自然接地体和人工接地体

自然接地体和人工接地体. 一、自然接地体和人工接地体.

Télécharger la présentation

自然接地体和人工接地体

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 自然接地体和人工接地体

  2. 一、自然接地体和人工接地体 接地装置是接地体(极)和接地线的总称。运行中电气设备的接地装置应当始终保持良好状态。自然接地体是用于其他目的、且与土壤保持紧密接触的金属导体。例如,埋设在地下的金属管道(有可燃或爆炸性介质的管道除外)、金属井管,与大地有可靠连接的建筑物的金属结构、水工构筑物及类似构筑物的金属管、桩等自然导体均可用作自然接地体。利用自然接地体不但可以节省钢材和施工费用,还可以降低接地电阻,并能等化地面及设备问的电位。如果有条件,应当优先利用自然接地体。当自然接地体的接地电阻符合要求时,可不敷设人工接地体(发电厂和变电所除外)。在利用自然接地体的情况下,应考虑到自然接地体拆装或检修而被断开时,断口处出现的电位差及接地电阻发生变化的可能性。自然接地体至少应有两根导体在不同地点与接地网相连(线路杆塔除外)。利用自来水管及电缆的铅、铝铠皮作接地体时,必须取得主管部门同意,以便施工和检修时互相配合。

  3. 人工接地体可采用钢管、角钢、圆钢或废钢铁等材料制成。人工接地体宜采用垂人工接地体可采用钢管、角钢、圆钢或废钢铁等材料制成。人工接地体宜采用垂 直埋设,多岩石地区可采用水平埋设。垂直埋设的接地体可采用直径为40~50 mm的钢管或40 mm×40 mm×4 mm至50 mm×50 mm×5 mm的角钢,可以 成排布置,也可以作环形布置。水平埋设的接地体可采用40 rnm×4 mm的扁钢 或直径为16 H1rn的圆钢,多呈放射形布置,也可成排布置或环形布置。 电力线路杆塔接地体引出线应镀锌,截面积不得小于50 mm 。