1 / 108

CLOSE CONTROL UNIT

CLOSE CONTROL UNIT. By Olivier Lenglet. RANGE DESCRIPTION. Range description. 2 Families. Close Control Unit – INNOV@. Telecom Unit – @DNOVA. Capacity kW. Range description. 4 ranges. DX from 6 to 20kW. INNOV@ CENTRIFUGAL. Medium size : DM. Chilled water from 8 to 22kW.

beau
Télécharger la présentation

CLOSE CONTROL UNIT

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. CLOSE CONTROL UNIT By Olivier Lenglet

  2. RANGE DESCRIPTION

  3. Range description 2 Families Close Control Unit – INNOV@ Telecom Unit – @DNOVA Capacity kW

  4. Range description 4 ranges DX from 6 to 20kW INNOV@ CENTRIFUGAL Medium size : DM Chilled water from 8 to 22kW INNOV@ECFAN Chilled water from 8 to 236kW High size : DH INNOV@ECFAN DX from 20 to 120kW DX from 7 to 70kW INNOV@ENERGY DX from 2.5 to 26kW @DNOVA

  5. INNOV@ Codification Codification : D H x x x 0000 INNOV@CENTRIFUGAL & INNOV@ECFAN Medium size DM INNOV@ECFAN High size DH IN INNOV@ENERGY TH @DNOVA

  6. INNOV@ Operating mode Codification : D H A x x 0000 A Air cooledwithremote condenser W Water cooled with remote dry-cooler Z Water cooled for city tap water

  7. INNOV@ Operating mode Codification : D H C x x 0000 C Chilled water Dual Cooling • Air cooledwithremote condenser more • chilled water coil D

  8. INNOV@ Operating mode Codification : D H K x x 0000 • Water cooled with remote dry-cooler • more • chilledwater coil K Dual Cooling Dual Cooling • Water cooled for city tap water • more • chilled water coil Q

  9. INNOV@ Operating mode Codification : D H F x x 0000 • Water cooled with remote dry-cooler • And indirect free-cooling F

  10. Return air INNOV@ Operating mode Indirect Free-cooling Onlyavailable for unit water-cooled with dry-cooler Itisnot and option thisis a type of unit Dry Cooler

  11. INNOV@ airflowconfiguations Codification : D H x D x 0000 Downflow discharge D Upflow discharge U Displacement X

  12. INNOV@ Fans Codification : D H x x R 0000 Centrifugale For capacity from 6kW to 22kW C High pressure fan as an option Psd =100 à 250 Pa Radial plug fan For capacity from 6kW to 236W R Plug Fan with EC motor (std) Aesp =140 à 560 Pa 600mm for DM 795 or 950mm for DH

  13. INNOV@ Codification Codification : D H A D R 0 5 9 2 • DH = INNOV@ A = Air cooledwithremote condenser • D = Downflow discharge • R = Radial plug fan with EC motor • Capacity kW in this case 59kW • Number of compressors/circuits in this case 2 comp/2 circuits • 0 or 1 = 1 compressor / 1 ref. circuit or chilled water unit • 2 = 2 compressors/2 circuits • 4 = 4 compressors/2 circuits • One exception 0205 whichmean 20.5kW withonly 1 compressor/1 circuit

  14. INNOV@ General features • Refrigerant: R407c et R410a • Refrigerant components • Scroll compressor • Plate heatexchanger AISI304 • Filterwithmolecularsieve and activated alumina. • Sight glass withhumidity indication. • Thermostatic valve with MOP function and externalequalization. • Liquidreceiver • HP pressostat withmanual reset • LP pressostat withautomatic reset • Schrader valves for maintenance and/or Control. • Hydrophiliccoiltreatment: • Allows film condensation in dehumidification • Process • No water dragging, especially in downflow units

  15. RANGE DESCRIPTIONDM • 6 - 21kW direct expansion • 8 - 23kW chilled water

  16. INNOV@ DMDXCSizes

  17. INNOV@ DMDXRSizes

  18. INNOV@ DMCWCSizes

  19. INNOV@ DMCWCSizes

  20. DM architecture Double inlet centrifugal fan

  21. DM architecture • Downflow discharge • Direct expansion • Air cooled Filter Control Electrical panel Electricalheater Centrifugal fan TXV Compressor Humidifier DMADC

  22. DM architecture • Downflow discharge • Chilled water Control Filter Electrical panel 3 or 2-way valve With actuator Humidifier DMCDC

  23. DM architecture • Upflow discharge • Chilled water Control Electrical panel Electricalheater Filter 3 or 2-way valve With actuator Humidifier DMCUC

  24. DM architecture Plug fan with EC motor

  25. Plug fan with EC motor Standard for ranges DM__R, DH__R, ENERGY ZIEHL ABEGG EC Blue for DM EBM for DH / ENERGY Aesp =350 à 450 Pa

  26. Plug fan with EC motor Brushlesssynchronous motor

  27. Plug fan with EC motor Better motor efficiency 90 EC-Motor 80 3~AC 70 1~AC 60 50 Motor efficiency [%] 40 30 20 10 0 50 100 150 200 250 300 350 400 450 500 Motor Power [W]

  28. Plug fan with EC motor Startingcurrent AC/EC AC motor : Inrush current around 3.5 the nominal input current No inrush And Speed ramp up

  29. Plug fan with EC motor EC-Motor Features • Energy Savings • Excellent noise behaviour • Compact design • Commutation electronics is integrated into the motor including EMC and mains supply filter for ease of installation • PFC (power-factorcontrol) • Integrated motorprotection •  no additional wiring,  no additional componentsnecessary • Motor andelectronicsareoptimallymatched • Maintanencefreeoperationwithlonglife time

  30. Plug fan with EC motor Next improvment EBM - RADICAL Plastic Impeller with Aerodynamically optimized shape To increase the efficiency and reduce the noise level (up to 50%) Availableyet on ENERGY

  31. DM architecture

  32. DM architecture • Downflow discharge • Direct expansion • Air cooled Control Filter Electrical panel Electricalheater Compressor Humidifier DMADR

  33. DM architecture • Downflow discharge • Chilled water Control Filter Electrical panel Electricalheater 3 or 2-way valve With actuator Humidifier DMCDR

  34. DM architecture • Upflow discharge • Direct expansion • Air cooled Electricalheater Control Electrical panel Filter Compressor Humidifier DMAUR

  35. DM architecture • Upflow discharge • Chilled water Electricalheater Control Electrical panel Filter 3 or 2-way valve With actuator Humidifier DMCUR

  36. RANGE DESCRIPTIONDH • 20 - 120kW direct expansion • 30 - 210kW chilled water

  37. INNOV@ DH Sizes

  38. INNOV@ DH Sizes

  39. INNOV@ DH Sizes

  40. INNOV@ DH Sizes

  41. INNOV@ DH Sizes

  42. INNOV@ DH Sizes

  43. INNOV@ DH Sizes • Chilled water • Only downflow configuration

  44. INNOV@ DH Sizes • Chilled water • Only downflow configuration

  45. DH architecture • Downflow discharge • Direct expansion • Air cooled Filter Control Electrical panel Electricalheater Compressor Humidifier DHADR

  46. DH architecture • Downflow discharge • Chilled water Filter Control Electrical panel 3 or 2-way valve With actuator Electricalheater Humidifier DHCDR

  47. DH architecture • Upflow discharge • Direct expansion • Air cooled Radial fan Electricalheater Control Electrical panel Compressor Filter Humidifier DHAUR

  48. DH architecture • Upflow discharge • Chilled water Radial fan Electricalheater Control Electrical panel Filter 3 or 2-way valve With actuator Humidifier DHCUR

  49. DH architecture • Downflow discharge • Direct expansion • Water cooled Filter Control Electrical panel Compressor Electricalheater Plateheatcondenser Humidifier DHWDR

  50. RANGE DESCRIPTIONENERGY • 9- 70kW direct expansion