MCQUAY DIGITAL SCROLL SYSTEM

MCQUAY DIGITAL SCROLL SYSTEM. Troubleshooting. SELF DIAGNOSIS. MDS Outdoor Unit. SELF DIAGNOSIS. MDS Outdoor Unit. Compressor Protection High & low pressure switch / Sensor Overload protection input from compressor. Monitoring Point (Temperature Sensor) Compressor Discharge

collice
Télécharger la présentation

MCQUAY DIGITAL SCROLL SYSTEM

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. MCQUAY DIGITAL SCROLL SYSTEM Troubleshooting

  2. SELF DIAGNOSIS MDS Outdoor Unit

  3. SELF DIAGNOSIS MDS Outdoor Unit • Compressor Protection • High & low pressure switch / Sensor • Overload protection input from compressor • Monitoring Point (Temperature Sensor) • Compressor Discharge • Compressor Suction • Ambient Temperature • Coil Inlet • Coil • Coil Outlet • Compressor

  4. SELF DIAGNOSIS 7 segment display on outdoor PCB

  5. 7 Segment Display on outdoor PCB SELF DIAGNOSIS Indicator Code

  6. LED of outdoor PCB SELF DIAGNOSIS ERROR Code

  7. SELF DIAGNOSIS MDS Indoor Unit • Temperature Sensor • Coil Inlet • Coil • Coil Outlet • Return air

  8. LCD Indicator of controller SELF DIAGNOSIS ERROR Code

  9. LED Indicator of Receiver SELF DIAGNOSIS ERROR Code Indication light twinkle related to malfunction code :

  10. TROUBLESHOOTING Frequent Malfunction for Commissioning – Communication Error Symptom: For A series Outdoor, the 7 segment display C- For B series Outdoor, the 7 segment display EC78 For Wired Handset, the LCD panel display FC For LED Display, the Heat LED will be blinking Potential Caused A: The communication chip MAX485 of outdoor unit is damaged (Possibility is low. The Communication is tested before ship out) Solution: To replace the MAX485 chip Potential Caused B: The communication wires A/B get crossed each other or not connected (Most common caused) Solution: Check on all wiring. Ensure proper tighten and the polarity is consistent.

  11. TROUBLESHOOTING Frequent Malfunction for Commissioning – Communication Error (cont’) Potential Caused C: Shielding wire is connected to ground terminal (not grounded). (Long wiring and running the communication wire together with power supply wire will cause this to happen) Solution: Ensure the shielding wire is only grounded at the outdoor unit. Do not run the communication wire with the power supply wire together. Potential Caused D: Address of indoor are wrongly set (Caution, the indoor address must be start at ‘0000’ and follow. Do no jump the number.) Solution: Make sure the address start from ‘0000, did not skip any address and no repetition.

  12. TROUBLESHOOTING Frequent Malfunction for Commissioning – Specific Indoor Communication Error Symptom: For A series Outdoor, the 7 segment display CX (X – Indoor Unit Number) For B series Outdoor, the 7 segment display ECXX (XX – Indoor Unit Number) For Wired Handset, the LCD panel display FC For LED Display, the Heat LED will be blinking Example: For A series Outdoor, the 7 segment display C3 (Indoor Unit Number 4 not communicating) For B series Outdoor, the 7 segment display EC03 (Indoor Unit Number 4 not communicating)

  13. TROUBLESHOOTING Frequent Malfunction for Commissioning – Specific Indoor Communication Error (cont’) Potential Caused A: Indoor Unit PCB has no power supply. (Possible the power supply to the indoor had been turned off) Solution: Check the power supply of the indoor power. Potential Caused B: Indoor Unit address error. (Possible the indoor address is not set or duplication) Solution: Check the indoor model address.

  14. TROUBLESHOOTING Frequent Malfunction for Commissioning – Specific Indoor Communication Error (cont’) Potential Caused C: Indoor Unit PCB malfunction. (Possibility is low. PCB communication is tested before ship out.) Solution: Replace with another PCB and check the communication Potential Caused D: Wrong quantity of indoor set. (Possible the quantity of indoor unit set in the outdoor PCB is not tally with the actual indoor quantity) Solution: Check the quantity of indoor unit setting at the outdoor PCB.

  15. TROUBLESHOOTING If the followings malfunction occurred, please follow the steps below to resolve :

  16. Thank You