An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. EN779:2012 &Eurovent EnergyEfficiency Classification Steve Devine

  2. Eurovent Energy Efficiency Classification • Energy rating system using EN779:2012 • Advantages • Independent label • Makes filters comparable • Escape price discussions • Talk about IAQ and • Energy • Select best solution • Energy saving (Eurovent) • IAQ (EN779:2012) • Minimum efficiency (EN779:2012)

  3. What´s needed to be able to classify filters • EN779:2012 test rig • ASHRAE Dust feeding • EN779:2012 Test Report

  4. Airborne Particulate Size Outdoor air ASHRAE Dust Average Diameter ~0.08mm Average Diameter ~7.7mm 100x difference in size, so what does loading with ASHRAE dust tell you? Answer: How your filter will perform when it is challenged with ASHRAE dust, Do you have ASHRAE dust in your system???

  5. ASHRAE Dust ΔP vs. Real Life ΔP Actual Average ΔP DPF Dx DPI DP ASHRAE Dust = 0.63” WG DP ”Real Life” = 0.46” WG Simple averaging ΔP (DPI+DPF)/2 = 0.75” WG DPF DPI

  6. So is ASHRAE Dust a Problem? • It is an acceptable compromise • This procedure is a Method of Calculation using existing test data • EN779 uses ASHRAE test dust • Data is available • Generally, a filter with a “better” ASHRAE loading curve will have a lower energy cost • Better than any alternative method available at this time • Not 100% true • LCC Green will correct the ones that fail

  7. The system is available in Europe ”Low energy consumption in combination with a high indoor air quality.”

  8. ASHRAE and ISO? • ASHRAE • Guideline Project Committee is forming • Proposed method is similar • Uses ASHRAE dust loading • Proposed method is different • Data from 52.2, ISO 16890 or EN779 • 4-5 years minimum from a document • ISO • Started a Work Item in 2011 • Stopped the WI in 2012 • Project is on hold • If it gets started again, it will also be 4-5 years from a document

  9. How would our USA products rate? • All Values are calculated kWh per Eurovent 4/11

  10. How would some USA products do in Eurovent 4/11? • The lower the kWh value the better the performance • Why are any of you buying a 12” HF ES???? • Difference between 4V and 2V • AAF VXL has a better kWh than the HF ES, but not in the field… • Aeropleat – Not Good, but What – 30/30??? • AAF PP has same rating as a 30/30…

  11. The biggest issues facing ASHRAE and ISO • The USA uses pleated filters • Based on energy, pleats are horrible products • The Eurovent methodology shows NO differentiation between any pleats • The AP3 and 30/30 are both a “G” • The AAF PP is also a “G” at ½ the 30/30 price • This is the problem facing ASHRAE and ISO • The ASHRAE and ISO methods will have to show differentiation of pleated filters • Similar to why there is an Arrestance test method and a Particle Removal Efficiency test method – different levels of filtration

  12. THANK YOU VERY MUCH!