An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Milovan Unković, Tatjana Dlabač EFEKTI ŠTEDNJE ENERGIJE KORIŠTENJEM KOMPENZACIJE REAKTIVNE ELEKTRIČNE SNAGE

  2. KONCEPT SANACIJE I REVITALIZACIJE SISTEMA KLIMATIZACIJE , GRIJANJE I TERMIČKE PRIPREME MINERALNE I SANITARNE VODE I TERAPIJSKOG BLATA – INSTITUT IGALO, novembar 2007. Revitalizacija sistema kompenzacije reaktivne električne snage, Revitalizacija automatike HVAC sistema (klimati, FC sistemi, grijanje bazenske vode) Zamjena starih klipnih toplotnih pumpi GRASSO, Revitalizacija dotrajalog kotlovskog postrojenja(kotlovnica, toplovod, podstanice), Izvođenje nove energetski efikasne fasade.

  3. NAPAJANJE II FAZE INSTITUTA ELEKTRIČNOM ENERGIJOM • Tri trafostanice 10/0,4 kV, • Ukupno petnaest 630 kVA transformatora, • Stare kompenzacije ugrađene 1985. godine, • Kompenzacija vršena piralenskim baterijama , • Po jednom transformatoru šest baterija, • Ukupan broj baterija : 90, • Težina jedne baterije : 30 kg.

  4. POSTUPCI PRI UGRADNJI NOVOG SISTEMA KOMPENZACIJE • Mjerenje parametara potrošnje i mreže, • Uklanjanje postojećih piralenskih ćelija, • Proračun novog sistema kompenzacije, • Implementacija sistema kompenzacije, • Praćenje ponašanja pouzdanosti sistema tokom garantnog roka.

  5. MJERENJE PARAMETARA POTROŠNJE I MREŽE • Promjene aktivne snage pojedinih transformatora, • Promjene reaktivne snage pojedinih transformatora, • Promjene faktora snage (cosφ), • Promjena napona na sabirnicama, • Sadržaj viših harmonijskih izobličenja ( THD - Total Harmonic Distortion).

  6. MJERENJA NA TRAFOSTANICI TS-310.03. – 13.03. 2008. god.

  7. IZABRANI TRANSFORMATORI ZA KOMPENZACIJU

  8. OZNAKE NA STARIM KOMPENZACIONIM BATERIJAMA

  9. STARI REGULATORI I KONTAKTORI

  10. SERTIFIKAT O RECIKLAŽI PIRALENA

  11. Instalisana snaga i struktura ugrađenih kondenzatorskih baterija

  12. UGRADNJA NOVIH BATERIJA24.06. – 29.06. 2008.

  13. IZGLED NOVOG SISTEMA KOMPENZACIJE

  14. NOVI REGULATORI, SKLOPKE I KONDENZATORI

  15. TROŠKOVI REVITALIZACIJE KOMPENZACIJE

  16. TROŠKOVI PLAĆANJA REAKTIVNE ENERGIJE • U godini prije revitalizacije kompenzacije ( 07.2007.-07.2008. godine) potrošeno 5.796.000,00 kVAr reaktivne energije i plaćeno je 32.015,00 €, • U godini poslije uvođenja nove kompenzacije (07.2008.-07.2009. godine) potrošeno je 2.432.000,00 kVAr reaktivne energije i plaćeno je 928,59 €.

  17. HAVARIJA NA SISTEMU KOMPENZACIJE07.04.2009.

  18. HAVARIJA NA SISTEMU KOMPENZACIJE

  19. NOVI SISTEM KOMPENZACIJEugradnja 24.02.-28.02.2010.

  20. NOVI SISTEM KOMPENZACIJE

  21. TROŠKOVI SANACIJE HAVARIJE • Ukupna cijena nove opreme:19.586,18 € • Cijena utrošene reaktivne energije u periodu kada je kompenzacija samo djelimično radila (08.2009.-05.2010.) : 18.435,74 €.

  22. PRAĆENJE POTROŠNJE ELEKTRIČNE ENERGIJE

  23. PLAĆANJE REAKTIVNE ENERGIJE • U 2012. godini aktivna energija na II Fazi Instituta je plaćena u iznosu: 632.653,67 €, • Reaktivna energija je plaćena u iznosu: 0,0€. • Od maja mjeseca 2012. godine reaktivna energija ne prelazi 7% aktivne. • Investicija se otplatila za 18 mjeseci.

  24. MJERENJE HARM. IZOBLIČENJA NAKON UGRADNJE KOMPENZACIJE