1 / 10

NA62 DCS CAN bus lines

NA62 DCS CAN bus lines. Short reminder. General properties of CAN bus Up to 64 nodes on one bus Different devices need different buses (WIENER, ISEG, ELMB,?) Transition rate depends on the length of cable (from 1 Mbit /s for 25m to 10 kbit /s for 5000m)

shubha
Télécharger la présentation

NA62 DCS CAN bus lines

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. NA62 DCS CAN bus lines FV

  2. Short reminder • General properties of CAN bus • Up to 64 nodes on one bus • Different devices need different buses (WIENER, ISEG, ELMB,?) • Transition rate depends on the length of cable (from 1 Mbit/s for 25m to 10 kbit/s for 5000m) • Characteristic impedance 120 Ohm, termination on both ends • The starting point of the CANbus cables is DCS rack(s) in the PC farm area (b.918) • ISEG CAN bus • One module has two CAN-nodes, crate is one node. So one fully populated crate with 8 Modules EDS 20 130n_504 equals 17 CAN-nodes • Not more than 3 crates per cable • Peak PCAN-PCI two channel cards VF

  3. Short reminder -2 • ELMB CAN bus • In addition to the CAN bus signals the cable also provide the power for the ELMBs (12V) • Thick cable (SCEM code 04.21.60.491.2) will be used for long distance to minimize the voltage drop, thin cable (SCEM code 04.21.60.430.5) for local distribution + junction box “a la ATLAS” (has to be investigated) • Fixed double cable “PHOENIX CONTACT” connectors • KvaserPCIcanx4xHS cards • WIENER CAN bus • KvaserPCIcanx 4xHS cards • TCP/IP option for the WIENER equipment control is under consideration. Price for one fan-tray unit • CAN bus: 627 EURO • TCP/IP: 755 or 991 EURO • In total we will have about 60 crates VF

  4. Experimental Area PC farm area VF

  5. ISEG CAN bus lines • MUV, SAV • LAV 12, 11, 10 • LAV 9, 8, 7 • LAV 6, 5, 4 • LAV 3, 2, 1 • CEDAR (?) GT 854 (to PC farm) GT 853 (to NA48 CR) VF

  6. ISEG CAN bus lines • LAV 3, 2, 1 • CEDAR (?) VF

  7. WIENER crate control CAN bus lines • LKr • All other crates in EB, LAV12, LAV11, LAV10 • Straw tracker • LAV 9, 8, 7, 6, 5, 4, 3, 2, 1, CHANTI, GTK (?), CEDAR GT 854 (to PC farm) GT 853 (to NA48 CR) VF

  8. WIENER crate control CAN bus lines • LAV 5, 4, 3, 2, 1, GTK (?), CHANTI, CEDAR VF

  9. ELMB CAN bus lines • LKr • RICH, MUV, SAV • STRAW 1 • STRAW 2 • STRAW 3 • STRAW 4 • CHANTI, GTK3, GTK2, GTK1, CEDAR VF

  10. Other CAN bus lines • CAN bus cables for LAV thresholds (one cable per station) • Gas systems (one cable per system ?) • CEDAR NINO front-end cards control (one cable)? • RICH NINO front-end card control ? VF