SITOP power flexi The power pack handles it all - from 3 to 52V

SITOP power flexi The power pack handles it all - from 3 to 52V. SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i. SITOP power flexi Special features. Output voltage adjustable from 3 to 52 V

cheche
Télécharger la présentation

SITOP power flexi The power pack handles it all - from 3 to 52V

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. SITOP power flexiThe power pack handles it all - from 3 to 52V SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i

  2. SITOP power flexiSpecial features • Output voltage adjustable from 3 to 52 V • By using a potentiometer or analog input signal (0 to 2.5 V) • Can even be adjusted dynamically during operation • Max. output current adjustable from 2 to 10 A • By using a potentiometer or analog input signal (0 to 2.5 V) • Current monitoring • Output current depending on the analog signal (0 to 2.5 V) • Red LED indicates when the set current limit is reached • Additional functions • Automatic power limitation to 120 W • Sense line for precise voltage to power load • Power-ok signal provided as a relay contact • Power-fail signal SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i

  3. SITOP power flexiApplication areas and customer advantages • One device for different applications • Lower logistics costs • Easier to configure • Easier to service • Standard device instead of special power pack • For “non-standard” voltages between 3 and 52 Volt • For applications, with a need for a direct current, which can be changed dynamically • lab applications, testing systems, control of DC motors etc. • For load control with integrated current monitoring • As battery charger due to adjustable current limitation • All the advantages of a standard SITOP power device (e.g., industrial capability, ready to use, high quality, compliance with all pertinent international standards,) • Comparable price to standard Dc 24V/ 100 watt unit SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i

  4. SITOP power flexiOutput characteristic 60 50 SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i 40 30 Volt 1 ) 20 2 ) 10 0 0 2 4 6 8 10 12 Ampere 1) Range of adjustment for output voltage2) Range of adjustment for current limiting

  5. SITOP power dual 15VMounted quickly, even at ±15 V! SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i

  6. SITOP power dual 15VSpecial features and customer advantages • Industrial-capacity, compact device for the switching cabinet • Wide-range input (93 to 264 V AC) for worldwide use • Two floating outputs (15 V DC/3.5 A) • Can be used in parallel for 15 V/ 7 A (single output) • In series for ±15 V/ 3.5 A (dual output) • Simple compensation of power losses • Outputs adjustable from 14.5 to 17 V with potentiometer in front • Extremely easy to handle • Fast mounting on standard DIN rail • Easy wiring SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i

  7. SITOP power dual 15VApplication areas • General mechanical engineering • Powering of electronics • Powering of operation amplifiers • Laser processing machines • Powering of deflection mirrors of laser heads(e.g., with laser inscribers) • Measuring technology • Powering of measuring converters SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i

  8. SITOP power 0.5 - Power out of 22.5 mmIdeal for low-voltage switchgear SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i

  9. SITOP power 0.5Special features • AC version: 24 V/ 0.5 A • DC version: 24 V/ 0.375 A • Wide range input • AC version: Urated= 120 - 230V AC (87 ... 264V AC) • DC version: Urated= 48 - 220V DC (30 ... 264V DC, 30 ... 187V AC) • Width: 22.5 mm • Weight: 0.11 kg (AC) / 0.14 kg (DC) • Temperature range: -20° to +70° C SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i

  10. SITOP power 0.5Customer benefits • Space savings • Due to narrow width and minimum space requirement • Optimal for use in switching cabinet • Cost savings • Due to use of 24 V standard contacter and relay types for "odd" voltages • Due to reduced number of models because of wide-range input • Time savings due to availability from warehouse • Worldwide use • Certifications in according with UL and cUL SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i

  11. SITOP power 2-phase 20AFor high network voltages SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i

  12. SITOP power 2-phase 20A Special features and application areas • 24VDC /20 A DC for 3-phase networks in 480 and 575 VAC • 2-phase power supply • No need for line protection of third phase • Single phasing doesn‘t require additional protection devicesas recommended with 3w-phase power supplies • Wide- input voltage range from 420-682 VAC for ... • 575VAC 3-phase networks in the USA and Canada • Highest protection against voltage fluctuations in case of unstable network conditions • Adjustable output voltage from 22.8 to 28.8 V • Devices can be switched in parallel • Provides agency approvals for the North American market • UL, cUL, CSA SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i

  13. Power supplies in SIMATIC design • Optimal for SIMATIC S7-200 • AC 120/230 V, 24 V/ 3.5A • RFI specification class B • Parallel connection possible • Slim like the SIMATIC ET200B • AC 120/230 V, 24 V/ 5 A and 10 A • Optimal for use with distributed I/O device • Minimum width requirements when used with a mounting bracket (2.5 inch width even for 10 amp unit)) SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i

  14. Power supply with degree of protection IP65 Optimal for the SIMATIC ET 200X • Single phase 120/230 VAC, 24 VDC/10A • Design adapted to SIMATIC ET200X • 24 VDC via back plane bus for electronics/ encoders and/or load • 24 VDC via screw-type terminals for loads • Choice after short circuit: • Automatic restart • Switch off • For use under roughest conditions from -25 to +55°C • Can be installed in any position SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i

  15. SITOP power with direct current and universal connection • Direct current input (DC/DC 2A) • For 48/60/110 V battery networks via DC input 38 to 121 V • Universal connection (2.5/4/10 A) • For 120 V and 230 V power networks without switching thanks to wide-range input range from 93 to 264 V AC • For 220 VAC - battery systems. DC operation within 110 to 350 V possible • Parallel connection for redundancy and power increase • Design adapted to SIMATIC AG 95/100 (2.5/ 4A) SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i

  16. Power supplies for AS-interface • 30 VDC /2.4 A in class of protection IP 65 • Input voltage from 20.4 to 28.VDC • Only 57 mm mounting depth • No mounting restrictions • Ambient temperaturefrom -25° to +55°C • 30 V/7 A with wide input voltage range from • 93 to 264 VAC or 110 to 350 VDC • Can be snapped on standard DIN rail or specific S7-300 rail • Data buffering according to the AS-i specification • Also suitable for public low voltage networks SITOP power flexi SITOP power dual SITOP power 0.5 2-phase 20A In SIMATIC design DC/UC- Input For AS-i