An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. EEE 302Electrical Networks II Dr. Keith E. Holbert Summer 2001 Lecture 10

  2. Source/Load Connections • The equivalent load may be in an equivalent delta () or wye (Y) configuration • the delta load configuration has no neutral line • the current is zero in the neutral line for a balanced wye load configuration • Source/Load connections can be connected in any of the possible combinations: Ysource-Yloadsource-Yload Ysource-loadsource- load • Analysis prefers the first connection (Y-Y) Lecture 10

  3. Balanced Wye-Wye Connection a ZY Van + – b ZY + – Vbn c ZY + – Vcn n Load Lecture 10

  4. Balanced Wye-Wye Connection • The line-to-line voltages (or line voltages) are Vab = VP3 30° Vbc = Vab-120° Vca = Vab-240° where VP is the magnitude of the phasor voltage between any two lines • The magnitude of the line voltage is VL = VP3 Lecture 10

  5. Balanced Wye-Wye Connection • The line current for phase a is Ia = Van / ZY = Vp0° / ZY • In a Y-Y connection the magnitude of the line current (IL) equals the magnitude of the load current (IY) • The neutral current In is In = Ia + Ib + Ic = 0 • Balanced Y-Y three-phase ac circuits may be analyzed on a per phase basis Lecture 10

  6. Balanced Wye-Delta Connection Van a + – Z Vbn b + – n Z Z Vcn c + – Load Lecture 10

  7. Summarizing • A very good summary appears on pages 568-9 of the textbook including a figure and table for explanation Lecture 10

  8. Class Examples • Extension Exercise E10.1 • Extension Exercise E10.2 Lecture 10

  9. Three-Phase Power Relationships • The real and reactive power per phase are • The total real, reactive, and complex powers are Lecture 10

  10. Class Examples • Extension Exercise E10.8 • Extension Exercise E10.10 Lecture 10