An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. VHA PANEL WITH HPA12 CIRCUIT BREAKER PRODUCT PRESENTATION

  2. VHA 12 PANEL • Designed and type tested to meet requirements of IEC 298 & 694 / IS:3427 • Air insulated indoor switchgear • Metal clad construction • Internal arc tested • IP4X degree of protection externally and IP2X between compartments • Independent exhaust vents for all HT compartments

  3. VHA 12 PANEL • Integral Earthing Switch optional • Normal service conditions: Min ambient temp:-5oC, Max ambient temp:+40oC • Up to 3000A in panel without forced cooling • Quality System Certification- ISO 9001 • Environmental Management System- ISO 14001

  4. BREAKER COMPARTMENT • Cassette mounted breaker with isolated position on cubicle front door • Racking in/out of breaker from test to service position and vice-versa with cubicle door closed only • Mechanical interlock to prevent racking in/out of breaker, when breaker is in closed position • Live parts covered by automatic shutters when breaker is racked out

  5. METERING COMPARTMENT • Metering compartment with numerical/static/electro-magnetic relays, indicating meters, lamp and control switches • Protection and measuring apparatus customized as per requirement

  6. CABLE AND CT COMPARTMENT • Spacious construction to accommodate 1 set of CTs and 2 runs of cables • Option of rear extension to accommodate extra CTs or cables • Adequate height for cable termination

  7. PT COMPARTMENT • Withdrawable line PT provided in the breaker panel • Removable fuses mounted on the PT • Safety shutters between PT & Cable compartment close automatically on PT withdrawal

  8. BUSBAR COMPARTMENT • Spacious busbar compartment for adequate air clearances • Option for busbar insulation available • Option for shrouds on joints available

  9. HPA BREAKER • The HPA type circuit breaker is designed and tested to meet requirements of IEC 56 / IS : 13118 • SF6 gas used as insulation and arc interruption medium • Arc control and extinction achieved by puffer principle • Capable of interrupting small magnetizing and capacitive currents

  10. HPA BREAKER • Features of operating mechanism • O-C-O operation without recharging • Closing spring charged by motor in less than 15secs • Electrical anti-pumoing • Provision for manual recharging • Synchronisation and fast auto reclosure duty

  11. HPA BREAKER • The HPA series of CB are designed and type tested to meet the requirements of IEC-60056 / IS:1318 • The HPA series of CB use SF6 gas as insulating and arc interruption medium • Arc interruption and control are achieved by puffer principle • Short arc duration followed by rapid dielectric recovery • Long electrical life, as the interruption system develops low arc energy and contact wear is minimal • Long mechanical life with study and proven operating mechanism - 10000 operations at no load - 10000 operations at rated current

  12. HPA BREAKER • Operationally safe and reliable in wide range of operating temperature-5o to +40o c • Capable of interrupting small magnetizing and capacitive currents • Compact design with relatively light weight construction • Features of operating mechanism • O-C-O operation without recharging • closing spring charged by motor in less than 15 secs. • electrical anti-pumping • provision for manual recharging • synchronization and fast auto-reclosure duty

  13. VHA PANEL CROSS SECTIONAL DWG

  14. VHA 12 PANEL TECHNICAL DETAILS Description Unit Rating Voltage kV 12 Frequency Hz 50 Current A 630, 1250, 1600, 2000, 2500, 3000, 4000 Short time withstand kA 40 current (for 3 secs) Peak withstand current kAp 100 Insulation level kVrms/kVp 28/75 WidthxDepthxHeight mm 800x1370x2340 Weight with breaker (approx.) kg 1000 Degree of Protection-Enclosure IP4X

  15. HPA12 CIRCUIT BREAKER TECHNICAL DETAILS Description Unit Rating Voltage kV 12 Frequency Hz 50 Current A 1250, 1600, 2000, 2500, 3150 Breaking capacity kA 40 Short time withstand kA 40 current (for 3 secs) Peak withstand current kAp 100 Insulation level kVrms/kVp 28/75 Operating sequence O-3min-CO-3min-CO/ O-0.3secs-CO-3min-CO Weight (approx.) kg 190-225

  16. INSTALLATIONS OVER 25,000 PANELS INSTALLED MAJOR INSTALLATIONS AT: • POWER PLANTS • DISTRIBUTION UTILITIES • STEEL PLANTS • CEMENT PLANTS • REFINERIES • VARIOUS INDUSTRIES & IN-FRASTRUCTURE PROJECTS

  17. SUCCESFULL INSTALLATIONS IN GENEARATIONS Major installations of VHA 12S +HPA POWER PLANT LOCATION SF6 SWGR INSTALLED • MSEB ( CHANDRAPUR UNIT IV V &VII ,KORADI) (1989,95,99)- 593 • NTPC ( VINDHYACHAL 500MW)(1995) - 248 • NTPC ( TALCHER 4 X 500MW) (1999) - 451 • APSEB ( RAYALSEEMA 2 X 210 MW) (1998) - 235 • BSES DAHANU ( 2 X 250MW) (1994) - 163 • MPEB SGTPS (1997) - 179 • GIPCL (2 X 125 MW) (1996) - 110 Total SF6 panels installed in Generations in India - 4100Nos ABB’s market share in Generation is 70% !!!

  18. HPA – Arc Interruption principle BBBBBBBB