN Transelectrica SA dr.Cornelia Marcolt - CN Transelectrica SA ing. C-tin Munteanu – SC Filiala ICEMENERG SA insp. Florian Duminica – ITM Bucuresti

  2. INDEX Sinteza aplicatiilor Prezentarea noxelor profesionale investigate Intensitatea campului electric si magnetic Noxe chimice (oxid de carbon,bioxid de sulf, oxizi de azot si hidrocarburi alifatice) Zgomot si vibratii Reglementari existente pe plan international si national Descrierea sistemului de masurare Concluzii privind rezultatele obtinute

  3. INTRODUCEREPrezentul articol cuprinde compararea determinarilor de noxe profesionale inainte si dupa retehnologizarea instalatiilor electrice, apartinand ST Craiova, din mediu de munca al personalului, verificarea incadrarii nivelului noxelor in limite admise de norme si aplicarea criteriilor si metodologiei pentru incadrarea locurilor de munca in conditii deosebite, in cazul nerespectarii acestor limite.ICEMENERG a efectuat determinarea noxelor profesionale inainte si dupa retehnologizarea instalatiilor electrice ce apartin ST Craiova.

  4. SINTEZA APLICATIILOR Reglementări existente pe plan internaţional si national pentru camp electric si magnetic Asociaţia Internaţională de Protecţie împotriva Radiaţiilor (IRPA) recomandă valorile din tabelul 1 privind limitele de câmp electric şi magnetic asociate perioadelor de expunere.

  5. Comitetul European pentru Standardizare - Sectia Electrotehnică (CENELEC) fixeaza prin publicaţia ENV 50166-1/1995 “Human exposure to electromagnetic fields. Low frequencies 0 - 10kHz” valorile limită (restricţii de bază) şi nivelele de referinţă pentru câmpul electric şi magnetic în domeniul frecvenţelor menţionate. UNIPEDE (Uniunea Producătorilor şi Distribuitorilor de Energie Electrică) face referiri în documentele sale la reglementările diferitelor ţări, precum şi a Comunităţii Europene .

  6. Reglementari existente pe plan national HG 1136/2006 transpune Directiva 2004/40/CE privind cerinţele minime de securitate şi sănătate, referitoare la expunerea lucrătorilor la riscuri generate de câmpul electromagnetic Intensitatea câmpului electric:10 kV/m Densitatea de flux magnetic (B, valoare r.m.s.) a câmpuluimagnetic la frecvenţa de 50 Hz este de:0,5 mT (0,5 mT = 500 μT)

  7. Aparatura utilizata pentru masurarea campului electric si magnetic Măsurarea intensităţii câmpului electric şi a inducţiei magnetice a fost efectuată folosind sistemul EMDEX II . Pentru măsurătorile de câmp electric s-a utilizat o sondă de câmp electric formată din două plăci din aluminiu separate de patru distanţiere din material plastic. În timpul măsurării aparatul EMDEX II este plasat între cele două plăci şi înregistrează curentul de frecvenţă industrială dintre acestea.

  8. Reglementări existente pe plan internaţional si national pentru noxe chimice Dintre reglementarile internationale amintim : Draft Standard for Code of Practice for an Occupational Health and Safety Management System (National Standards Authority of Ireland). Technical Report NPR 5001:1997. Guide to an occupational health and safety management system (Nederlands Normalisatie-Instituut) Dintre reglementarile existente pe plan national amintim : HG nr.1218 / 06.09.2006 - transpune Directiva 2000/39/CE privind protecţia sănătăţii şi securităţii lucrătorilor împotriva riscurilor legate de prezenţa agenţilor chimici la locul de muncă , Normele Metodologice de Medicina Muncii / 1996

  9. Aparatura utilizata pentru masurarea noxelor chimice * pentru recoltare probe: pompe recoltat probe de aer Gilian analizor de gaze tip Miniwarn-Drager cu senzori electrochimici specifici tip Drager Senzor XS EC NOx – 68 09 155, XS EC CO – 68 09 005, XS EC CO – 68 09 160, CAT Ex absorbitoare si microabsorbitoare * pentru determinarea propriu-zisa : spectrofotometru UV/VIS MILTON-ROY balanta analitica tip Mettler

  10. Reglementări existente pe plan internaţional si national pentru zgomot si vibratii HG 493/2006 şi HG 1876/2005, transpun Directiva 2003/10/CE şi Directiva 2002/44/CE privind cerinţele minime de securitate şi sănătate referitoare la expunerea lucrătorilor la riscurile generate de zgomot şi vibraţii("Occupational Safety and Health Standards").

  11. Aparatura utilizata pentru masurarea zgomotului si vibratiilor * pentru determinare zgomot: sonometrul BRÜEL&KJÆR * pentru determinare vibratii: sonometrul BRÜEL&KJÆR, prin inlocuirea senzorului de zgomot (microfonul) cu senzorul de vibratii (senzor piezoelectric)

  12. Principalele surse de zgomot in statiile electrice sunturmatoarele: -transformatoarele de putere si bobinele de reactanta din miez de fier, la care zgomotul este produs de vibratiile miezului ca urmare a fenomenului de magnetostrictiune; -instalatiile de racire fortata ale transformatoarelor si bobinelor de compensare alcatuite din ventilatoare si pompe de recirculare a uleiului; -instalatiile de producere a aerului comprimat (compresoarele aferente instalatiilor cu hidrofor); -grupul electrogen pentru alimentarea de siguranta a serviciilor proprii; -descarcarile corona care pot apare la tensiuni mai mari de 100 kV în conditii meteorologice nefavorabile; -anumite activitati din perioada desfasurarii lucrarilor de santier si de revizii–reparatii (manipulari de materiale, prelucrari mecanice, transporturi ,etc.).

  13. Masuratori camp electric si magnetic inainte si dupa retehnologizare

  14. Observaţii: La valorile gradientului de potential la sol, respectiv la inaltimea de 1,8 m, după retehnologizare se găsesc mai multe puncte cu E > 10 kV/m, dar aceste valori sunt în limite normale pentru noile echipamente de 220 kV.

  15. Observaţii: Valorile E >10 kV/m găsite în 2007 sunt comparabile cu cele din 2003 şi se justifică prin echipamentul primar montat în retehnologizare.

  16. Observaţii: Valorile E> 10 kV/m se găsesc în 2007 într-un număr mai mic decât în 2003 şi se justifică prin echipamentul primar montat la retehnologizare.

  17. Observaţii: Valorile E >10 kV/m găsite în 2007 sunt comparabile cu cele din 2003 şi se justifică prin echipamentul primar montat în retehnologizare.

  18. Observaţii: Valorile E >10 kV/m se găsesc în 2007 într-un număr de puncte mare deoarece s-au făcut măsurători în întreaga staţie comparativ cu cele efectuate în 2003 care au cuprins numai o parte din staţie.

  19. Observaţii: În 2003 s-au efectuat măsurători în jumătate din staţie. În 2007 s-au efectuat măsurători în întreaga staţie. Valorile E >10 kV/m găsite în 2007 sunt comparabile cu cele din 2003 şi se justifică prin echipamentul primar montat în retehnologizare.

  20. Observaţii: În 2003 s-au efectuat măsurători numai în două celule din staţie. În 2007 s-au efectuat măsurători în 12 celule din staţie. Cele 2 puncte de măsură cu E ≈10 kV/m găsite în apropierea unor întreruptoare cu SF6 ar putea fi rezultatul unei înălţimi faţă de sol a cordoanelor de legătură la barele staţiei .

  21. Comparatie a masuratorilor masuratorilor de noxe chimice in acele statii retehnologizate din ST Craiova unde s-au efectuat masuratori atat in anul 2003 cat si in anul 2007

  22. Observatii:Avand in vedere lucrarile de retehnologizare pentru instalatiile si echipamentele statiilor electrice de transformare Portile de Fier, Tantareni si Urechesti desfasurate in perioada 2003-2007, variatia CO este mult imbunatatita datorita noilor echipamente precum si lucrarilor de modernizare. Pentru compararea concentratiei CO determinat s-au analizat masuratorile efectuate de catre ICEMENERG urmarindu-se pe cat posibil aceleasi puncte de masura .

  23. Comparatie a masuratorilor zgomot in acele statii retehnologizate din ST Craiova unde s-au efectuat masuratori atat in anul 2003 cat si in anul 2007

  24. Nota : pct. nr. 9 din graficul de zgomot statia electrica Portile de Fier reprezinta valoarea determinata pentru Grupul Diesel in functiune, care este amplasat intr-o incinta inchisa. Personalul care deserveste aceasta statie este obligat ca in momentul functionarii Grupului Diesel sa poarte echipamentul individual de protectie.

  25. Nota : pct. nr. 5 din graficul de zgomot statia electrica Tantareni reprezinta valoarea determinata pentru Grupul Diesel in functiune, care este amplasat intr-o incinta inchisa. Personalul care deserveste aceasta statie este obligat ca in momentul functionarii Grupului Diesel sa poarte echipamentul individual de protectie.

  26. Nota : pct. nr. 6 din graficul de zgomot statia electrica Urechesti reprezinta valoarea determinata pentru Grupul Diesel in functiune, care este amplasat intr-o incinta inchisa. Personalul care deserveste aceasta statie este obligat ca in momentul functionarii Grupului Diesel sa poarte echipamentul individual de protectie.

  27. Observatii: Avand in vedere lucrarile de retehnologizare pentru instalatiile si echipamentele statiilor electrice de transformare Portile de Fier, Tantareni si Urechesti desfasurate in perioada 2003-2007, situatia nivelelor de zgomot este mult imbunatatita datorita noilor echipamente precum si lucrarilor de modernizare si reconfigurare a schemelor de functionare.Pentru compararea nivelelor de zgomot determinate s-au analizat masuratorile efectuate de catre ICEMENERG urmarindu-se pe cat posibil aceleasi puncte de masura chiar si in situatia modificarii configuratiei statiilor.

  28. Concluzii privind rezultatele obtinute : A. Pentru camp electric si magnetic : Măsurătorile de câmp electric şi magnetic s-au efectuat pe timp frumos nedepăşindu-se valoarea maximă admisibilă a umidităţii aerului de 80%; La statiile electrice de 400 kV retehnologizate se poate constata pana in prezent ca valorile gradientului de potential la sol din apropierea echipamentelor de protectie au valori mai reduse decat in situatia statiilor electrice neretehnologizate; Valorile măsurate ale intensităţii câmpului electric depăşesc în unele puncte din instalaţie valoarea maximă admisibilă pentru medii profesionale de 10 kV/m şi sunt marcate cu roşu; Valorile măsurate ale inducţiei câmpului magnetic nu depăşesc valoarea maximă admisibilă pentru medii profesionale de 500 µ.

  29. B. Pentru noxe chimice : Rezultatele determinarilor efectuate (CO, SO2, NOx, ulei mineral,hidrocarburi alifatice) in statiile electrice din ST Craiova evidentiaza faptul ca nu exista depasiri de noxe chimice; Prezenta in majoritatea cazurilor a CO in atmosfera in diverse incaperi (sub valoarea maxima admisibila) impune folosirea ferestrelor termopan tip fagure, iar aerisirea incaparilor trebuie facuta 20 min/8 ore; Inlocuirea intreruptoarelor IO care aveau in componenta mecanismele de actionare tip MOP cu intreruptoare cu hexaflorura au condus la eliminarea scurgerilor de ulei mineral si infiltrarea acestuia in sol in vecinatatea intreruptoarelor. In aceste conditii personalul de deservire este scutit de controarele obligatorii (zilnice) privind functionarea corecta a MOP-uri si in acelasi timp de inhalarea vaporilor de ulei mineral degajat.

  30. C. Pentru zgomot si vibratii : Masuratorile efectuate arata ca nivelele de zgomot se incadreaza in limita admisibila de 87dB(A), pentru majoritatea punctelor de masura situate pe amplasamentul statiilor electrice din ST Craiova, cu exceptia incintelor unde sunt amplasate grupurile electrogene (Grup Diesel) si compresoarele (acestea sunt amplasate in cladiri separate), iar expunerea personalului la acest nivel de zgomot ridicat este minima, deoarece grupul se porneste, de regula, cca. 10 min. o data pe saptamana. De asemenea functionarea compresorilor este intermitenta. Inlocuirea Grupului Diesel vechi cu unul modern, a condus la reducerea consistenta a nivelului de zgomot. La statiile de transformare care au grupurile electrogene sau statiile de compresoare aplasate in exterior (acestea sunt de obicei carosate) nu a fost determinat nivelul de zgomot deoarece riscul expunerii personalului la zgomotul generat este redus.

  31. Inlocuirea sistemelor de actionare tip MOP in statiile retehnologizate a dus la reducerea nivelului global de zgomot pe caile de acces ale acestora. Personalul executant este supus unui risc mai mic in ceea ce priveste nivelul de zgomot. Concluzia este ca la toate statiile electrice apartinand de ST Craiova nu se constata depasiri in ceea ce priveste expunerea personala zilnica (8 ore) la zgomot cu exceptia incintelor unde sunt amplasate grupurile electrogene sau compresoarele.

  32. Valorile masurate in cazul vibratiilor ne arata ca acestea sunt cu mult sub valorile maxime admisibile pentru locurile de munca care necesita o solicitare neuropsihica si psihosenzoriala crescuta si cu atat mai mult pentru locurile de munca obisnuite, care necesita o solicitare neuropsihica si psihosenzoriala normala. Concluzia este aceeasi ca la zgomot: nu exista depasiri in ceea ce priveste expunerea personala zilnica (8 ore) la vibratii.

  33. Masuri tehnico-organizatorice de protectie a influentei noxelor la locurile de munca din ST Craiova A. Pentru camp electric si magnetic : Principalele măsuri tehnico-organizatorice sunt : reducerea timpului de staţionare în câmpul electric; staţionarea personalului se permite numai pe durata efectuării de lucrări în instalaţii; montarea de plăcuţe avertizoare în locurile cu E > 10 kV/m. Plăcuţele vor fi vopsite în culoare galbenă şi inscripţionarea lor se va efectua în culoare roşie; instalarea în cazuri bine justificate, de exemplu la executarea de lucrări sistematice sau de durată, a unor ecrane metalice la locurile de muncă (ecrane fixe sau cu caracter temporar); instruirea personalului pentru a cunoaşte cu precizie locurile din instalaţiile electrice cu câmp electric E > 10 kV/m şi de a evita staţionarea nejustificată în acele locuri; interzicerea pătrunderii sau rămânerii personalului în zonele cu E > 10 kV/m în timpul pauzelor de masă, odihnă sau alte activităţi nelucrative; folosirea de mănuşi electroizolante de către personal pentru protejarea împotriva curenţilor capacitivi de descărcare care apar la contactul cu părţile legate la pământ când purtătorul se află plasat în câmp electric cu E > 10 kV/m.

  34. B. Pentru noxe chimice : Principalele măsuri tehnico-organizatorice sunt :- prezenta in majoritatea cazurilor a CO in atmosfera in diverse incaperi (sub valoarea maxima admisibila) impune folosirea ferestrelor termopan tip fagure, iar aerisirea incaparilor trebuie facuta 20 min/8 ore.

  35. C . Pentru zgomot si vibratii :Intrucat nu exista depasiri in ceea ce priveste expunerea personala zilnica (8 ore) la zgomot si vibratii, nu se impun masuri tehnico-organizatorice deosebite. Totusi, acolo unde este cazul, pentru zgomot se impun urmatoarele masuri tehnico-organizatorice :Angajatii vor fi informati privind locurile in care exista depasiri ale limitei maxime admise si riscurile potentiale pentru auzul lor datorita expunerii la zgomot;In aceste locuri se va reduce timpul de staţionare a personalului, aceasta permitandu-se numai pe durata efectuării de lucrări în instalaţii;Aceste locuri vor marcate cu panouri care sa arate ca purtarea echipamentului individual de protectie impotriva zgomotului este obligatorie in cazul in care durata de expunere zilnica depaseste 8 ore, conform Prescriptiilor minime pentru semnalizarea de securitate si/sau sanatate la locul de munca;In cazul in care in aceste locuri este necesar sa se efectueze lucrări în instalaţii pe perioade mai mari, astfel incat expunerea saptamanala medie la zgomot depaseste limita maxima admisa, angajatorul va trebui sa puna la dispozitia angajatilor echipamente individuale de protectie impotriva zgomotului;Se recomanda ca la pornirea si oprirea grupurilor Diesel sa se poarte echipamentul individual de protectie impotriva zgomotului, chiar daca expunerea este de scurta durata.