An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. ModelingLine Drop Compensation, Reactive Current Compensation, Cross-Current Compensation Dmitry Kosterev BPA November 2013

  2. Basics XT = 12 to 20% Line Drop Compensation Generator Terminal Voltage 01 Reactive Current Compensation gentpj 1 “UNIT1” 13.8 “01”: … “xcomp” 0.05 gentpj 2 “UNIT2” 13.8 “01”: … “xcomp” 0.00 gentpj 3 “UNIT3” 13.8 “01”: … “xcomp” – 0.05

  3. Basics POI Voltage Line Drop Compensation Generator Terminal Voltage Reactive Current Compensation Generator Reactive Power

  4. General Rule 01 02 RCC = – 5% Model: gentpj 1 “UNIT1” 13.8 “01”: … “xcomp” – 0.05 gentpj 1 “UNIT1” 13.8 “02”: … “xcomp” – 0.05

  5. Modeling In General Electric PSLF: “xcomp” is negative for Reactive Current Compensation In Siemens PTI PSS®E: “xcomp” is positive for Reactive Current Compensation Many cases when the data is converted incorrectly between the programs: E.g.Rock Island,Ryan,Magcorp

  6. General Rule Positive “xcomp” will result in sister units becoming unstable (one goes full boost, one goes full buck) if they have different parameters or initial unit loading Voltage Field Voltage Unit 1, Field Voltage Unit 2 Reactive Power Unit 1, Reactive Power Unit 2

  7. Rule Breakers – US ACE and BPA LDC = + 5% 01 02 Cross-Current Compensation

  8. Modeling • Present practice is to use the positive “xcomp” to represent Line Drop Compensation • Cross-compensation is not modeled • John Day, The Dalles and Willamette Valley plants • Models can have “xcomp” positive as long as two sister units have identical models and data, and have the same MW and MVAR output • State estimator models have units dispatched at different MW levels • Need to make sure models are stable

  9. Modeling XCOMP (Existing practice): gentpj 1 “UNIT1” 13.8 “01”: … “xcomp” +0.045 gentpj 1 “UNIT1” 13.8 “02”: … “xcomp” +0.045 CCOMP: gentpj 1 “UNIT1” 13.8 “01”: … “xcomp” 0.0 gentpj 1 “UNIT1” 13.8 “02”: … “xcomp” 0.0 ccomp 1 “UNIT1” 13.8 “01”: “rc” 0.0 “xc” –0.05 “rt” 0.0 “xt” 0.045 XCOMP_CCOMP: gentpj 1 “UNIT1” 13.8 “01”: … “xcomp” 0.045 gentpj 1 “UNIT1” 13.8 “02”: … “xcomp” 0.045 ccomp 1 “UNIT1” 13.8 “01”: “rc” 0.0 “xc” –0.05 “rt” 0.0 “xt” 0.0

  10. Model Testing 01_02 _02 01_ 01 01 01 02 02 02

  11. Model Testing LDC Setting is 4.5% Voltage dip is simulated, effective LDC is measured

  12. Recommendations • Use CCOMP model to represent cross-current compensation when used • Make changes to CCOMP and XCOMP models to work together • If “xt” in “ccomp” is zero, continue using “xcomp” parameter from “gentpj” model • If “xt” in “ccomp” is non-zero, set “xcomp” parameter to zero in “gentpj” model • John Day has +0.045 LDC and cross-current compensatio • Make sure that the following works • Set “xc” to –0.05 and “xt” to 0.0 in “ccomp” model • Set “xcomp” to 0.045 in “gentpj” model