1 / 17

Masterpact NT/NW Preventive - maintenance operation

Masterpact NT/NW Preventive - maintenance operation. Masterpact NT/NW Adaptation, replacement policy. Definition Adaptation: when a new item is installed on the breaker Modification : change the performance of the breaker ( either mechanical or electrical

Télécharger la présentation

Masterpact NT/NW Preventive - maintenance operation

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Masterpact NT/NWPreventive - maintenance operation

  2. Masterpact NT/NW Adaptation, replacement policy • Definition • Adaptation: when a new item is installed on the breaker • Modification : change the performance of the breaker ( either mechanical or electrical • Replacement : exchange a component by a new one • Adaptation by the customer • breaker electrical accessories: • auxiliary contacts OF/ SDE1 • ready to close contact PF • Motor mechanism MCH • non communicating MX/XFMN • Electrical closing push button BPFE • Delay block for MN

  3. breaker mechanical accessories: • operation counter • breaker locking devices ( key and padlock) • Disconnectable front connectors • Fixing brackets • Door frame • Transparent front cover • Door cut out screen • Interlock : 2S + 1Rg, 2S + 1C, 3S • Interlock cable 2NW/NT • Interlock rods 2NW/2NT • Cable door interlock NT/NW • Earthing device kit

  4. Cradle electrical accessories • Cradle position contacts CE CT CD • Combined connected closed contacts EF • Levers for additional cradle position contacts • Cradle mechanical accessories • Cradle locking in disconnected position • Cradle locking in all positions • Racking interlock • Insulating shutters (+ locking) • Mismatch protection • Terminal shield

  5. Trip units and accessories, communication • Cradle communication module • Vigi sensor • Neutral protection CT • External power supply • Modification by the customer • Breaker mechanical accessories • Breaker main connections • Cradle mechanical accessories • Cradle main connections • Trip units and accessories, communication • Rating plugs

  6. Replacement by the customer • Arc chute • Clusters • Front cover • Racking handle • Micrologic Battery

  7. Adaptation by the Aftersales Service :everything allowed to the customer plus : • Breaker electrical accessories • SDE2 contact • Cradle mechanical accessories • Automatic spring discharge • Shutter front locking (NW only) • Trip units and accessories, communication • Automatic reset • remote reset ( electrical operated) • Breaker communication module and wiring • M2C/M6C relays • External voltage pick-up (PTE option)

  8. Modification by the after sale service : everything allowed to the customer plus : • Breaker • Performer plug • Sensor plug • Trip units and accessories, communication • Trip units • Replacement by the After sales service • Fixed and moving contacts : change basic block • Toggle return springs • MX/XF communication coils

  9. Preventive - maintenance operation • Check on operating conditions • Save Micrologic parameters • Perform operating tests prior to servicing • check on contact wear and energy mechanism Non OK OK • Dismantle all auxiliaries and accessories • Replace by new breaker block • Clean & regrease chassis • Replace the Control unit and test the connection • Test auxiliaries • Test Micrologic • Check on communication • Dismantle a few auxiliaries (exchange systematically the coils) • Clean and regrease (breaker & chassis) • Test Micrologic • Check on communication

  10. Masterpact NT/NW Politique d’Adaptation et de remplacement • Definition • Adaptation: Installation d’un nouvel accessoire dans le disjoncteur • Modification : change les performances du disjoncteur ( soit mécanique soit électrique • Remplacement : échange d ’un composant par un nouveau • Adaptation par le client • Accessoires électriques du disjoncteur: • contacts auxiliaires OF/ SDE1 • contact Prêt à fermer PF • moto réducteur MCH • bobines non communicantes MX/XF/MN • Bouton poussoir de fermeture électrique BPFE • retardateur MN

  11. Accessoires mécaniques du disjoncteur: • Compteur de manœuvre • Systèmes de verrouillage du disjoncteur ( clé et cadenas ) • Kit de PAV déconnectables • Flasques de fixation mural • Cadre de porte • Capot transparent • Obturateur de porte • Inter verrouillage 2S + 1Rg, 2S + 1C, 3S • inter verrouillage par câble 2NW/NT • inter verrouillage par tringle 2NW/2NT • Inter verrouillage de porte NW/NT • Kit de mise à la terre ( earthing switch)

  12. Accessories électriques du châssis • Contacts de position châssis • Contacts combinés embroché fermé • Actionneurs pour contacts de position supplémentaires • Accessories mécaniques du châssis • Verrouillage châssis en position débrochée • Verrouillage châssis toutes positions • Verrouillage d'embrochage porte ouverte • Verrouillage de porte • Volets isolants et Verrouillage volets par sabot • Détrompeurs • Capot bornier

  13. Déclencheurs et accessoires, communication • Boiter de communication chassis • Cadre sommateur Vigi • TC de protection du neutre • Alimentation externe • Modification par le client • Accessoires mécaniques du disjoncteur • Plages de raccordement appareil • Accessoires mécaniques du châssis • Plages de raccordement châssis • Déclencheurs et accessoires, communication • Plug long retard

  14. Remplacement par le client • Chambre de coupure Arc chute • Pinces • Plastron avant • Manivelle d’embrochage • Batterie Micrologic

  15. Adaptation les Services Après vente : tout ce qui est autorisé au client plus : • Accessoires électriques du disjoncteur • contact SDE2 • Accessoires mécaniques du Châssis • Désarmement automatique à l'extraction • Verrouillage volets face avant (uniquement NW) • Déclencheurs et accessoires, communication • Réarmement automatique (RAR) • Réarmement électrique (RES) • Boiter et filerie communication appareil • Module M2C/M6C • Prise de tension extérieur (option PTE)

  16. Modification par les Services Après vente : tout ce qui autorisé au client plus : • Disjoncteur • Performeur • Calibreur • Déclencheurs et accessoires, communication • Déclencheur • Replacement par les Services Après vente • Contact fixe et mobile : échange par un bloc universel • Ressorts d'embiellage • MX, XF communicantes

  17. Opération de maintenance préventive • Vérifiez les conditions d’exploitation • Sauvegardez les réglages et historiques de Micrologic • Effectuez les tests de fonctionnement avant la maintenance • Vérifiez l’usure des contacts et le mécanisme d’accumulation d’énergie Non OK OK • Démontez tous les accessoires • Remplacez par un nouveau bloc • Nettoyez & regraissez le châssis • Replacez l’unité de contrôle et testez les connections • Testez les auxiliaires • Testez les courbes de Micrologic • Testez la communication • Démontez le minimum d’accessoires (échangez systématiquement les bobines ) • Nettoyez et regraissez (disjoncteur et châssis) • Testez les courbes de Micrologic • Testez la communication

More Related