Curie Reduction on Liquid Effluent Releases at the PSEG Salem Generating Station

Curie Reduction on Liquid Effluent Releases at the PSEG Salem Generating Station. Presented by: Ron Werline Author: Ron Werline - PSEG Nuclear LLC Radwaste Specialist Co-author: Kevin Davis - Duratek, Inc. TSR. Salem Nuclear Plant. 2 Unit Four Loop Westinghouse PWR

Télécharger la présentation

Curie Reduction on Liquid Effluent Releases at the PSEG Salem Generating Station

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Curie Reduction on Liquid Effluent Releases at the PSEG Salem Generating Station Presented by: Ron Werline Author: Ron Werline - PSEG Nuclear LLC Radwaste Specialist Co-author: Kevin Davis - Duratek, Inc. TSR RETS/REMPS Workshop

  2. Salem Nuclear Plant • 2 Unit Four Loop Westinghouse PWR • Located on Artificial Island in Southern New Jersey, 45 miles Southeast of Philadelphia • Each Unit rated at 1170 Mwe • Commercial operation: • Unit 1, December 1976 • Unit 2, May 1981 • Radwaste systems are common to both units RETS/REMPS Workshop

  3. Salem Liquid Radwaste System • Floor Drains • Equipment Drains • Lab Drains • Containment Sumps and Drains • Waste Hold-up Tanks (WHUT) • Laundry/Hot Shower/Chemical Drain Tanks (LHS/CDT) • Auxiliary Building Sump Tanks • Chemical Volume & Control System Monitor Tanks (CVCSMT) RETS/REMPS Workshop

  4. 1980’s Primary liquid Radwaste processing goal was centered on cost reduction through volume reduction 1990’s Curie reduction plan was set in motion with the primary goal to reduce curies released from liquid waste by 10% per year Curie Reduction Effort RETS/REMPS Workshop

  5. Curie Reduction Effort (cont.) • In 1998 Chemistry department took ownership of Radwaste from Operations • Implemented a release limit of 1.43e-05 • Curie reduction achievement • 1998 Curie goal of 0.50, actual released 0.43 • 1999 Curie goal of 0.50, actual released 0.37 • 2000 Curie goal of 0.12, actual released 0.10 • 2001 Curie goal of 0.10, actual released 0.03 RETS/REMPS Workshop

  6. Past Liquid Effluent Releases RETS/REMPS Workshop

  7. ALPS/AIM System • Advanced Liquid Processing System (ALPS) with Advanced Injection Method (AIM) was installed in late January of 2001 • Chemical Volume Control System (CVCS) Water was initially processed with Plant Evaporator • Initially processed “Waste” Water (Floor Drains, Equipment Drains and Chemical/Laundry Drains) • Eventually processed everything including CVCS water RETS/REMPS Workshop

  8. ALPS/AIM Process • Combination of filtration, ion exchange and chemical treatment technologies • Establishes and maintains the most efficient chemical additive concentration • Removal of soluble ionic species by standard and ion specific exchange media • Removal of colloids by deep bed filtration and chemical addition RETS/REMPS Workshop

  9. Salem’s ALPS Processing Area RETS/REMPS Workshop

  10. Salem’s ALPS Processing Area RETS/REMPS Workshop

  11. Salem Goals • Total activity less than 0.10 curies released per year for both units combined • Effluent Chromate less than 220 ppb • Effluent Hydrazine less than 10 ppb • Minimize waste generation based on influent conductivity • No filter usage RETS/REMPS Workshop

  12. Salem Challenges • Minimizing Waste Generation • Higher than typical PWR conductivity • Lower than typical PWR curie release goal • Processing all CVCS Hold-Up Tank Water • Plant took Evaporators out of service in April 2001 • Maintain Waste Tanks less than 30 % • Process rate is limited to 36-38 gpm by Plant’s pumps RETS/REMPS Workshop

  13. Salem Challenges (cont.) • 90,000 gallons of high conductivity (up to 8,000 uS/cm) service water • No means for plant to segregate the waste streams • Results in inconsistent waste water parameters RETS/REMPS Workshop

  14. Gallons Processed RETS/REMPS Workshop

  15. Solid Radwaste Produced RETS/REMPS Workshop

  16. Conductivity vs. Waste Produced RETS/REMPS Workshop

  17. 2001 Curies Received 15.5398 Curies Released 0.0042423 Average Monthly Gallons 149,019 Average Monthly Conductivity 392.2 Average Monthly pH 7.13 Average Monthly Flow 35.4 gpm 2002 Thru April Curies Received 35.8639 Curies Released 0.0001854 Average Monthly Gallons 194,499 Average Monthly Conductivity 207.5 Average Monthly pH 6.87 Average Monthly Flow 37.5 gpm ALPS Performance Data RETS/REMPS Workshop

  18. Salem 2001 Accomplishments • 2001 total curie release of .0318 uCi/ml was lowest ever (Goal was 0.10) • Salem removed evaporators from service • Successfully processed 90,000 gallons of high conductivity service water • Floor drain input control • No filter usage (Goal was met) RETS/REMPS Workshop

  19. Salem Accomplishments (cont.) • Average total activity DF of 5,416 • Average Co58 DF of 2,257 • Average Cs137 DF of 5,758 • Zero water “re-processing” • Minimizes impact on Operations and Chemistry personnel • Effluent Chromate and Hydrazine Goals were met RETS/REMPS Workshop

  20. Process Partnership • Communication/Teamwork • Between Radwaste Supervisor and Vendor • Chemistry Support • Radiochemistry results as needed • Standard chemistry analysis • Rad Protection Support • Coverage on all pertinent radiological activities • Site Services Support RETS/REMPS Workshop

  21. Summary • ALPS/AIM System produces proven results • Customer satisfaction at an all time high • Plant chemistry has improved since installation • Freed up Operations & Chemistry personnel • Reduced contaminated areas • No System leaks • Lowered processing area dose RETS/REMPS Workshop