1 / 53

Preferred Utilities Manufacturing Corp

Preferred Utilities Manufacturing Corp. Fuel Oil Handling Systems Overview. Preferred Utilities Mfg. Corp. 31-35 South Street • Danbury • CT www.preferred-mfg.com. PUMC Identity.

pilcher
Télécharger la présentation

Preferred Utilities Manufacturing Corp

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Preferred Utilities Manufacturing Corp Fuel Oil Handling Systems Overview Preferred Utilities Mfg. Corp. 31-35 South Street • Danbury • CT www.preferred-mfg.com

  2. PUMC Identity Founded in 1920 and in continuous operation since then. We are an engineering - based manufacturer of combustion and fuel handling products for industrial, institutional, and commercial power plants. Our Core Business is Combustion Control.

  3. PUMC Identity

  4. Plant Wide Controller Hot Water Reset Application 2 to 10 Boiler Modulating Lead / Lag

  5. New Plant Wide Controller (PWC) Displays Plant Overviews Historical Trends Alarm Summary Setup

  6. PCC-III™ Multiloop Controller • Third Generation Controller • 12 year PCC II life with over 2000 installed • 2 year PCC III life with over 300 already installed • There are many digital controller manufacturers, but NONE have Preferred’s in-depth and on going combustion control experience.

  7. New WN Best Combustion System • Low NOx • Low Energy Consumption • Burner + Controls + BMS + SCADA = Maintained Performance

  8. Complete System Expertise

  9. Typical Piping Arrangement Emerg. Gen. Day Tank Vent with Rupture Basin Fill Return Supply Suction Pump Main Oil Tank

  10. Fuel Fill • Spill Containers • Model 1 In Ground Spill Container • Drains oil spilled from delivery disconnect into storage tank • Designed to handle driveway traffic • Removable bellows for easy fuel testing without pavement excavation.

  11. Fuel Fill • Model 2 In Wall Spill Container • For indoor storage tanks with fill lines to building walls • Standard models from simple box to integrated digital level display and overfill alarming • We can customize many things:A bronze Model 2 was recently installed at Radio City Music Hall to contribute to the building’s décor.

  12. In-Wall Fill Box with Sign

  13. Typical Piping Arrangement Emerg. Gen. Day Tank Vent with Rupture Basin Fill Return Supply Suction Pump Main Oil Tank

  14. Vent • Vent Caps & Bricks • Standard Tank Vent Protectors for storage tanks • Conform to Standards for the Installation of Oil Burning Equipment (NFPA No. 31)

  15. Vent • Vent Bricks provide a terminal for indoor storage tank vent lines • Standard masonry brick size • Fits 2" & 3" vent lines

  16. Typical Piping Arrangement Vent Emerg. Gen. Day Tank with Rupture Basin Fill Return Supply Suction Pump Main Oil Tank

  17. Anti-Syphon Valves • Patented by Preferred Utilities. • UL Labeled & Listed

  18. Anti-Syphon Valve Manifold

  19. Anti-Syphon Valves • Used where fuel leaks will result in fuel being syphoned into areas which can cause a dangerous and costly situation • UL Labeled and listed • For No. 2 through No. 6 Oils • 5’, 10’, 15’ or 20” Head Selection • Installed at highest point in piping

  20. Fire Safety Shut-off Valves • Preferred’s Lever Gate Valve • Fully mechanical • Emergency fuel line shut-off is mandated by many codes • Fusible links open at 165F • for pipe ranges 1" - 3" • Fusomatic Valve • Replaceable fusible element • Fusible links open at 165F, May be manually opened/closed • for pipes 3/4" or 1"

  21. Type 110 Fire Valve

  22. Foot Valves • Ensures maintenance of pump prime by preventing oil backflow into the tank when pumps are off • Single Poppet • 1/2” to 3” Size • Double Poppet • Double the protection • 1-1/2” or 2” Sizes • Foot Valve Extractor Fitting • Easy Removal and Inspection of Foot Valve

  23. Foot Valves

  24. Typical Piping Arrangement Vent Emerg. Gen. Day Tank with Rupture Basin Fill Return Supply Suction Pump Main Oil Tank

  25. Relief Valves • Very important for use on positive displacement pumps • Sizes for 1/2” to 3” • For use with any type oil • Pressure Ranges of 5-35psi, 25-100psi, 75-300psi

  26. Typical Piping Arrangement Vent Emerg. Gen. Day Tank with Rupture Basin Fill Return Supply Suction Pump Main Oil Tank

  27. Fuel Components • Strainers • Duplex • No flow interruption for routine cleaning • 90° handle movement switches baskets • Handle blocks inadvertent opening of active side • Sizes from 3/4" - 6" • Simplex • Special yoke design for quick cleaning • Large basket • Sizes from 1/2" - 2"

  28. Pump Sets with Multiple Pumps • Multiple pumps share common suction and discharge piping • Most common is duplex set • two 100% pumps, one for backup • control system can monitor flow, start lag pump • Triplex pump sets for large plants • three 50% pumps allow for one spare • two 100% “winter pumps” - one 50% “summer pump”

  29. Strainer Close-up

  30. Pump Set Leak Detector

  31. Pump Set Relief Valves

  32. Flow Sensor

  33. Flow Control Manifold

  34. Day Tank Features • Complete Tank, RuptureBasin, and InstrumentationPackage • Standard & Custom Sizes • Standard: 20-620 Gallons (UL Approved) • Custom: up to 2,000 Gallons • Tank/Rupture BasinAssemblies 290 Gal orLess are Doorway Accessible • UL Approved Catalog 22, p16-17

  35. Day Tanks Features Continued • UL Approved • Available with integrated rupture basin • 160% of tank capacity (200% for NYC) • Includes: 4 point Level Switch, Tank Gauge, Vent Protector • Fully Tested at Factory Prior to Shipment

  36. Tank Gauge • D3 Tank Gauge • Single Tank Applications • Wire Float Available for Limited Tank Clearance • Standard 4-20 mA output

  37. Wire Float Level Sensor • Requires only 14 Inches of Head Room • Reads tanks 36 to 145 inches Tall • Buna-N Float • Requires only a 4 inch 125# Flange • Easy to Install and Calibrate • Can Be Installed in an Empty or Full Tank • Intrinsically Safe

  38. Wire Float Level Sensor

  39. Day Tank Level Sensor

  40. Tank Gauges • Digital Level Readout in Inches and Gallons • Alarm Silence, Test, and Alarm Recall Push-buttons • Analog Output for Remote Display of Level • Interface to Leak Detectors • Displays H20 for Water Leak (Outer Wall) • Displays OIL for Oil Leak (Inner Wall) • Low and Overfill Alarm Relays

  41. Leak Detection • Factory Mutual Approved • Intrinsically Safe • Monitors for both Oil and Water • Three Detectors per Tank Gauge • Manual Testing of Unit • Completely Potted for Long Life • Fail Safe Circuitry

  42. Leak Sensor Test Modules

  43. Interstitial Space Leak Sensor

  44. Floor Leak Detector

  45. Leak Sensor

  46. Leak Sensor Test Module

  47. Fil-A-Larm Systems • Mounted at Tank Fill Point to Assist Truck Driver in Properly Filling Tank • Bright Lamps Indicate When Tank Is Full • Alarm Horn Sounds For No More Than 90 Sec. • Alarm Test and Alarm Silence Push-buttons • Available with Gallons Display

  48. Fuel Components • Tank Selector Valves • Replaces confusing array of hand valves • Simple lever operation transfers both supply & return lines from one tank to the other • Designed with no “blind spots” where flow could be blocked to or from the tanks • Threaded or flanged connections available

  49. Back Pressure Regulating Valves • Used in a flow loop to maintain proper pressure for burners. • Type BQ for flow rates up to 390gal/hour • Standard Ranges of 26-75psi or 76-150psi • 1/2” Size • Type V for higher flow rates • Standard Range of 30-150psi • 1” Size

  50. Pump and Heater Sets • Residual Fuel Oil • Waste Liquids • Steam or Hot Water • Dual Transfer Safety Heaters • Single Transfer Oil Heaters • Job Specific Engineering

More Related