Fire Detection and Fire Fighting in ALICE

Smoke detection in UX cavern and Counting Rooms in PX Alarms sent to CSAM (+ DCS for info) SNIFFER system in the experimental apparatus Alarms sent to CSAM + DCS for info and action Automatic fire fighting in the ITS volume by means of N 2 flush

elan
Télécharger la présentation

Fire Detection and Fire Fighting in ALICE

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Smoke detection in UX cavern and Counting Rooms in PX Alarms sent to CSAM (+ DCS for info) SNIFFER system in the experimental apparatus Alarms sent to CSAM + DCS for info and action Automatic fire fighting in the ITS volume by means of N2 flush Automatic fire fighting in the racks under the Muon-arm by means of CO2 flush Fire Detection andFire Fighting in ALICE Marc Tavlet / Alice GLIMOS

  2. Sniffer system to detect leak of flammable gas emission of smoke (fire) lack of oxygen …in the experimental apparatus ! Sniffer racks equipped with pumps and detectors Alarms sent to CSAM + DCS The SNIFFER Sampling Network Marc Tavlet / Alice GLIMOS

  3. SNIFFER network in L3 Flam.Gas + Smoke Sniffer racks B 18 and B 19 to Muon-arm L3 chicane 2 br. to EMC rail 12 br. to Back-Fr. 12 br. to Mini Fr. 8 br. to HMPID 2 br. to ITS 9 br. to Sp-Fr Marc Tavlet / Alice GLIMOS

  4. SNIFFER network in L3 Oxygen-Deficiency Hazard Sniffer racks B 18 and B 19 to Muon-arm L3 chicane 2 branches to upper volume 2 branches to mid volume 2 branches to lower volume Marc Tavlet / Alice GLIMOS

  5. SNIFFER network in Muon arm Flam.Gas + Smoke Sniffer racks B 18 and B 19 L3 chicane 4 branches above st. 4, 5 for smoke 4 branches above Trig for smoke 2 branches for St. 3 (in dipole) 4 branches below Trig for gas 2 branches in FASS Marc Tavlet / Alice GLIMOS

  6. SNIFFER network in Muon arm Oxygen-Deficiency Hazard 2 lines Sniffer racks B 18 and B 19 L3 chicane “point” 2 branches in dipole 2 branches in FASS Marc Tavlet / Alice GLIMOS

  7. SNIFFER Sampling Network Recapitulation Marc Tavlet / Alice GLIMOS

  8. Tuyaux = NBR ‘Silverpress’ Diamètres : lignes = 7.5/13.5 mm branches principales = 6/10 branches finales = 4/7 Dans une ligne, toutes les branches doivent avoir la même longueur (+/- 10%) Connecteurs disponibles – Tés et croix SNIFFER Sampling Network Données Techniques Marc Tavlet / Alice GLIMOS

  9. Filling from truck 8 m3 of N2 at 200 bar 60 m3 of Ar/N2 mixture at 22.5 bar 52/54 mm steel pipes Main Valve With padlock 1st-flush Valve 2nd-flush Valve to UX-25 via PX-24 Ventil. Unit for ITS to ITS in L3-Magnet Fire fighting in ITS volume by N2 flush Marc Tavlet / Alice GLIMOS

  10. Area C, below the μ platform is difficult to access. Automatic fire fighting installation with CO2, Triggered from DCS-DSS. Local alarm (siren) needed before triggering. 1 bottle/rack (L = 80 cm, Ø = 15 cm) Best offer = 1152 CHF/rack (instead of 900) + maintenance for 5y (232 CHF/rack) Fire fighting in racks, area C by CO2 flush Marc Tavlet / Alice GLIMOS

  11. General smoke detection by TS-CSE, OK SNIFFER by TS-CSE EDMS doc for ALICE in preparation Installation by summer 2006 N2 flush in ITS by ALICE + TS-CV EDMS doc in preparation CO2 flush in C-racks by PH-CMM Installation by end 2006 Summaries of fire detection and fire fighting in ALICE Marc Tavlet / Alice GLIMOS