ESPECIFICACIONES DE MEDICION PARA ACOMETIDAS TRIFASICAS

CFE EM-BT301 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, CON BARDA FRONTAL CFE EM-BT302 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD

derick
Télécharger la présentation

ESPECIFICACIONES DE MEDICION PARA ACOMETIDAS TRIFASICAS

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. CFE EM-BT301 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, CON BARDA FRONTAL CFE EM-BT302 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT303 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED AEREA, CON BARDA FRONTAL CFE EM-BT304 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT305 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANADA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, CON BARDA FRONTAL CFE EM-BT306 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT307 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED SUBTERRANEA, CON BARDA FRONTAL CFE EM-BT308 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED SUBTERRANEA, CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT309 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANADA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, EN ZONAS DE ARQUITECTURA COLONIAL CFE EM-BT310 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, EN ZONAS DE ARQUITECTURA COLONIAL CFE EM-BT3 ESPECIFICACIONES DE MEDICION PARA ACOMETIDAS TRIFASICAS

  2. 1 3 7 ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, CON BARDA FRONTAL CFE EM-BT301 HOJA 1 DE 2 #310 VISTA DE CONJUNTO F1 F1 2 F2 F2 F3 F3 N N 500 mm DELONGITUD #310 6 5 4800 12 C F E 13 4 1800 PARA CONEXIONES ENLA BASE ENCHUFEVER DETALLE 8 9 10 11 VISTA LATERAL VISTA FRONTAL

  3. 5 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, CON BARDA FRONTAL CFE EM-BT301 HOJA 2 DE 2 ESPECIFICACIONES DE MATERIALES Y EQUIPO DE LA ACOMETIDA F3F2F1 N A CARGO DEL USUARIO 2 1 MUFA INTEMPERIE DE 38 mm (1 1/2") DE DIAMETRO 2 TUBO CONDUIT DE FIERRO GALVANIZADO PARED GRUESA DE 38 FFFmm (1 1/2")DE DIAMETRO Y CON 3000 mm DE LONGITUD3 CABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE A CALIBRES Y DEMANDAS, DESDE LA MUFA HASTA EL . INTERRUPTOR,EL FORRO DEL CONDUCTOR NEUTRO DE . COLOR BLANCO Y LOSDE LAS FASES DIFERENTES AL BLANCO4 BASE ENCHUFE DE 7 TERMINALES, 100 AMPERES TIPO AEREA A A A CON TAPA 5 INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS,100 FFFAMPERES A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIE 6 MONITOR Y CONTRATUERCA DE 38 mm (1 1/2")7 REDUCCION DE 38 mm (1 1/2") A 12,7 mm (1/2")8 TUBO CONDUIT PARED DELGADA DE 12,7 mm (1/2") DE DIAMETRO9 ALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMO 10 CONECTOR PARA VARILLA DE TIERRA 11 VARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS 4 A INSTALACIONINTERIOR 6 A VARILLADE TIERRA DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR INSTALADO POR C.F.E. MEDIDOR TIPO ENCHUFE DE 15(100) AMPERES, 3 FASES, 4 HILOS, 120 VOLTS (FD21)SELLO DE PLASTICO 1213 AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBE SALIR COMO MINIMO 10 mm DEL MURO PARA COLOCAR EL MEDIDOR Y LA TAPA NOTAS : TAPA DE LA BASE A LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO MAXIMO A 35 METROS DEL POSTE DESDE EL CUAL SE DARA EL SERVICIO B EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) C LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE PROPIEDAD, EMPOTRADA O SOBREPUESTA D EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCION E LA ALTURA DE LA MUFA PARA RECIBIR LA ACOMETIDA ES DE 4800 mm F EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR G MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE MURO DETALLE DE EMPOTRADO DE BASE 4 PROPIEDADDEL USUARIO VIAPUBLICA MEDIDOR VISTA DE PLANTA ACOTACIONES EN mm SIN ESCALA

  4. ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT302 HOJA 1 DE 2 VISTA DE CONJUNTO 3 1 F1 F2 N F1 F3 N F2 F3 500 mm DELONGITUD 2 220 MINIMO 300 MINIMO MURETEDECONCRETO MURETE ARMADO DE CONCRETO Y VARILLA 12 4800 4 13 13 C F E 2800 MINIMO 14 5 1800 7 8 A INSTALACIONINTERIOR 10 9 A INSTALACIONINTERIOR CIMIENTO DE PIEDRA CON CEMENTO Y ARENA 11 VISTA LATERAL VISTA FRONTAL

  5. 5 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT302 HOJA 2 DE 2 ESPECIFICACIONES DE MATERIALES Y EQUIPO DE LA ACOMETIDA F3F2F1 N A CARGO DEL USUARIO 2 1 MUFA INTEMPERIE DE 38 mm (1 1/2") DE DIAMETRO 2 TUBO CONDUIT DE FIERRO GALVANIZADO PARED GRUESA DE 38 FFFmm (1 1/2")DE DIAMETRO Y CON 3000 mm DE LONGITUD 3 CABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE CALIBRES . Y DEMANDAS DESDE LA BASE HASTA EL INTERRUPTOR, EL . FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y LOS DE . LAS FASES DIFERENTES AL BLANCO 5 INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS,100 FFFAMPERES A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIE 6 MONITOR Y CONTRATUERCA DE 38 mm ( 1 1/2”) 7 REDUCCION DE 38 mm (1 1/2") A 12,7 mm (1/2")8 TUBO CONDUIT PARED DELGADA DE 12,7 mm (1/2") DE DIAMETRO9 ALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMO 10 CONECTOR PARA VARILLA DE TIERRA 11 VARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS 12 MURETE DE ACUERDO A LO INDICADO 4 A INSTALACIONINTERIOR 6 A VARILLADE TIERRA DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR INSTALADO POR C.F.E. AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBERA SALIR COMO MINIMO 10 mm DEL MURO PARA COLOCAR EL MEDIDOR Y LA TAPA MEDIDOR TIPO ENCHUFE DE 15(100) AMPERES, 3 FASES, 4 HILOS, 120 VOLTS (FD21)SELLO DE PLASTICO 1314 NOTAS : BASE ENCHUFE A LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO MAXIMO A 35 METROS DEL POSTE DESDE EL CUAL SE DARA EL SERVICIO B EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) C LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE PROPIEDAD, EMPOTRADA O SOBREPUESTA D EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCION E LA ALTURA DE LA MUFA PARA RECIBIR LA ACOMETIDA ES DE 4800 mm F EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR G MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE TAPA DE LA BASE MURO DECONCRETO DETALLE DE EMPOTRADO DE LA BASE PROPIEDADDEL USUARIO VIAPUBLICA MEDIDOR VISTA DE PLANTA ACOTACIONES EN mm SIN ESCALA

  6. 1 3 7 ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED AEREA, CON BARDA FRONTAL CFE EM-BT303 HOJA 1 DE 2 #310 VISTA DE CONJUNTO F1 F1 2 F2 F2 F3 F3 N N 500 mm DELONGITUD #310 6 5 4800 12 C F E 13 4 1800 PARA CONEXIONES ENLA BASE ENCHUFEVER DETALLE 8 9 10 11 VISTA LATERAL VISTA FRONTAL

  7. 5 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED AEREA, CON BARDA FRONTAL CFE EM-BT303 HOJA 2 DE 2 ESPECIFICACIONES DE MATERIALES Y EQUIPO DE LA ACOMETIDA F3F2F1 N A CARGO DEL USUARIO 2 1 MUFA INTEMPERIE DE 63.5 mm (2 1/2") DE DIAMETRO 2 TUBO CONDUIT DE FIERRO GALVANIZADO PARED GRUESA DE63.5 . mm (2 1/2")DE DIAMETRO Y CON 3000 mm DE LONGITUD3 CABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE .CALIBRES Y DEMANDAS, DESDE LA MUFA HASTA EL INTERRUPTOR, . EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y LOS .DE LAS FASES DIFERENTES AL BLANCO4 BASE ENCHUFE DE 7 TERMINALES, 200 AMPERES TIPO AEREA A A A CON TAPA 5 INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS, 200 FF AMPERES A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIE 6 MONITOR Y CONTRATUERCA DE 63.5 mm (2 1/2")7 REDUCCION DE 63.5 mm (2 1/2") A 12,7 mm (1/2")8 TUBO CONDUIT PARED DELGADA DE 12,7 mm (1/2") DE DIAMETRO9 ALAMBRE O CABLE DE COBRE DE CALIBRE SEGÚN LA TABLA DE CALIBRES Y DEMANDAS 10 CONECTOR PARA VARILLA DE TIERRA 11 VARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS 4 A INSTALACIONINTERIOR 6 A VARILLADE TIERRA DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR INSTALADO POR C.F.E. MEDIDOR TIPO ENCHUFE DE 30(200) AMPERES, 3 FASES, 4 HILOS, 120 - 480 VOLTS (KL28)SELLO DE PLASTICO 1213 AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBE SALIR COMO MINIMO 10 mm DEL MURO PARA COLOCAR EL MEDIDOR Y LA TAPA NOTAS : TAPA DE LA BASE A LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO MAXIMO A 35 METROS DEL POSTE DESDE EL CUAL SE DARA EL SERVICIO B EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) C LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE PROPIEDAD, EMPOTRADA O SOBREPUESTA D EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCION E LA ALTURA DE LA MUFA PARA RECIBIR LA ACOMETIDA ES DE 4800 mm F EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR G MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE 13 MURO DETALLE DE EMPOTRADO DE BASE 4 PROPIEDADDEL USUARIO VIAPUBLICA MEDIDOR VISTA DE PLANTA ACOTACIONES EN mm SIN ESCALA

  8. ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT304 HOJA 1 DE 2 #305 VISTA DE CONJUNTO 3 1 F1 F2 N F1 F3 N F2 F3 500 mm DELONGITUD 2 220 MINIMO 300 MINIMO MURETEDECONCRETO MURETE ARMADO DE CONCRETO Y VARILLA 12 4800 4 13 13 C F E 2800 MINIMO 14 5 1800 7 8 A INSTALACIONINTERIOR 10 9 A INSTALACIONINTERIOR CIMIENTO DE PIEDRA CON CEMENTO Y ARENA 11 VISTA LATERAL VISTA FRONTAL

  9. 5 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT304 HOJA 2 DE 2 ESPECIFICACIONES DE MATERIALES Y EQUIPO DE LA ACOMETIDA F3F2F1 A CARGO DEL USUARIO N 2 1 MUFA INTEMPERIE DE 63.5 mm (2 1/2") DE DIAMETRO 2 TUBO CONDUIT DE FIERRO GALVANIZADO PARED GRUESA DE 63.5 mm (2 1/2")DE DIAMETRO Y CON 3000 mm DE LONGITUD3 CABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE A CALIBRES Y DEMANDAS, DESDE LA MUFA HASTA EL . INTERRUPTOR, A EL FORRO DEL CONDUCTOR NEUTRO DE . COLOR BLANCO Y LOS DE LAS FASES DIFERENTES AL BLANCO4 BASE ENCHUFE DE 7 TERMINALES, 200 AMPERES TIPO AEREA A A A CON TAPA 5 INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS, 200 FFFAMPERES A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIE 6 MONITOR Y CONTRATUERCA DE 63.5 mm ( 2 1/2”)7 REDUCCION DE 63.5 mm (2 1/2") A 12,7 mm (1/2") 8 TUBO CONDUIT PARED DELGADA DE 12,7 mm (1/2") DE DIAMETRO9 ALAMBRE O CABLE DE COBRE CALIBRE SEGÚN LA TABLA DE . CALIBRES Y DEMANDAS 10 CONECTOR PARA VARILLA DE TIERRA 11 VARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS 12 MURETE DE ACUERDO A LO INDICADO 4 A INSTALACIONINTERIOR 6 A VARILLADE TIERRA DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR INSTALADO POR C.F.E. AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBERA SALIR COMO MINIMO 10 mm DEL MURO PARA COLOCAR EL MEDIDOR Y LA TAPA MEDIDOR TIPO ENCHUFE DE 30(200) AMPERES, 3 FASES, 4 HILOS, 120 - 480 VOLTS (KL28)SELLO DE PLASTICO 1314 NOTAS : BASE ENCHUFE A LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO MAXIMO A 35 METROS DEL POSTE DESDE EL CUAL SE DARA EL SERVICIO B EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) C LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE PROPIEDAD, EMPOTRADA O SOBREPUESTA D EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCION E LA ALTURA DE LA MUFA PARA RECIBIR LA ACOMETIDA ES DE 4800 mm F EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR G MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE TAPA DE LA BASE MURO DECONCRETO DETALLE DE EMPOTRADO DE LA BASE PROPIEDADDEL USUARIO VIAPUBLICA MEDIDOR VISTA DE PLANTA ACOTACIONES EN mm SIN ESCALA

  10. ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANADA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, CON BARDA FRONTAL CFE EM-BT305 HOJA 1 DE 2 #411 C F E DUCTO RED B.T. DUCTO RED B.T. REGISTRO DE ACOMETIDAEN B.T. VISTA DE CONJUNTO 4 11 C F E 5 12 6 1800 1800 7 2 13 VER DETALLE "A" 8 1 9 10 SECUNDARIO DE LA RED VISTA FRONTAL VISTA LATERAL

  11. 5 DISPONIBLES 15 14 ACOMETIDA SECUNDARIODE LA RED ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANADA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, CON BARDA FRONTAL CFE EM-BT305 HOJA 2 DE 2 ESPECIFICACIONES DE MATERIALES Y EQUIPO A CARGO DEL USUARIO 3 1 CODO DE PVC 38 mm ( 1 1/2” ) DE DIAMETROTUBO RIGIDO DE PVC 38 mm ( 1 1/2” ) DE DIAMETROCABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE CALIBRES Y DEMANDAS DESDE LA BASE HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y LOS DE LAS FASES DIFERENTES AL BLANCOBASE ENCHUFE DE 7 TERMINALES, 100 AMPERES INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS, 100 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE PVC 38 mm (1 1/2") A 12,7 mm (1/2")TUBO RIGIDO PVC DE 12.7 mm ( 1/2” ) DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMOCONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS 2 3 4 A INSTALACIONINTERIOR 4 5 A VARILLADE TIERRA 2 DEL REGISTRO 6 7 8 9 10 DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR INSTALADO POR C.F.E. AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBERA SALIR COMO MINIMO 10 mm DEL MURO PARA COLOCAR EL MEDIDOR Y LA TAPA 11 MEDIDOR TIPO ENCHUFE DE 15(100) AMPERES, 3 FASES, 4 HILOS, 120 VOLTS (FD21) SELLO DE PLASTICO CABLE DE ALUMINIO XLP A LA BASE ENCHUFE CONECTOR EMPALME A COMPRESION TENSION MINIMA TIPO ZAPATA MANGA TERMOCONTRACTIL O REMOVIBLE 12 13 14 BASE ENCHUFE 15 TAPA DE LA BASE NOTAS : MURO DECONCRETO A. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO MAXIMO A 35 METROS DEL REGISTRO. B. EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) C. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE LA PROPIEDAD EMPOTRADA D. EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCIONE. EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR F. MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE DETALLE DE EMPOTRADO DE LA BASE DETALLE “A” PROPIEDADDEL USUARIO VIAPUBLICA MEDIDOR VISTA DE PLANTA ACOTACIONES EN mm SIN ESCALA

  12. ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT306 HOJA 1 DE 2 #435 DUCTO RED DE BAJA TENSION VISTA DE CONJUNTO 220 300 5 13 11 2 2000 1800 14 8 VISTA FRONTAL VISTA LATERAL

  13. 5 DISPONIBLES 16 15 ACOMETIDA SECUNDARIODE LA RED ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT306 HOJA 2 DE 2 ESPECIFICACIONES DE MATERIALES Y EQUIPO A CARGO DEL USUARIO 3 CODO DE PVC 38 mm ( 1 1/2” ) DE DIAMETROTUBO RIGIDO DE PVC 38 mm ( 1 1/2” ) DE DIAMETROCABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE CALIBRES Y DEMANDAS DESDE LA BASE HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y LOS DE LAS FASES DIFERENTES AL BLANCOBASE ENCHUFE DE 7 TERMINALES, 100 AMPERES INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS, 100 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE PVC 38 mm (1 1/2") A 12,7 mm (1/2")TUBO RIGIDO PVC DE 12.7 mm ( 1/2” ) DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMO CONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS MURETE DE ACUERDO A LO INDICADO 1 2 3 4 A INSTALACIONINTERIOR 4 5 A VARILLADE TIERRA 2 DEL REGISTRO 6 7 8 9 10 DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR 11 INSTALADO POR C.F.E. AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBERA SALIR COMO MINIMO 10mm DEL MURO PARA COLOCAR EL MEDIDOR Y EL ARO 12 MEDIDOR TIPO ENCHUFE DE 15(100) AMPERES, 3 FASES, 4 HILOS, 120 VOLTS (FD21) SELLO DE PLASTICO CABLE DE ALUMINIO XLP A LA BASE ENCHUFE CONECTOR EMPALME A COMPRESION TENSION MINIMA TIPO ZAPATA MANGA TERMOCONTRACTIL O REMOVIBLE 13 14 15 BASE ENCHUFE 16 TAPA DE LA BASE NOTAS : MURO DECONCRETO A. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO MAXIMO A 35 METROS DEL REGISTRO. B. EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) C. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE LA PROPIEDAD EMPOTRADA D. EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCIONE. EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR F. MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE DETALLE DE EMPOTRADO DE LA BASE DETALLE “A” PROPIEDADDEL USUARIO VIAPUBLICA MEDIDOR VISTA DE PLANTA ACOTACIONES EN mm SIN ESCALA

  14. ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED SUBTERRANEA, CON BARDA FRONTAL CFE EM-BT307 HOJA 1 DE 2 #411 C F E DUCTO RED B.T. DUCTO RED B.T. REGISTRO DE ACOMETIDAEN B.T. VISTA DE CONJUNTO 4 11 C F E 5 12 6 1800 1800 7 2 13 VER DETALLE "A" 8 1 9 10 SECUNDARIO DE LA RED VISTA FRONTAL VISTA LATERAL

  15. 5 DISPONIBLES 15 14 ACOMETIDA SECUNDARIODE LA RED ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED SUBTERRANEA, CON BARDA FRONTAL CFE EM-BT307 HOJA 2 DE 2 ESPECIFICACIONES DE MATERIALES Y EQUIPO A CARGO DEL USUARIO 3 1 CODO DE PVC 63.5 mm ( 2 1/2” ) DE DIAMETROTUBO RIGIDO DE PVC 63.5 mm ( 2 1/2” ) DE DIAMETROCABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE CALIBRES Y DEMANDAS DESDE LA BASE HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y LOS DE LAS FASES DIFERENTES AL BLANCOBASE ENCHUFE DE 7 TERMINALES, 200 AMPERES INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS, 200 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE PVC 32 mm (1 1/4") A 12,7 mm (1/2")TUBO RIGIDO PVC DE 63.5 mm ( 2 1/2” ) A 12.7 mm ( 1/2” ) DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE SEGÚN TABLA DE CALIBRES Y DEMANDASCONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS 2 3 4 A INSTALACIONINTERIOR 4 5 A VARILLADE TIERRA 2 DEL REGISTRO 6 7 8 DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR 9 10 INSTALADO POR C.F.E. AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBERA SALIR COMO MINIMO 10 mm DEL MURO PARA COLOCAR EL MEDIDOR Y EL ARO 11 MEDIDOR TIPO ENCHUFE DE 30(200) AMPERES, 3 FASES, 4 HILOS, 120 VOLTS (KL28) SELLO DE PLASTICO CABLE DE ALUMINIO XLP A LA BASE ENCHUFE CONECTOR EMPALME A COMPRESION TENSION MINIMA TIPO ZAPATA MANGA TERMOCONTRACTIL O REMOVIBLE 12 13 14 BASE ENCHUFE 15 TAPA DE LA BASE NOTAS : MURO DECONCRETO A. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO MAXIMO A 35 METROS DEL REGISTRO. B. EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) C. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE LA PROPIEDAD EMPOTRADA D. EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCIONE. EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR F. MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE DETALLE DE EMPOTRADO DE LA BASE DETALLE “A” PROPIEDADDEL USUARIO VIAPUBLICA MEDIDOR VISTA DE PLANTA ACOTACIONES EN mm SIN ESCALA

  16. ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED SUBTERRANEA, CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT308 HOJA 1 DE 2 #590 DUCTO RED DE BAJA TENSION VISTA DE CONJUNTO 220 300 5 13 11 2 2000 1800 14 8 VISTA FRONTAL VISTA LATERAL

  17. 5 DISPONIBLES 16 15 ACOMETIDA SECUNDARIODE LA RED ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED SUBTERRANEA, CONSTRUCCION AL FONDO DE LA PROPIEDAD CFE EM-BT308 HOJA 2 DE 2 ESPECIFICACIONES DE MATERIALES Y EQUIPO A CARGO DEL USUARIO 3 1 CODO DE PVC 63.5 mm ( 2 1/2” ) DE DIAMETROTUBO RIGIDO DE PVC 63.5 mm ( 2 1/2” ) DE DIAMETROCABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE CALIBRES Y DEMANDAS DESDE LA BASE HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y LOS DE LAS FASES DIFERENTES AL BLANCOBASE ENCHUFE DE 7 TERMINALES, 200 AMPERES INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS, 200 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE PVC 63.5 mm (2 1/2") A 12,7 mm (1/2")TUBO RIGIDO PVC DE 12.7 mm ( 1/2” ) DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE SEGÚN LA TABLA DE CALIBRES Y DEMANDASCONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS MURETE DE ACUERDO A LO INDICADO 2 3 4 A INSTALACIONINTERIOR 4 5 A VARILLADE TIERRA 2 DEL REGISTRO 6 7 8 9 DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR 10 11 INSTALADO POR C.F.E. AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBERA SALIR COMO MINIMO 10 mm DEL MURO PARA COLOCAR EL MEDIDOR Y EL ARO 12 MEDIDOR TIPO ENCHUFE DE 30(200) AMPERES, 3 FASES, 4 HILOS, 120 - 480 VOLTS (KL28) SELLO DE PLASTICO CABLE MONOPOLAR XLP A LA BASE ENCHUFE CONECTOR EMPALME A COMPRESION TENSION MINIMA TIPO ZAPATA MANGA TERMOCONTRACTIL O REMOVIBLE 13 14 15 BASE ENCHUFE 16 TAPA DE LA BASE NOTAS : MURO DECONCRETO A. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO MAXIMO A 35 METROS DEL REGISTRO. B. EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) C. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE LA PROPIEDAD EMPOTRADA D. EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCIONE. EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR F. MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE DETALLE DE EMPOTRADO DE LA BASE DETALLE “A” PROPIEDADDEL USUARIO VIAPUBLICA MEDIDOR VISTA DE PLANTA ACOTACIONES EN mm SIN ESCALA

  18. 7 ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANADA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, EN ZONAS DE ARQUITECTURA COLONIAL CFE EM-BT309 HOJA 1 DE 2 72 74 76 VISTA DE CONJUNTO 3 1 F1 2 F2 N F3 500 mm DELONGITUD F3 N F2 F1 350 12 4 4800 500 C F E 5 1800 13 MURODEADOBE 8 9 INTERIOR BANQUETA 10 11 VISTA FRONTAL VISTA LATERAL

  19. 5 DISPONIBLES 15 14 ACOMETIDA SECUNDARIODE LA RED PROPIEDADDEL USUARIO MEDIDOR VIAPUBLICA ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANADA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, EN ZONAS DE ARQUITECTURA COLONIAL CFE EM-BT309 HOJA 2 DE 2 DE LA ACOMETIDA F3F2F1 ESPECIFICACIONES DE MATERIALES Y EQUIPO N 2 A CARGO DEL USUARIO 1 MUFA INTEMPERIE DE 38 mm (1 1/2") DE DIAMETRO 2 TUBO CONDUIT DE FIERRO GALVANIZADO PARED GRUESA DE 38 FFFmm (1 1/2")DE DIAMETRO Y CON 3000 mm DE LONGITUD3 CABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE A CALIBRES Y DEMANDAS, DESDE LA MUFA HASTA EL . INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR . BLANCO Y LOS DE LAS FASES DIFERENTES AL BLANCO4 BASE ENCHUFE DE 7 TERMINALES, 100 AMPERES TIPO AEREA A A A CON TAPA 5 INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS,100 FFFAMPERES A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIE 6 MONITOR Y CONTRATUERCA DE 38 mm (1 1/2”) 7 REDUCCION DE 38 mm (1 1/2") A 12,7 mm (1/2")8 TUBO CONDUIT PARED DELGADA DE 12,7 mm (1/2") DE DIAMETRO9 ALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMO 10 CONECTOR PARA VARILLA DE TIERRA 11 VARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS A INSTALACIONINTERIOR 4 6 A VARILLADE TIERRA 7 DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR INSTALADO POR C.F.E. 12 MEDIDOR TIPO ENCHUFE DE 15(100) AMPERES, 3 FASES, 4 HILOS, 120 VOLTS (FD21) 400 13 SELLO DE PLASTICO 14 CONECTOR EMPALME A COMPRESIÓN A TENSION MINIMATIPO ZAPATA MANGA TERMOCONTRACTIL O REMOVIBLE 15 NOTAS : 500 A. EL NICHO PARA MEDIDOR SERA DE CONCRETO ARMADO DE 500 X 400 X 350 mm B. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO MAXIMO A 35 METROS DEL POSTE DESDE EL CUAL SE DARA EL SERVICIO. C. EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) D. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE LA PROPIEDAD EMPOTRADA E. EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCIONF. LA ALTURA DE LA MUFA PARA RECIBIR LA ACOMETIDA SERA DE 4800 mm G. EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR H. MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE MALLAMETALICA PUERTA DEL NICHOCON APLANADO IDENTICOAL MATERIAL DE LA FACHADA DETALLE PUERTA DEL NICHO DETALLE “A” VISTA DE PLANTA ACOTACIONES EN mm SIN ESCALA

  20. 6 ACOTACIONES EN mm SIN ESCALA ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, EN ZONAS DE ARQUITECTURA COLONIAL CFE EM-BT310 HOJA 1 DE 2 72 74 76 REGISTRO DE ACOMETIDA BAJA TENSION DUCTO RED BAJA TENSION DUCTO RED BAJA TENSION VISTA DE CONJUNTO 4 350 400 11 500 500 C F E 5 1800 12 MURODEADOBE 7 2 8 VER DEATLLE “A” 13 INTERIOR BANQUETA 1 9 10 VISTA FRONTAL VISTA LATERAL

  21. 5 DISPONIBLES 15 14 ACOMETIDA PROPIEDADDEL USUARIO SECUNDARIODE LA RED MEDIDOR VIAPUBLICA ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, EN ZONAS DE ARQUITECTURA COLONIAL CFE EM-BT310 HOJA 2 DE 2 ESPECIFICACIONES DE MATERIALES Y EQUIPO A CARGO DEL USUARIO 3 1 CODO DE PVC 38 mm ( 1 1/2” ) DE DIAMETROTUBO RIGIDO DE PVC 38 mm ( 1 1/2” ) DE DIAMETROCABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE CALIBRES Y DEMANDAS DESDE LA BASE HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y LOS DE LAS FASES DIFERENTES AL BLANCOBASE ENCHUFE DE 7 TERMINALES, 100 AMPERES INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS, 100 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE PVC 38 mm (1 1/2") A 12,7 mm (1/2")TUBO RIGIDO PVC DE 12.7 mm ( 1/2” ) DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMOCONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS 2 3 4 A INSTALACIONINTERIOR 4 5 A VARILLADE TIERRA 2 DEL REGISTRO 6 7 8 9 10 DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR INSTALADO POR C.F.E. 11 MEDIDOR TIPO ENCHUFE DE 15(100) AMPERES, 3 FASES, 4 HILOS, 120 VOLTS (FD21) 400 SELLO DE PLASTICO CABLE MONOPOLAR XLP A LA BASE ENCHUFE CONECTOR EMPALME A COMPRESION TENSION MINIMA TIPO ZAPATA MANGA TERMOCONTRACTIL O REMOVIBLE 12 13 14 15 500 NOTAS : A. EL NICHO PARA MEDIDOR SERA DE CONCRETO ARMADO DE 500 X 400 X 350 mm B. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO MAXIMO A 35 METROS DEL REGISTRO. C. EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION ( FUSIBLE O TERMOMAGNETICO ) D. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL LIMITE DE LA PROPIEDAD EMPOTRADA E. EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCIONF. EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR G. MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE MALLAMETALICA PUERTA DEL NICHOCON APLANADO IDENTICOAL MATERIAL DE LA FACHADA DETALLE PUERTA DEL NICHO DETALLE “A” VISTA DE PLANTA ACOTACIONES EN mm SIN ESCALA