SPP Local Area 2 Sub Regional Meeting Jason Fortik August 3, 2010

SPP Local Area 2 Sub Regional Meeting Jason Fortik August 3, 2010. Lincoln Electric System. Publicly-Owned Municipal Utility – Serving Approximately 200 Square miles within Lancaster County NE. Governed by LES Administrative Board The City Council approves rates, budget and debt financing

arvin
Télécharger la présentation

SPP Local Area 2 Sub Regional Meeting Jason Fortik August 3, 2010

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. SPP Local Area 2Sub Regional MeetingJason FortikAugust 3, 2010

  2. Lincoln Electric System • Publicly-Owned Municipal Utility – Serving Approximately 200 Square miles within Lancaster County NE. • Governed by LES Administrative Board • The City Council approves rates, budget and debt financing • Approximately 128,800 retail customers • Retail Energy Sales – 3.1 billion kWh • Peak Demand – 779 MW (2006) • LES Revenues - $245.7 million • Overall Average rate 7.00 cents/kWh

  3. Forecast Peak Loads • 2010 – 750 MW • 2020 – 835 MW (average 1.1% growth) • 2010 Long Range Forecast for 2020 is 66 MW lower than the 2009 forecast

  4. LES Electric System Summary Transmission • 76 circuit miles of 345 kV lines; • 12 circuit miles of 161 kV lines; • 197 circuit miles of 115 kV lines; Distribution – • 1,921 circuit miles of 35 kV and 12 kV primary distribution lines;

  5. Local Planning Criteria • Normal Operation-no outages • All facilities within normal ratings • All voltages between .95 and 1.05pu • Single contingency from normal • All facilities within normal ratings • All voltages between .95 and 1.05pu • Another contingency after a single contingency • All facilities within Emergency ratings • All voltages between .95 and 1.05pu • System can readjust to normal

  6. Transfer of Load at West Lincoln to 115/12kV from 115/35kV • Add NW 70th & Fairfield Substation in the year 2012 with 115/12kV transformer • Retire 35kV substations at NW 38th & Cumming and NW 48th & Adams • Retire West Lincoln 115/35kV Transformer T082 in the year 2014 • Retire West Lincoln 115/35kV Transformer T083 in the year 2018

  7. 115kV line from 57th & Garland to 84th & Leighton • Project: rebuild a 2-mile overhead 115kV line • Reason: age and need for a higher thermal capacity • Expected Complete Date: 2012

  8. 115kV line from 17th & Holdrege to 21st & N to 30th & A to 56th & Everett • Project: replace 115kV underground cable with new 115kV overhead line • Reason: age • Expected Complete Date: 2012 thru 2016

  9. 115kV line from Sheldon to 20th & Pioneers and 115kV Folsom & Pleasant Hill Substation • Project: rebuild a 115kV overhead line • Project: add a 115kV substation and re-terminate 115kV lines • Reason: age, need for a higher thermal capacity, and need for a new substation • Expected Complete Date: 2010 thru 2012

  10. 115kV line from SW7th & Bennet to 40th & Rokeby • Project: Construct a new 115kV overhead line • Reason: Future System Growth • Expected Complete Date: 2014

  11. Contact information: LES Website: www.les.com Jason Fortik, Resource & Transmission Planning Manager Phone: (402) 473-3380 jfortik@les.com Alan Burbach, Senior Engineer Phone: (402) 473-3374 aburbach@les.com