1 / 17

Radon in the Air:

Radon in the Air:. Why Dilution may not always be a Solution Winnie Cheng, Regional Radiation Specialist AARST 2014 International Radon Symposium Charleston, South Carolina September 30, 2014. Radon in the Air: Outline.

Télécharger la présentation

Radon in the Air:

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Radon in the Air: Why Dilution may not always be a Solution Winnie Cheng, Regional Radiation Specialist AARST 2014 International Radon Symposium Charleston, South Carolina September 30, 2014

  2. Radonin the Air: Outline • The Canadian Regulations & Guidelines; Occupational & Environmental Exposure • Case Study • Lessons Learned Rn 2

  3. Occupational Exposure: Regulations • Nuclear Safety & Control Act (Canadian Nuclear Safety Commission): • Nuclearfacilities and materials 3

  4. Canadian Guidelines for the Management of Naturally Occurring Radioactive Materials (NORM): Uranium Thorium Potassium Any of their radioactive decay products, such as radium and radon) Jurisdiction over the use and radiation exposure to NORM rests with each Canadian province and territory Occupational Exposure: Guidelines 4

  5. NORMIndustries: mineralextraction and processing oil and gas production metal recycling forest products and thermal-electric production tunnelling and underground workings water treatmentfacilities Occupational Exposure: Guidelines 5

  6. Workplace Environmental Exposure • Canada Labor Code • General workplaces of federal building should not be >800 Bq/m3 (21.6 pCi/L)—is currently under review 6

  7. Canadian Regulations & Guidelines Occupational Exposure Ionizing Radiation Environmental (Workplace) Exposure Radon • Federal Law: Canada Labour Code (Workplace): • Radon: 800 Bq/m3 (21.6 pCi/L) • Federal Law: Nuclear Safety & Control Act • Nuclear mines Federal Guidelines Federal Guidelines • HC Radon Guideline (Workplace): • 200 Bq/m3 (5.4 pCi/L) • HC NORM Guidelines (Occupational) 7

  8. Radon in the Air: Non-residential Building “Radon in the Air?” Case Study Rn 8

  9. Radon in the Air: Non-residential Building Features • Slab on grade • >1,000 m2 • Numerous “rooms + open spaces” Radon In some rooms >200 Bq/m3(>5.4pCi/L) With one room >5,000 Bq/m3(137 pCi/L) 9

  10. Radonin the Air: Mitigation Actions • Stage 1: • Sealed pipe penetrations, and cracks on floors and walls • Set dampers to increase the outdoor air ventilation • Installed a new HVAC system to improve the overall ventilation • Stage 2: • HVAC adjustments: 24/7 • Stage 3: • Achieved positive indoor pressure • Further sealing of perimeter walls 10

  11. Radon in the Air: Considerations • Dilution is the solution via ventilation does not apply where • There are multiple sources of entry • Radon level is very high • Key: • Achieving positive indoor pressure • Having all occupied rooms tested at once • Testing enclosed areas that are outside of the HVAC system may help identify various entry points and the need of other mitigation actions 11

  12. Risk Management: NORM Program Canadian Guidelines for the Management of Naturally Occurring Radioactive Materials (NORM) 12

  13. Risk Management: NORM Program 13

  14. RadonRisk Communication • Employers should have their workplaces tested in order to ensure that workers are not exposed to high levels of radon, and to conform to guidelines set out by the appropriate jurisdictions. • In radon prone areas, employees could also be receiving significant exposure at home. • Staff who live in radon prone areas are encouraged to test their homes. • The need for protection against radon both at home and at work. 14

  15. Lessons Learned • “Dilution is the solution” – may not be applicable in reducing high levels of radon or when there are multiple entry routes. • Adjustment of the HVAC system should be considered along with achieving a positive indoor pressure to effectively reduce the radon levels. • Check rooms that are outside of the HVAC system; may need to consider a separate radon reduction system such as an Active Sub-slab Depressurization Unit. 15

  16. Conclusion • Where applicable, employers should consider the NORM Guidelines for radon risk management and protection of workers while mitigation is underway. • Once remedial work is completed, a long term post-remediation measurementmust be carried out in the building to ensure that radon concentrations are below 200 Bq/m3. • Precautionary principle: To reduce radon below 200 Bq/m3 or to as low as reasonably achievable (ALARA). 16