1 / 28

(Textbook Chapter 7)

Protection against Electric Shock (Note: All the mentioned tables in this course refer to, unless otherwise specified, Low Voltage Electrical Installation Handbook, by Johnny C.F. Wong, Edition 2004). (Textbook Chapter 7). Introduction. 3 Approaches

mari-west
Télécharger la présentation

(Textbook Chapter 7)

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Protection against Electric Shock(Note: All the mentioned tables in this course refer to, unless otherwise specified, Low Voltage Electrical Installation Handbook, by Johnny C.F. Wong, Edition 2004) (Textbook Chapter 7)

  2. Introduction • 3 Approaches • Combined protection against both Direct & Indirect Contact • Protection against Direct Contact • Protection against Indirect Contact

  3. Combined Protection against Both Direct & Indirect Contact • By Separated Extra-Low Voltage (SELV) System • It is extra-low voltage system without connection to earth • By Limitation of Discharge of Energy • The equipment incorporates means of limiting the current which can pass through the body of a person to a value lower than that likely to cause danger • However, the open circuit voltage is not limited E.g. equipment with power source and very high internal impedance

  4. Protection against Direct Contact • By Insulation of Live Parts • By Barriers or Enclosures • By Obstacles • By Placing out of Reach • Refer to Fig. 7.5 for illustration

  5. Protection again Indirect Contact • BS7671 (IEE Wiring Regulations) stipulates 5 methods of protection against indirect contact: • Protection by earthed equipotential bonding and automatic disconnection of supply (EEBADS) • Protection by Class II equipment or by insulation equivalent • Protection by non-conducting location • Protection by earth-free local equipotential bonding • Protection by electrical separation Method 1 above is commonly adopted in HK.

  6. Protection again Indirect Contact • IEC61140 classifies methods of protection into 4 types: • Class 0: by basic insulation only and no provision is made for the earthing of accessible conductive parts • Class I: by basic insulation and earthing of all accessible conductive parts • Class II: by double or reinforced insulation, and no provision is made for the connection of a protective conductor to the accessible conductive parts • Class III: by SELV supplies

  7. SELV

  8. Reduced Low Voltage System 55V 55V

  9. Reduced Low Voltage System

  10. EEBADS • Earthed Equipotential Bonding & Automatic Disconnection of Supply (EEBADS) • An established practice in Hong Kong • Earthed Equipotential Bonding • TT - when l.v. supply is given directly by the supply company • TN-S - allowed only when the supply transformer is owned by the consumer • Equipotential Bonding - to create an equipotential zone within reach, and all equipotential zones should be bonded to each other • Automatic Disconnection of Supply • Purpose - to limit duration and magnitude of the touch voltage (voltage that arises between simultaneously accessible exposed and extraneous conductive parts)

  11. EEBADS (Cont’d) • Protective device can be • overcurrent protective device (e.g. MCBs, MCCBs, fuses, etc) • residual current device (in socket outlets and where prospective earth fault current is insufficient for prompt operation) • CoP requirements differ from IEE Requirements(BS7671). We mainly focus our discussion on CoP requirements.

  12. Terms for Earthing and Protective Conductors exposed conductive parts extraneous conductive parts A1 A2 gas pipes, water pipes, lightning down conductor, A/C ducts, etc B1 B2 circuit protective conductor(cpc) supplementary equipotential bonding main equipotential bonding main earthing terminal earthing conductor earth electrode

  13. EEBADS (Cont’d) • Exposed conductive parts & Extraneous conductive parts (refer to Fig. No. 11(1) of CoP) • Refer to Fig. 7.7 for installation component illustration • Earth fault loop impedance, Zs = Z1 + Z2 + ZE where Zs = earth fault loop impedance Z1 = phase conductor impedance Z2 = CPC impedance ZE = earth fault loop impedance external to the installation For max. permissible Zs, please refer to CoP’s Tables 11(8) to 11(14) for different types of protective device.

  14. Touch Voltage, Vt • Refer to Fig. 7.8 for symbols and illustration Earth fault current, Ia = Uo/(Z1+Z2+ZE) Vt = Ia Z2 = Z2Uo/(Z1+Z2+ZE) • Generally, the max. disconnection time should not exceed those indicated in fig. 7.4 for the particular Vt involved, E.g. Z1 = 0.3Ω, Z2 = 0.6Ω, ZE = 0.5Ω Ia= Uo/(Z1+Z2+ZE) = 220 / (0.3+0.6+0.5) = 157 A Vt = Ia Z2 = Z2Uo/(Z1+Z2+ZE) = 157 x 0.6 = 94.2 A FromFig. 7.4, in order to avoid danger, the max. disconnection time is 0.34 s

  15. Touch voltage • Fig. 7.8 Extraneous Conductive parts

  16. General requirement for touch voltage • However, if the circuit complies with the specific requirements as laid down by the IEE Regulations or the CoP (see the following discussion), the general requirements for touch voltage are deemed to be complied.

  17. EEBADS according to COP (see Table 7.14) • Socket Outlet Circuits • must be protected by a residual current device • must satisfy • Refer to Table 7.5 or CoP’s Table 11(14) • Fixed Equipment used inside Equipotential Zone • Disconnection time in case of earth fault within 5 sec. • Fixed Equipment Circuits outside Equipotential Zone or inside Bathroom • Disconnection time in case of earth fault within 0.4 sec.

  18. EEBADS according to COP • Installation supplied from Overhead Line System - must be protected by RCD and, • Distribution circuit supplying circuits for both Socket Outlets and Fixed Equipment • Equipotential bonding shall be provided at the distribution board connecting it to the same types of extraneous-conductive-parts as the man equipotential bonding.

  19. Calculation of circuit impedance • Refer to Tables 7.15 to 7.17 • For cable sizes > 35 mm2, reactance is taken into account • An average earth fault temperature of (70+160)/2 = 115oC is assumed for PVC copper cables used as CPC

  20. Size of Protective Conductor • Method 1: Refer CoP’s Table 11(2), or • Method 2: Refer CoP’s Tables 11(3) to 11(7) • Method 2: By using formula, where S = CSA of protective conductor I = earth fault current t = disconnection time k= a factor taking account of the resistivity, temperature coefficient and heat capacity of the conductor material, and the appropriate initial and final temperatures. Values of k are given in Table 7.20

  21. Types of Earthing SystemsTN-S System

  22. Types of Earthing SystemsTT System

  23. Types of Earthing SystemsCombined TT & TN-S System

  24. Electric Shock Protection in Locations Containing a Bath or Shower • Is of hazardous areas • In case of earth fault, equipment need disconnecting within 0.4 s, except that supplied from SELV • Local supplementary equipotential bonding is required for those parts simultaneously accessible with extraneous-conductive-parts and/or other exposed-conductive-parts. • Every switch or other means of electrical control should be inaccessible to a person using the facilities.

  25. Electric Shock Protection in Locations Containing a Bath or Shower • Lampholder within a distance of 2.5m from the bath or shower cubicle should be constructed of or shrouded in an insulating material. • No stationary equipment having heating elements which can be touched should be installed within reach of a person using the bath or shower. • No electrical installation or equipment should be installed in the interior of a bath tub or shower.

  26. Electric Shock Protection in Locations Containing a Bath or Shower • Divided into 4 zones, see Fig. 7.17A & B • The provision of socket outlets can be in zone 3 location (i.e. 0.6m away from shower basin or bath tub) and they should be protected by a RCD with a residual operating current not exceeding 30mA

  27. To Bond or Not to Bond • To bond, one has to determine if the following 2 conditions are fulfilled together: 1. the part is an extraneously-conductive-part, i.e. insulation to earth ≥ 22000 Ω ? 2. the part is simultaneously accessible with exposed- conductive-parts and/or other extraneously-conductive-parts, i.e. separation distance ≥ 2 m ?

  28. Extraneous Conductive Parts ?

More Related