Modesto Irrigation District

Modesto Irrigation District. Utilizing SMART Grid Technology To Identify Power Theft. Benefits to date (beginning August 2012). Located over 270 significant residential energy diversions Identified and repaired dozens of faulty line side connections

ian-frank
Télécharger la présentation

Modesto Irrigation District

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Modesto Irrigation District Utilizing SMART Grid Technology To Identify Power Theft

  2. Benefits to date (beginning August 2012) • Located over 270 significant residential energy diversions • Identified and repaired dozens of faulty line side connections • Identified hundreds of meters that were mapped to incorrect transformer • Billed over 1.5 million for energy theft and saved millions from time of resolution going forward.

  3. Voltage Drop Identification • Group meters/readings together by transformer • Identify unusual meter voltage drop • Field investigation on those locations having unusual drop in voltage • Inspect meter service conduit, meter socket, service entrance etc.

  4. 240v 240v 240v 240v 235v 240v 240v

  5. Diverted Load Voltage chart

  6. Diverted load current chart

  7. Average comparisons

  8. Method • Utilizing SSN UIQ • Schedule 5 to 15 minute interval on demand readings of meter voltage, current, power, and temperature • Utilizing Microsoft Access • Join readings together with meter information, location, and transformer type • Utilizing Microsoft Excel • Run pivot tables, graphs, etc. that will identify unusual drop in meter voltage