Operating Room/ Surgical Room Ceiling

Surgical Room Ceiling / Ultra Clean ventilating<br><br>Necessary Airflow<br>Trapezoidal Absolute Filters<br>Plenum for Air Distribution<br><br>In conventional ventilating operating rooms over 90% of the bacterial contamination of the wounds comes from the air and clean air results in a lower risk.<br><br>Airtech Ultra Clean Ventilating (U.C.V) system, which is unique in generating an ultra clean zone free from peripheral entrainment of contaminated air and creates a clear zone larger than its diffuser area, giving protection over instrument tables in addition to the immediate surgical area. BSL4.<br><br>

adamjoshnaa
Télécharger la présentation

Operating Room/ Surgical Room Ceiling

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. We work on the forefront of INNOVATION AND TECHNOLOGY to take products from an idea all the way to the client

  2. Table of Content • About UTOPIA • Our Products • About Utopia’s Operating Room / Surgical Room 1. Necessary Airflow 2. Trapezoidal Absolute Filters 3. Plenum for Air Distribution • Surgical Room Ceiling / Ultra Clean Ventilating

  3. About Us • Utopia is all geared up for this exciting challenge. In our organisation, we practice quality like a religion. From our micro level, we hope our contribution will benefit the macro level on the world stage, in order that one and all, we will progress towards harmony, mutual understanding and better way of life. • To know more details visit https://www.utopia.com.sg

  4. Our Products • Hospitals Equipments • Biofit Chairs • HVAC Equipment • Cleanroom Products • Cleanroom Equipment

  5. Utopia’s Operating Room / Surgical Room

  6. Utopia’s Operating Room / Surgical Room

  7. Utopia’s Operating Room / Surgical Room • Necessary Airflow The cost of running a unidirectional ceiling is strongly related to the air flow, and therefore to the surface of the ceiling itself. Airtech proposes an octagonal ceiling instead of square, so to eliminate the protection on the angles where there is no need for. The total surface of the ceiling therefore is smaller by approximately 20%. In regards to this necessary air flow goes down to around 7.200 m3/h.

  8. Utopia’s Operating Room / Surgical Room • Trapezoidal Absolute Filters All the Airtech laminar ceiling have a octagonal shape 3,2 m by 3,2 m; there are 8 filters with efficiency H14 and their shape is trapezoidal. The absolute filters have a double density; greater in the centre of the ceiling so to have a higher speed and therefore guaranty a better effect of expulsion of the contamination from the aseptic nucleus. With the same filtering ceiling area the trapezoidal filters have a covered area greater by approximately 20% than the traditional standard rectangular filters.

  9. Utopia’s Operating Room / Surgical Room • Plenum for Air Distribution Trapezoidal filters are equipped with a system to guaranty that air drops in a circular crown around the filters in case of air leakage from the gaskets around the filtering section. Keeping the crown in depression using the re-suction fans, allows for evacuation of the air which is bypassed the HEPA Filter.

  10. Utopia’s Operating Room / Surgical Room • Plenum for Air Distribution Above the filters there’s a galvanished steel plenum (accessory: Stainless steel) for an optimal distribution of the primary air coming from the air conditioner and the re-circulated one is coming from the ceiling. The connections are riveted and sealed. Under the filters there’s a perfectly sterilisable lamination system in micro-holed tissue. At the centre of the octagon the scialitic lamp connection is foreseen.

  11. Surgical Room Ceiling / Ultra Clean Ventilating

  12. Surgical Room Ceiling / Ultra Clean Ventilating

  13. Surgical Room Ceiling / Ultra Clean Ventilating

  14. Surgical Room Ceiling / Ultra Clean Ventilating • In conventional ventilating operating rooms over 90% of the bacterial contamination of the wounds comes from the air and clean air results in a lower risk. • Airtech Ultra Clean Ventilating (U.C.V) system, which is unique in generating an ultra clean zone free from peripheral entrainment of contaminated air and creates a clear zone larger than its diffuser area, giving protection over instrument tables in addition to the immediate surgical area. BSL4.