1 / 3

壹、學校供電現況及預估說明

壹、學校供電現況及預估說明. 目前工程進度:高壓改壓工程規劃、設計及簽證電機技師;已於 96/4/18 送遠東聯合採購處辦理發包中。. 第三宿舍. 游泳池. 七館. 3 ∮ 11.4KV. 台電可供應電力 11.4KV : 4999KW 22.8KV : 9999KW. 台電變電站. 供電系統現況架構. 台電配電場. 紅色為 11.4 KV 級 配線. 電力現況資料 變壓器容量 : 18350KW 契約容量 : 3800KW (20%) 最高用電需量 : 4800KW (26%). 綠色為 22.8KV 級配線. 總變電站. B 變電站.

makan
Télécharger la présentation

壹、學校供電現況及預估說明

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 壹、學校供電現況及預估說明 目前工程進度:高壓改壓工程規劃、設計及簽證電機技師;已於96/4/18送遠東聯合採購處辦理發包中。 第三宿舍 游泳池 七館 3∮11.4KV 台電可供應電力 11.4KV : 4999KW 22.8KV : 9999KW 台電變電站 • 供電系統現況架構 台電配電場 紅色為11.4KV級配線 電力現況資料 變壓器容量 : 18350KW 契約容量 : 3800KW (20%) 最高用電需量 : 4800KW (26%) 綠色為22.8KV級配線 總變電站 B變電站 C變電站 D變電站 A變電站 一館 第一宿舍 第二宿舍 二館 五館 六館 三館

  2. 貳、學校供電現況及預估說明 • 各變電站電壓等級現況(含第三宿舍、游泳池、七館)及電力預估 十年電力預估資料 (增加八館及有庠館共增加6500KVA) 變壓器容量 : 33100KW 契約容量 : 6620KW (20%) 最高用電需量 : 8606KW (26%) (適用22.8KV供電系統) 近期電力預估資料 (增加第三宿舍、游泳池及七館共增加8250KVA) 變壓器容量 : 26600KW 契約容量 : 5320KW (20%) 最高用電需量 : 6916KW (26%) (適用22.8KV供電系統)

  3. 參、改壓工程工作流程 改壓工作開始 台電配電場預審 不合格 台電配電場正審 不合格 合格〈目前進度〉 改壓圖說台電審查 校區內改壓規劃設計 台電設計股外管線規劃設計 合格 校區內改壓工程發包施作,為不影響學生上 課及校務正常運轉,規劃利用今年96年暑假 進行更新各館輸變電設備,且各館停電時間 不超過二天,預定開學前校內設備更換完成 台電工務股發包施作 預計2007.8~10月完成 向台電申請改壓供電 改壓工作完成