An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. E90 Technical Presentation 230 Yuma Street Denver, CO 80223 (800) 582-4524 sales@xpcc.com www.xpcc.com

  2. XPC E90 Technical Training Agenda • Product Overview • Options • Design and Operation • Installation • Front Panel • System Operation • Troubleshooting

  3. E90 Product Overview • 208/120V Three-Phase UPS Product snapshot • 10kVA/10kW, 15/15kW, 20kVA/20kW, 208/120V 3Ph Tower UPS • Unity power factor • Compact footprint • UL, cUL, RoHS, FCC A • 2 year electronics, 2 year battery warranty (USA and Canada)

  4. E90 Product Overview Features • Internal Maintenance bypass—manually transfer critical loads from UPS power to utility power • Communication— USB, RS485, RS232, Dry Contacts + 2 communication slots for Web/SNMP, Relay/Dry Contact, Modbus • Charging current—1A to 20A, adjustable from LCD display • 0, I, 2, or 3 Internal Battery Strings • Extended battery packs— optional matching battery cabinets available for extended runtimes • Dual or Single Input. Single input jumpers come pre-installed • Parallel up to 4 modules for capacity or redundancy • Up to 80kVA Full Capacity • Up to 60kVA N+1 Redundant • Field Replaceable Electronics Module

  5. E90 Product Overview Extended Runtimes

  6. E90 Options • Internal and External Battery Options • 0, 1,2,or 3 Strings Internal • 63A External Battery Pack (10kVA) • 125A External Battery Pack (15/20kVA) • Connectivity Options • SNMP-1P3PIN – one port card • SNMP-2P3PIN – 2 port card • Relay-STND – Relay Card • Service Options • 5 x 8 Startup with 1, 2, or 3 Year On-Site Warranty • 7 x 24 Startup with 1, 2, or 5 Year On-Site Warranty • One Year Extended Warranty • 7 x 24 Preventative Maintenance

  7. E90 Design and Operation • Specifications

  8. E90 Design and Operation • E90 One-Line

  9. E90 Design and Operation • E90 Internal – Left Side DC Center-tap Electronics Module External DC Connector External DC Fuses String #1 - String #1 +

  10. E90 Design and Operation • E90 Internal – Right Side DC + Fuses DC - Fuses DC Center-tap String #3 - String #3 + String #2 - String #2 +

  11. E90 Design and Operation • E90 Rear 2 x Intelligent Slots Parallel Comm. Ports Cold Start Power Switch REPO Option Contact Port Local EPO USB Port 2 x Battery Temp RS485 Ports Serial Port Output Breaker Maintenance Bypass Breaker Mains Input Breaker External Battery Connector Bypass Input Breaker AC Connection Terminal

  12. E90 Installation • Thermo-magnetic circuit-breaker • IEC 60947-2 trip curve D (normal) • Sized for 125% of the current as listed below. • 10Kva: 40A Input Circuit Breaker required. * • 15Kva: 60A Input Circuit Breaker required. • 20Kva: 80A Input Circuit Breaker required. • * If the battery charger current is to be programmed to 15A or higher, increase the 10kVA input circuit breaker to 45A • Wiring • Wiring shall be in accordance with local and national electrical codes. • Recommended cabling sizing:

  13. E90 Installation • AC Connection Terminal

  14. E90 Installation • External Battery Connection • Up to 4 x XPC EBP80 cabinets • Can use 3rd party battery system

  15. E90 Front Panel • Buttons and LEDs Alarm LED Bypass LED Battery LED Inverter LED Scroll Button Enter Button On Button

  16. E90 Front Panel • LCD Display - Main Working Mode UPS Status Time and Date Bypass Data Display Items Input Data Battery Data Events and Faults ID Number

  17. E90 Front Panel • LCD Display - Data • Press the scroll key for approximately 1 sec. to highlight Data. • The Data page will display all three phases of input and output voltage, current, and frequency and output load percentage

  18. E90 Front Panel • LCD Display - Data • While in the Data page, additional data pages to view will be shown on the right side of the screen. • Input: Press ENTER key for approximately 1 sec. The display will show all three phases of the Main voltage, current, and frequency and the Bypass voltage and frequency.

  19. E90 Front Panel • LCD Display - Data • Output: Press the scroll key for approximately 1 sec. The display will show all three phases of the Output voltage, current, and frequency.

  20. E90 Front Panel • LCD Display - Data • Battery: Press scroll key for approximately 1 sec. The display will show the Battery voltage, current, estimated battery runtime and battery capacity .

  21. E90 Front Panel • LCD Display - Data • Load : Press the scroll key for approximately 1 sec. The display will show all three phases of the Load %, kW, and kVA .

  22. E90 Front Panel • LCD Display - Data • Inside: Press the scroll key for approximately 1 sec. The display will show the internal V-BUS (DC bus voltage), T1/T2 (Temperature 1 and Temperature 2), V-Inv (Inverter Voltage), and F-Inv (Inverter Frequency) .

  23. E90 Front Panel • LCD Display - Info • Press the scroll key for approximately 3 sec. to exit Data, and press the scroll key for approximately 1 sec. move to Info. • The display will show LCD, PFC, and INV software versions and power rating .

  24. E90 Front Panel • LCD Display – Setting-User • Press the scroll key for approximately 1 sec. to move to the setting page, then press ENTER key to enter setting-user page. • Press the scroll key to change item, press ENTER key to enter item and press the scroll key to change value, press ENTER key confirm the setting.

  25. E90 Front Panel • LCD Display – Setting-Maintenance • Maintenance : Press Scroll + ENTER key to enter maintenance and display a password window. • Press Scroll to change the number and press ENTER to select the value, the password is “1121”

  26. E90 Front Panel • LCD Display – Setting – Maintenance - System • Once the Maintenance password is entered, press the Enter key. • The UPS goes into the Setting-System window. • Press the Enter key to enter item and confirm value, press the Scroll key to change the value.

  27. E90 Front Panel • LCD Display – Setting – Maintenance - System • 1) Factory default setting for Working Mode is ECO. To disable ECO, reprogram Working Mode to Normal or Parallel. • 2) Must be in static bypass to change • 3) If not in static bypass, output will drop load • 4) This is the MODBUS device address used for RS232 & RS485 communication ports. • a. Press Scroll key to set the address. • b. When battery temperature sensor is open, choose ID 1~10 & 13~15 • c. If UPS is set for parallel mode and device address <= parallel quantity, device address = parallel ID • d. Press “ON” to exit the device address setting and save the device address setting value and parallel ID setting. • e. Note: Under single UPS mode, until this device address setting save and exit, single UPS setting is done. • 5) OFF turns off the sensor switch, ON turns on the sensor switch and send query command to sensor with address • 11 and 12 every second. .

  28. E90 Front Panel • LCD Display – Setting – Maintenance - Bypass • Press the Scroll key to highlight Bypass and press the Enter key to enter the Setting-Bypass window. • Press the Enter key to enter item and confirm value, press the Scroll key to change the value.

  29. E90 Front Panel • LCD Display – Setting – Maintenance - Battery • Press the Scroll key to highlight Battery and press the Enter key to enter the Setting-Battery window. • Setting-Battery: press the Enter key to enter item and confirm value, press the Scroll key to change the value.

  30. E90 Front Panel • LCD Display – Setting – Maintenance - Battery 1. Number is the number of batteries per string 2. Capacity is the Amp-Hour rating of the batteries per string 3. Group is the number of strings of batteries 4. I-Maxcharge is the maximum charger current. Setting this above 15A on the E90-10kVA increases the input current rating and requires an input circuit for 45A .

  31. E90 Front Panel • LCD Display – Setting – Maintenance - Parallel • Press the Scroll key to highlight Parallel and press the Enter key to enter the Setting-Parallel window. • Press the Enter key to enter item and confirm value, press the Scroll key to change the value.

  32. E90 Front Panel • LCD Display – Setting – Maintenance - Parallel 1. ID - Program each UPS in Parallel with a unique ID 2. Number - Program the total number of UPS systems in parallel. Maximum of 4 in parallel. 3. Redu. Num. – Program to the total number of UPS systems in parallel to be used for redundancy

  33. E90 Front Panel • LCD Display – Record • Displays event records and fault records. Displays the Index (number in list), Time of event or fault, State (Mode) of UPS and event or fault. • Press the scroll key for approximately 1 sec. to move to the Record page, then press ENTER key to enter.

  34. E90 Front Panel • LCD Display – Record • Press the scroll key to select Up or Down or Delete. Press ENTER key to confirm. • If Delete is selected, all event or fault records will be deleted..

  35. E90 Troubleshooting • Troubleshooting begins by identifying the alarm

  36. E90 Troubleshooting

  37. E90 Troubleshooting

  38. E90 Troubleshooting • Service Manual contains Table based on fault code and lists most probable cause

  39. E90 Troubleshooting • Service Manual contains Appendix A: UPS Fault Judgement

  40. The end, questions? Xtreme Power Conversion 230 Yuma Street Denver, CO 80223 800.582.4524 Sales & Customer Support1-800-582-4524 ext 1sales@xpcc.com Technical Support & Service1-800-582-4524 ext 2support@xpcc.comservice@xpcc.com Marketingmarketing@xpcc.com