1 / 35

IZBOR ELEMENATA PRIMARNE OPREME

IZBOR ELEMENATA PRIMARNE OPREME. “PROJEKTIRANJE ELEKTRIČNIH POSTROJENJA”. ELEKTRIČNA POSTROJENJA. UNUTARNJA IZVEDBA. VANJSKA IZVEDBA. OTVORENA POSTROJENJA ZATVORENA POSTROJENJA PLINOM IZOLIRANA POSTROJENJA. OTVORENA POSTROJENJA ZATVORENA POSTROJENJA.

elle
Télécharger la présentation

IZBOR ELEMENATA PRIMARNE OPREME

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. IZBOR ELEMENATA PRIMARNE OPREME “PROJEKTIRANJE ELEKTRIČNIH POSTROJENJA”

  2. ELEKTRIČNA POSTROJENJA UNUTARNJA IZVEDBA VANJSKA IZVEDBA • OTVORENA POSTROJENJA • ZATVORENA POSTROJENJA • PLINOM IZOLIRANA POSTROJENJA • OTVORENA POSTROJENJA • ZATVORENA POSTROJENJA

  3. PRIMARNA OPREMA ELEKTRIČNOG POSTROJENJA

  4. I. NAPREZANJA PRIMARNE OPREME ELEKTRIČNOG POSTROJENJA (HRN-HD 637) • NAPONSKA NAPREZANJA • STRUJNA NAPREZANJA • MEHANIČKA NAPREZANJA (POTRESI I SL.) • KLIMATSKI UTJECAJ • UTJECAJ OKOLIŠA KOJI SE OČEKUJE NA LOKACIJI POSTROJENJA

  5. ELEKTRIČNI ZAHTJEVI • NAČINI POSTUPANJA S NEUTRALNOM TOČKOM • RAZREDBA NAPONA • STRUJA U NORMALNOM POGONU • STRUJA KRATKOG SPOJA • NAZIVNA FREKVENCIJA • KORONA

  6. PRORAČUN STRUJA KS-a(HRN HD 533) VRSTE KRATKIH SPOJEVA: • TROPOLNI KS • DVOPOLNI KS • ZEMLJOSPOJ • DVOPOLNI KS S ISTODOBNIM SPOJEM SA ZEMLJOM • DVOSTRUKI ZEMLJOSPOJ

  7. JEDNOPOLNI KS

  8. DVOPOLNI KS

  9. DVOPOLNI KS S ISTOVREMENIM SPOJEM SA ZEMLJOM

  10. TROPOLNI KS

  11. PRORAČUN STRUJA KS-a (2) U struji kratkog spoja razlikujemo tri struje presudne za dimenzioniranje i odabir elemenata rasklopnog postrojenja: • UDARNA STRUJA KS-a, • PREKIDNA STRUJA KS-a i • STRUJA MJERODAVNA ZA UGRIJAVANJE

  12. ODREĐIVANJE NAJVEĆE STRUJE ZA RAZLIČITE VRSTE KS-a

  13. ODREĐIVANJE UDARNE STRUJE KRATKOG SPOJA TROPOLNI KS JEDNOPOLNI KS Ik'' – efektivna vrijednost struje neposredno nakon nastanka kratkog spoja, Zd''– zbroj subtranzijentne (početne) reaktancije generatora i impedancije u direktnom sustavu od generatora do mjesta kratkog spoja, V – efektivna vrijednost faznog napona mreže, k – faktor u ovisnosti o omjeru R/X zadane mreže.

  14. ODREĐIVANJE PREKIDNE STRUJE KRATKOG SPOJA -Ia VRIJEDNOST ISTOSMJERNE KOMPONENTE U TRENUTKU ODVAJANJA KONTAKATA -EFEKTIVNA VRIJEDNOST STRUJE KOJA PROTIČE KROZ PREKIDAČ U TRENUTKU ODVAJANJA KONTAKATA

  15. ODREĐIVANJE STRUJE MJERODAVNE ZA UGRIJAVANJE

  16. MEHANIČKI ZAHTJEVI • NORMALNO OPTEREĆENJE • OPTEREĆENJE USLIJED ZATEZANJA • OPTEREĆENJE USLIJED IZVOĐENJA • OPTEREĆENJE USLIJED LEDA • OPTEREĆENJE USLIJED VJETRA • SILE USLIJED SKLAPANJA • SILE USLIJED KRATKOG SPOJA • OTPUŠTANJE VODIČA • VIBRACIJE • DIMENZIONIRANJE NOSIVIH KONSTRUKCIJA

  17. KLIMATSKI UVJETI IUVJETI OKOLIŠA • TEMPERATURA • NADMORSKA VISINA I TLAK • VLAŽNOST • OBORINE • ONEČIŠĆENJE • SUNČEVO ZRAČENJE

  18. POSEBNI ZAHTJEVI • POSTROJENJA NA VELIKIM NADMORSKIM VISINAMA • UČINCI MALIH ŽIVOTINJA I MIKROORGANIZAMA • RAZINA BUKE • UČINCI POTRESA

  19. II. IZOLACIJA • KOORDINACIJU IZOLACIJE USKLADITI S EN 60071-1 I EN 60071-2 • EN 60071-1 DEFINIRA VRIJEDNOSTI NAJVIŠEG NAPONA OPREME Um • EN 60071-2 DEFINIRA ODGOVARAJUĆE MINIMALNE RAZMAKE

  20. NAJMANJI IZOLACIJSKI RAZMACI U ZRAKU ZA AKTIVNE DIJELOVE (1)

  21. NAJMANJI IZOLACIJSKI RAZMACI U ZRAKU ZA AKTIVNE DIJELOVE (2)

  22. NAJMANJI IZOLACIJSKI RAZMACI U ZRAKU ZA AKTIVNE DIJELOVE (3)

  23. III. OPREMA • SABIRNICE • PREKIDAČI • OSIGURAČI • RASTAVLJAČI • MJERNI TRANSFORMATORI • ODVODNICI PRENAPONA • IZOLATORI

  24. 1. SABIRNICE DIMENZIONIRANJE: • OBZIROM NA MAKSIMALNU STRUJU U NORMALNOM POGONU • OBZIROM NA DOZVOLJENO POVIŠENJE TEMPERATURE ZA VRIJEME KRATKOG SPOJA • OBZIROM NA MEHANIČKA NAPREZANJA ZA VRIJEME KRATKOG SPOJA

  25. MAKSIMALNA STRUJA U NORMALNOM POGONU • LOCIRATI NAJVIŠE OPTEREĆENI DIO SABIRNICA U NORMALNOM POGONU, ALI I U SLUČAJU n-1 • VODITI RAČUNA O PROPISIMA KOJI ODREĐUJU MINIMALNE PRESJEKE ODNOSNO PROMJERE CIJEVNIH SABIRNICA • PROVJERITI TRAJNU STRUJU ODABRANIH SABIRNICA TE IZVRŠITI KOREKCIJE U OVISNOSTI O DOZVOLJENOJ NADTEMPERATURI

  26. KONTROLA PRESJEKA OBZIROM NA UGRIJAVANJE ZA VRIJEME KS-a • RAČUNSKIM PUTEM ODREDITI PRESJEK SABIRNICA TE GA USPOREDITI S PRESJEKOM ODABRANOG TIPA SABIRNICE ZA BAKAR ZA ALUMINIJ

  27. KONTROLA PRESJEKA SABIRNICA OBZIROM NA MEHANIČKA NAPREZANJA ZA VRIJEME KS-a • ODREDITI RAZMAK SABIRNICA POJEDINIH FAZA TEMELJEM PROPISA, A U OVISNOSTI O NAPONSKOJ RAZINI • ODREDITI RAZMAK POTPORNIH IZOLATORA • IZRAČUNATI MAKSIMALNI MOMENT SAVIJANJA U UPORIŠTIMA • ODREDITI LINIJSKI OTPORNI MOMENT • ODREDITI MAKSIMALNO NAPREZANJE I USPOREDITI GA S DVOSTRUKOM VRIJEDNOSTI GRANICE TEČENJA ODABRANOG MATERIJALA SABIRNICA

  28. 2. PREKIDAČI DIMENZIONIRANJE: • OBZIROM NA NAZIVNI NAPON • OBZIROM NA MAKSIMALNU STRUJU U NORMALNOM POGONU • OBZIROM NA VRIJEDNOST PREKIDNE STRUJE Ipr • KONTROLA OBZIROM NA UDARNU STRUJU KS-a

  29. VRSTE PREKIDAČA • ULJNI • MALOULJNI • HIDROMATSKI • PNEUMATSKI (KOMPRIMIRANI ZRAK, SF6) • VAKUUMSKI PREKIDAČI • ZRAČNI PREKIDAČI

  30. 3. OSIGURAČI • ZAŠTITA OD KS-a I PREOPTEREĆENJA • UPORABA VN OSIGURAČA DO 35 kV • UGRADNJA NA MJESTU SMANJENJA PRESJEKA I POČETKU ŠTIĆENOG VODIČA • SELEKTIVNOST - OMJER NAZIVNIH STRUJA SUSJEDNIH OSIGURAČA >= 1,6 • IZBOR - PREMA NAZIVNOM NAPONU I STRUJI

  31. 4. RASTAVLJAČI VIDLJIVO ODVAJANJE DIJELOVA POD NAPONOM OD OSTALIH DIJELOVA KOJI NISU POD NAPONOM DIMENZIONIRANJE OBZIROM NA: • NAZIVNI NAPON RASTAVLJAČA • MAKSIMALNU STRUJU U NORMALNOM POGONU • KONTROLA OBZIROM NA UDARNU STRUJU KS-a I STRUJU MJERODAVNU ZA UGRIJAVANJE

  32. 5.MJERNI TRANSFORMATORI 5.1 STRUJNI MJERNI TRANSFORMATORI • PRIKLJUČAK ZAŠTITNIH I MJERNIH UREĐAJA NA SEKUNDARNE STEZALJKE • IZBOR PRIMARNE STRUJE PREMA MAKSIMALNOJ STRUJI U NORMALNOM POGONU • SEKUNDARNA STRUJA 5A ILI 1A • BROJ PRIKLJUČENIH INSTRUMENATA ODREĐUJE SNAGU STRUJNOG TRANSFORMATORA • KLASA STRUJNOG TRANSFORMATORA

  33. 5.2 NAPONSKI MJERNI TRANSFORMATORI • IZVEDBA KAO U TRANSFOMRATORA SNAGE • INDUKTIVNI ILI KAPACITIVNI TRANSFORMATORI • PRIMARNI NAPON ODGOVARA LINIJSKOM ILI FAZNOM NAPONU POSTROJENJA • SEKUNDARNI NAPON IZNOSI 100V ILI 100/√3V • SNAGU DEFINIRAJU PRIKLJUČENI INSTRUMENTI NA SEKUNDARU

  34. 6. ODVODNICI PRENAPONA • NAZIVNI NAPON ODVODNIKA VEĆI OD NAJVEĆEG POVREMENOG POVIŠENJA POGONSKOG NAPONA UP0 UP0=cu*cf*Um/√3 cu=1,07 cf=1,3 izravno uzemljena mreža cf=1,74 izolirana ili “gašena” mreža Um-najveća vrijednost linijskog pogonskog napona • PRORADNI NAPON - DJELOVANJE ODVODNIKA • PREOSTALI NAPON - MANJI OD NAPONSKE RAZINE IZOLACIJE ŠTIĆENOG UREĐAJA (POSTROJENJA) • VENTILNI ODVODNICI, CIJEVNI ODVODNICI, BROJAČI PRORADE ODVODNIKA

  35. 7. IZOLATORI 7.1 POTPORNI IZOLATORI ODABIR SE VRŠI PREMA: • NAZIVNOM NAPONU I VELIČINI SILE KOJA SE PRENOSI NA IZOLATOR • TIPOVI: PORCULAN, UMJETNA SMOLA 7.2 PROVODNI IZOLATORI ODABIR SE VRŠI PREMA: • NAZIVNOM NAPONU • MAKSIMALNOJ STRUJI U NORMALNOM POGONU • MEHANIČKIM NAPREZANJIMA ZA VRIJEME KS-a • UGRIJAVANJU ZA VRIJEME KS-a