1 / 39

Air Conditioning

Air Conditioning. Evaporators For Air Conditioning. Evaporators. Discussed in much more detail in HVACR312 the refrigeration term. In air conditioning there are two primary types of evaporators used: Natural Draft Forced Convection. Natural Draft. Forced Draft. Operating Design.

mliss
Télécharger la présentation

Air Conditioning

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Air Conditioning Evaporators For Air Conditioning

  2. Evaporators • Discussed in much more detail in HVACR312 the refrigeration term. • In air conditioning there are two primary types of evaporators used: • Natural Draft • Forced Convection

  3. Natural Draft

  4. Forced Draft

  5. Operating Design • Direct Expansion • Refrigerant directly cools the air. The evaporator coil is full of refrigerant and air is blowing across the coil.

  6. Operating Design • Indirect expansion • Refrigerant cools secondary medium, such as water or glycol. • The secondary medium flows through a coil in the air stream and that cools the space.

  7. Indirect Expansion

  8. Operating Design • Two types of Direct Expansion coils exist: • Dry Type • Flooded Type

  9. Dry Types • Use 25% less refrigerant than the flooded type. • Have more vapor in the evaporator • Have less chance of floodback to the compressor.

  10. Dry Type • The disadvantages of the dry type coil are: • Slower pull-down with heavy loads • System runs with higher head pressures.

  11. Evaporator Purpose • There are two purposes of evaporators: • Cooling • Dehumidification

  12. Cooling • Changes the sensible heat content in the air. • This you can actually measure.

  13. Dehumidification • Dehumidification changes the latent heat and the moisture in the air. • This is the process described in the psychometric chart. • Must keep indoor humidity under 50%.

  14. Evaporator Design • Most often done by mechanical engineers. • You will have a catalogue to choose evaporator and condenser combinations based on cooling requirements and size.

  15. Design Factors • There are several factors looked at for evaporator design: • Pressure Drop • Evaporator Capacity

  16. Design Factors • Causes of pressure drop: • Long evaporators • Not actual size, but the length of a run. • Solved by multiple evaporator circuits. • Tubing too small

  17. Design Factors

  18. Poor Evaporator Design • Low Gas Velocity • Poor oil return • No “scrubbing” effect, refrigerant debris build up in evaporator tubes. • Oil clogged evaporator

  19. Evaporator Capacity • Factors that effect evaporator capacity: • Surface Area • Temperature Difference • Refrigerant Velocity • Conductibility (How fast heat moves through metal) • Metal thickness • Air Volume

  20. Superheat

  21. Superheat • A sensible heat added to the vapor refrigerant after the change of state has taken place. • The difference between the boiling refrigerant and the suction line temperature.

  22. Superheat • Is used to check if the evaporator has proper level of refrigerant. • Superheat is gained in the evaporator – refrigerant picks up additional sensible heat after the change in state takes place.

  23. Superheat

  24. Superheat • Normal superheat is between 8-12 degrees for a TXV system. • Depending on the application this can be much lower or higher. • If the superheat is high • Starved coil • Low refrigerant

  25. Superheat • If the superheat is low • Flooded coil • To much refrigerant • DO NOT ADJUST REFRIGERANT WITH JUST SUPERHEAT UNLESS YOU ARE SURE THAT YOU KNOW HOW THE SYSTEM SHOULD WORK!

  26. Superheat • Complete vaporization of refrigerant should occur around the last bend of the evaporator. • Any additional heat absorbed is now referred to as superheat. • The TXV as a metering device is designed to maintain proper superheat.

  27. Measuring superheat • Take the temperature of the suction line with a thermometer. • Best to do within 6 inches of the evaporator. • Take the suction pressure and convert to the temperature of saturation.

  28. Measuring Superheat • Subtract the saturation temperature from the suction line temperature. • Example: • R22 system • Suction Pressure is 68.5psi (40 degrees) • Suction line temp is 50 degrees • 50 – 40 = superheat of 10 degrees

  29. Measuring Superheat • Add 2 psi to your suction line if: • Condenser is in remote location. • Suction line is well over 8 feet. • You are working on a split system.

  30. Trouble shooting with superheat • Domestic and commercial units: • 8 to 12 degrees of superheat is the rule of thumb. • Whatever must be done to superheat the opposite must be done to the refrigerant.

  31. Troubleshooting with superheat • If you have a superheat of 20 degrees • Superheat must be lowered • Increase refrigerant charge (or flow). • If you have a superheat of 2 degrees • Superheat must be raised • Decrease refrigerant charge (or flow).

  32. Troubleshooting with superheat • Anytime you make a superheat adjustment you must wait 10 to 15 minutes prior to making next adjustment. • This wait is so the system will stabalize.

  33. Superheat • With a fixed orifice metering device or a cap tube: • Adding charge lowers superheat • Removing charge raises superheat

  34. Additional Notes • The difference between the temperature of the refrigerant boiling in the evaporator and the temperature at the evaporator outlet is known as the evaporator superheat.

  35. Additional Notes • When measuring evaporator superheat on a commercial system with a long suction line the pressure reading should be taken at the evaporator outlet, not the compressor inlet.

  36. Additional Notes • Superheat measurements are best taken with the system operating at design conditions.

  37. Additional notes • Evaporators can by multi-pass. This means the coil has been folded over on itself or is actually 2 or three coils clamped together and fed by a distributor.

  38. Additional Notes • When an evaporator coil is multi pass and has a superheat that is higher than others this can be caused by un-even air distribution, a blocked distributor, or even a dirty coil section.

  39. Additional Notes • Evaporators that are used to chill liquids, like the ones found in slurpey machines and soda dispensers can have a normal superheat measurement but not be cooling properly. This is caused by deposits built up on the liquid side of the evaporator or poor circulation of the liquid.

More Related