1 / 68

VIGILOHM insulation monitoring devices

VIGILOHM insulation monitoring devices. by Patrick HENRY Business Development Manager Energy Management Solutions. Contents. Introduction – What is Vigilohm? Earthing arrangements Applications How does Vigilohm work? The Vigilohm offer Strong points Conclusion.

gaia
Télécharger la présentation

VIGILOHM insulation monitoring devices

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. VIGILOHMinsulation monitoring devices by Patrick HENRY Business Development Manager Energy Management Solutions

  2. Contents • Introduction – What is Vigilohm? • Earthing arrangements • Applications • How does Vigilohm work? • The Vigilohm offer • Strong points • Conclusion

  3. Section 1 - Introduction What is Vigilohm?

  4. What is Vigilohm? • Vigilohm is the range of Insulation Monitoring Devices for Schneider Electric. • Used in IT earthing arrangements, the solution • Guarantees process continuity in case of earth fault, • Improves staff and process safety, and • Optimizes maintenance.

  5. Vigilohm products and solutions Level 1 Level 2 Level 3 Manual fault location Automatic fault location Measurement per feeder

  6. Insulation monitoring device (IMD) functions • Level 1 : fault detection and signaling, manual fault location (all IMDs) IM9: for AC networks only IM9OL: for off-line motor monitoring (TN, TT or IT networks) IM10, IM20: for AC and DC networks XGR, XRM: fault location is done manually (current probe + mobile detector) • Level 2 : automatic fault locationXM200 + XD devices + use of current probe + mobile detector • Level 3 : feeder measurement + communication XML / XM300C + XL devices, XD devices XLI, XTU interfaces

  7. Section 2 Earthing Arrangements

  8. The letters in earthing arrangements • 1st letter represents the transformer neutral connection to earth T (terre – earth) or I (isolated) • 2nd letter represents the load frame connection:frame connected to earth (T) or neutral (N) Grounded neutral Ungrounded neutral Grounded load frame Load frame connected to neutral

  9. MV LV L1 L2 L3 N PE RB RA TT earthing arrangements • The exposed conductive parts of the installation are connected to an earth electrode (Ra) which is electrically separated from the LV substation earth electrode (Rb). • Protection by RCDs

  10. L1 L1 L2 L2 L3 L3 N PEN PE RPAB RPAB TN earthing arrangements • Protection by overcurrent tripping TN-C TN-S

  11. L1 L2 L3 PE RPAB IT earthing arrangements • No protection is needed

  12. Earthing arrangement & applications • Earthing arrangement choice will depend on the type of application: • TT: small tertiary and residential networks • TN: industrial networks, large tertiary networks • IT: marine, some specific hospital areas, for industry applications with a high service continuity need • All systems are equivalent with regard to people safety • In large installations, the best system is a combination of earthing arrangements.

  13. 230V Ph CB N R1 < 10 Earth fault consequence • TN-C / TN-S : CB magnetic tripping • TT : CB tripping with RCD • IT : First fault - No effect !!!Second fault - CB magnetic tripping (like TN-C/TN-S)

  14. L1 L2 L3 PE RPAB Case of a second fault in IT system • A short circuit means breaker trips!

  15. Earthing arrangement comparison

  16. 230V Ph CB N R C D 30mA / 10mA R1 < 10 R2 < 10 1 K  Ph Defect UB R2 U0 Ground R1 N Indirect contact and insulation fault (TT) Hypothesis: R1 = R2 = 10  U body: UB = 230 * R2/(R1+R2) = 115 V I body: Ib = 115V / 1K = 115 mA (high risk over 30mA) Fault current: 230V / 20 = 11.5A This current is not high enough to trip the circuit breaker. This is why RCDs are mandatory in TT; the RCD makes the protection.

  17. 230V Ph CB N R2 < 10 R1 < 1 M 1 K  Ph Defect Ub R2 U0 Ground R1 N Indirect contact & insulation fault (IT) Hypothesis: R1 = 1 M  U body: : Ub = 230 V * R2/(R1+R2)=230*R2/R1 = 2.3 mV I body:Ib= Ub /1 k  = 2.3 mV / 1k = 2,3 µA I body increases with R1 decrease Fault current IR1 = 230V / 1M = 0.2 mA No risk after the first fault: no trip is needed. What happens after a second fault on another phase?Short circuit so the circuit breaker will open.It is necessary to detect the first fault.

  18. Ph Defect Uc RT U0 Ground Zc N 40 µF 4 x 10 µF Limits for an IT earthing network 1 wire: 10 M / km 0.3 µF / km (10.6 K / Km @ 50 Hz) 3 wires * ==> 0.9 µF / Km (* 3 rather than 4 as one capacitance isin // with the defect) Uc max = 50V (safety limit) Uc = U0 * RT/Zc C max to have Uc < or = to 50V Cmax = Uc / U0 * RT * 2*pi * f Cmax = 1 / U0 * 62.8 (for 50Hz) Max length according to the voltage Ph - Ph = 760V ==> Ph - N = 760 / 1.732 = 439V => 36 µF 0.9 µF / Km ==> limit = 40 Km 240V = 66 µF ==> limit = 73 Km (3 phases)

  19. IT earthing arrangement: Pros & Cons • Energy availability - Up-time >> • Fire and explosion risks • ED life time • Preventive and corrective maintenance But • Implementation costs • Network size • Fault localisation

  20. Section 3 IT earthing Applications

  21. Typical applications in IT arrangement Some hospital areas Off-shore Ships Availability Fire Explosion Oil & Gaz Safety lighting Industrial applications with continuous or sensitive processes ( furnaces, industrial robots…) Nuclear plants Airports (runway lighting, traffic supervision) = mandatory = prescription / promotion

  22. Hospital applications • Key application driver : patient safety • Product features for this environment • AC internal impedance > 100 kOhms • Test voltage (=injection voltage) <= 25 Vdc • Injected current <= 1mA, even under fault conditions • 50 kOhms threshold

  23. Marine applications • All vessel types (both commercial and military) and the whole LV electrical distribution • 5 to 10 devices par vessel • Cruise liners, transport ships – car ferries, containers, navy vessels

  24. Industry and infrastructure applications Key application drivers : energyavailability and safety

  25. Section 4 How does Vigilohm work?

  26. How does Vigilohm work? Protection threshold • IT earthing arrangement is used to guarantee supply continuity (energy availability) in an electrical installation • Requirements of the IT system: • Continuously monitor the installation insulation by DC injection or AC injection • Signal the first fault • Locate faults (manually or automatically) • The Vigilohm range of IMDs provide a permanent insulation monitoring solution • Thus helping end users to increase process availability and improving staff and process safety Fault threshold

  27. IMD connected to neutral IMD connected to a phase L1 L2 L3 L1 L2 L3 V V IMD IMD V E95484 V E95485 3 Operating diagram • Vigilohm IMDs are connected to neutral or to a network phase When the first fault occurs,the IMD detects the network phase-to-neutral voltage across its terminals When the first fault occurs,the IMD detects the network phase-to-phase voltage Vacross its terminals Multiple sources > A single Insulation Monitoring Device

  28. LF generator Current injection • InIT arrangement, because the fault current is very small, and therefore difficult to measure, the insulation monitoring device (IMD) injects a low frequency or a DC current. This current can go though the IMD because the IMD impedance is high at 50Hz (IT) but low for the injected current (equivalent to a TT). • The aim is to measure the return current to calculate the system’s impedance. • This current depends on the leakage impedance of the network to be monitored. Locating insulation faults is done by tracing the path of a low frequency current injected at the origin of the installation.

  29. What does Vigilohm measure & monitor? • Insulation resistance • If the resistance value is under the set-point, an alarm is triggered • This resistance value is displayed on some modules • For more advanced modules: • Insulation resistance and 2 set-points (warning and alarm) • Leakage capacitance • Resistance and capacitance are good ways to know the status of the system • Allows preventive maintenance

  30. Why do we measure the network capacitance? • Monitoring the C value is essential on large networks since the C-related impedance can cause these networks to drift towards a TT arrangement. This configuration would generate a dangerous voltage contact and a high fault current in case of earth fault. • Only Schneider Electric monitors these value. • Thus, during ED design, it will be highly recommended to limit network size (long cables).

  31. i i R network C network Vi Vi Vs R network = - Rs and i = i Rs Rs Vs E95476 Rs Vs (Vi - Vs) R network = IMD Network Operating principle: DC Injection • The capacitance of the network is irrelevant when a DC voltage injection IMD is used to measure the insulation. • DC voltage injection IMDs can only be used on AC networks

  32. RS i R network C network Vi 1 C network x  Z = R network // , E95480 network complex impedance IMD Network Operating principle: AC Injection • The resistance and capacitance of the network are displayed by measuring the insulation with an AC voltage injection IMD. • Synchronous demodulation is used to indicate the real and imaginary parts of Z and therefore to calculate the resistance R and capacitance C of the network.

  33. Different injection methods, different IMDs • There are two types of permanent insulation monitors that use different injection methods: • DC current injection IMD • ACcurrent injection IMD (can be communicating) IM9 / IM9OL IM10 / IM20 IM10 / IM20H XM200 XM300C

  34. P1 CPI Two Types of monitoring MV/LV • On-line insulation monitoring • IT system for a part or the whole installation • IT system for AC or DC installations • Off-line insulation monitoring • Load insulation monitoring CPI CPI

  35. Multiple configuration options • Network type : AC / DC • Injection type : AC / DC • Injection type : permanent or non permanent Network type Injection type

  36. Section 5 The Vigilohm Offer

  37. Vigilohm offer • Level 1 solution – Manual fault location • Hospital – IM10H, IM20H, HRP • Marine, Industry & Infrastructures: IM9, IM10, IM20 • Industry / off-line monitoring: IM9OL • Level 2 solution – Automatic fault location • XM200, XD3xx • Level 3 solution – Feeder measurement & communication • XML3xx, XM300C • XL3xx, XD308C, XLI / XTU communication interface • Accessories • Toroids • Cardew surge limiter • ZX impedance • HV-IM20-1.7 subassembly • PHT1000 subassembly • Mobile fault location kit

  38. The Vigilohm Offer Level 1 solutionManual Fault Location

  39. Vigilohm offer : HospitalsProduct features Vigilohm IM10-H, IM20-H and HRP help ensure patient safety IM10-H • Fault detection and signaling • Insulation resistance value display IM20-H: • Fault detection and signaling • Insulation resistance value display • Transformer monitoring (current and temperature) • Modbus communication • Alarm log HRP • Insulation fault remote indicator (audible & visual) • Electrical fault (transformer overload or circuit breaker tripping ) remote indicator (audible & visual) • Insulation daily test IM10-H / IM20-H

  40. Vigilohm offer : HospitalsKey technical specifications IM10-H / IM20-H • Standards: IEC 60364-7-10, IEC 61557-8 • Network voltage: up to 230 V ac, 50 or 60 Hz • Insulation resistance value reading: from 1 kOhm to 1 MOhm • Minimal fault threshold: 50 kOhms • Accuracy : 5% • Auxiliary supply: AC or DC (generally the monitored network) HRP key technical features: • Tested with Anios products (anti-bacterial cleaning product) • Insulation Monitoring test button • 24 Vdc auxiliary supply HRP: Hospital remote panel

  41. Vigilohm offer : Marine, Industry, Infra.Product features (Online insulation monitoring) IM9, IM10 and IM20 help ensure process continuity, staff and process safety in IT earthing network arrangements IM9 • Fault detection and signaling without display (only for monitoring small AC networks) • Pre-alarm threshold IM10: • Fault detection and signaling with large, intuitive multi-language display • Insulation resistance value display IM20: • Same as IM10 plus • Leakage capacitance measurement display • Transformer monitoring (current and temperature) • Modbus communication • Alarm log • Current injection inhibition feature • Compatible with higher network nominal voltages with the HV subassembly

  42. Vigilohm offer : Marine, Industry, Infra.Specific standards for IM9, IM10 and IM20 • IEC 60364-4-41 : Electrical standards in buildings • IEC 61557-8 : Insulation Monitoring Devices in IT earthing arrangement • IEC 61557-9 : Equipment for insulation fault location in IT earthing arrangements

  43. Vigilohm offer : Marine, Industry, Infra. IM9 key technical specifications • Network voltage • Up to 480 Vac L-L, 50, 60 or 400 Hz • Two alarm thresholds • Pre-alarm: from 2,5 to 500 kOhms • Alarm: from 1 to 250 kOhms • 1 changeover contact in case of earth fault • Auxiliary supply: • 110 to 415 Vac (+/- 15%) • 125 to 250 Vdc (+/-15%) IM9

  44. Vigilohm offer : Marine, Industry, Infra. IM10 / IM20 key technical specifications • Network voltage: • Up to 480 Vac L-L, 50, 60 or 400 Hz • Up to 345 Vdc • Up to 1700 Vac L-L with subassembly (IM20) • Range for leakage capacitance readings: • 0,1 – 40 µF (IM20) – Impedance display • 2 thresholds • Pre-alarm: from 1 kOhm to 1 Mohms • Alarm: from 0,5 kOhm to 500 kOhms • 1 changeover contact in case of earth fault • Auxiliary supply: • 110 to 415 Vac (+/-15%) / 125 to 250 Vdc (+/-15%) • Multi-language support for English, French, Spanish, Italian, Portuguese, Chinese, and Russian • DNV approval for the Marine market IM10 / IM20

  45. Vigilohm offer : IndustryIM9-OL Product features (Offline insulation monitoring) IM9-OL for insulation monitoring of offline motors (i.e., motors that are not normally powered, such smoke extractors) • Functions • Insulation monitoring with an adjustable threshold • Motor start inhibition with a second threshold • Ability to authorize start, even in case of low insulation • Fault detection and signaling in all motor earthing arrangements (TN, TT, IT) • Standards • Product: IEC 61557-8, Safety : 61010-1 • Features • Motor nominal voltage : up to 690 V • Pre-alarm threshold: from 0,5 to 10 Mohms • Motor inhibition threshold: from 0,25 to 2 Mohms • Suitable for 1 ph or 3 ph motors, including star/delta start IM9-OL

  46. The Vigilohm Offer Level 2 solutionAutomatic Fault Location

  47. Vigilohm offer - automatic fault location • Ideal for medium or large networks with a significant number of feeders • Typical architecture • XM200 IMD that displays global R and C • XD312 / XD301 automatic fault locators • The customer typically uses a manual fault locating kit for the downstream distribution

  48. Automatic fault location – strong points • Global network monitoring (R and C) • Unlimited number of locators • No link between the XM200 (injector)and XD devices (locators) • Transient fault management on both XM200 and XD devices • Both XD312 and XD301locate the fault

  49. XM200 key technical features • Network voltage: • up to 760 Vac (injection connected to neutral) • up to 440 Vac (injection connected to phase) • up to 500 Vdc • For higher voltages, please use XM300C. • Range for insulation resistance readings: • from 0,1 to 999 kOhms • Range for leakage capacitance readings: • from 0,1 to 199 µF • 2 thresholds (pre-alarm and alarm) and 2 output contacts

  50. XD301 / XD312 key technical features • Immediateidentification of the faultyfeeder • Network type: • low voltage, AC (45 to 400 Hz) or DC • Operating threshold: • 2,5 mA @ 2,5 Hz • Polling time: • 20 s per channel • 1 output contact

More Related