1 / 23

IMPACT OF GREEN POWER GENERATION ON DISTRIBUTION SYSTEMS

Not GreenBurn conventional fuelGasDiesel, oil, gasoline GreenUse renewable sources to reduce reliance of fossil fuels:SolarMethane (from decomposition)WindHydroBiomass (burn it)Tidal. DG: Green or Not Green. . . . . Typical Interconnection Protection. Disconnects the generator when it is

helga
Télécharger la présentation

IMPACT OF GREEN POWER GENERATION ON DISTRIBUTION SYSTEMS

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


    1. IMPACT OF GREEN POWER GENERATION ON DISTRIBUTION SYSTEMS

    2. Not Green Burn conventional fuel Gas Diesel, oil, gasoline Green Use renewable sources to reduce reliance of fossil fuels: Solar Methane (from decomposition) Wind Hydro Biomass (burn it) Tidal

    3. Typical Interconnection Protection Disconnects the generator when it is no longer operating in parallel with the utility. Protects the utility system from damage caused by connection of the generator (fault current and overvoltage). Protects the DG generator from damage from the utility system, especially through automatic reclosing.

    4. Typical Generator Protection Generator internal short circuits. Abnormal operating conditions (loss of field, reverse power, overexcitation and unbalance currents).

    5. Types of Green Power Generators Induction Synchronous Asynchronous

    6. Induction Generator Induction Excitation provided externally Start up like a motor (no sync. equipment needed) Less costly than synchronous machines Limited in size to 500 KVA

    7. Synchronous Generator

    8. Asynchronous Generator

    9. IEEE 1547 SAYS A DG SHALL: Not Cause Overvoltages or Loss of Utility Relay Coordination Disconnect When No Longer Operating in Parallel With the Utility. + Only Discusses 81O/U and 27, 59 Not Energize the Utility when it is De-energized Not Create an Unintentional Islands Use Utility Grade Relays Not Cause Objectionable Harmonics Not Cause Loss of Synchronism That Results in Objectionable Flicker

    10. Greatly complicates restoration Requires synchronizing at utility substation Inhibits automatic reclosing Power quality issue DG may not be able to maintain voltage, frequency and harmonics within acceptable levels.

    11. Feeder deenergizes when utility opens feeder Restoration responsibility on the DG Requires synchronizing to utility Inhibits automatic reclosing

    12. OVERVOLTAGE AND LOSS OF COORDINATION Two Sources of Overvoltage +Choice of Delta Interconnection Transformer Primary Winding + Ferroresonance Loss of Coordination +Choice of Grounded Interconnection Transformer Primary Winding.

    14. Ungrounded Interconnection Transformers

    15. Grounded Primary Interconnection Transformers

    16. FERRORESONANCE NEW YORK FIELD TESTS 1989 FIELD TEST CIRCUIT

    17. FERRORESONANCE NEW YORK FIELD TESTS -1989 50KW Synchronous DG, 9KW load, 100KVAR Capacitance and Wye-Delta Interconnection Transformer A=2.74 pu B=2.34 pu C=2.92 pu

    18. FERRORESONANCE NEW YORK FIELD TESTS -1989 50KW Synchronous DG, 9KW load, 100KVAR Capacitance and Wye-Delta Interconnection Transformer A=2.74 pu B=2.34 pu C=2.92 pu PROTECTION SOLUTION: MEASURE PEAK OVERVOLTAGE NOT RMS (59I)

    19. CONDITIONS FOR FERRORESONANCE DG Must be Separated From the Utility System (islanded condition) KW Load in the Island Must be Less than 3 Times DG Rating Capacitance Must be Greater Than 25 and Less Than 500 Percent of DG Rating There Must be a Transformer in the Circuit to Provide Nonlinearity

    20. PROTECTION FUNCTION BEYOND 81O/U,27 AND 59 Total Interconnect Package Loss of Parallel Fault backfeed removal Damaging conditions Abnormal power flow Restoration

    21. TYPICAL INTERCONNECTION PROTECTION FOR WYE-GROUNDED (PRI.) INTERCONNECTION TRANSFORMER

    22. TYPICAL INTERCONNECTION PROTECTION FOR UNGROUNDED (PRI.) INTERCONNECTION TRANSFORMER

    23. CONCLUSIONS 1. Green Power DGs Interconnected on Distributions Systems Present Significant Technical Problems and Potential Harzards 2. There are No Standard Solutions Only Choices with Undersirable Drawbacks 3. IEEE 1547 Provides Limited Real Guidance Simply Cites Obvious Requirements 4. When Developing DG Interconnection Protection the Technical Issues Raised in this Paper Need to be Addresses

    24. THE END

More Related