1 / 32

Exits

Exits. Purpose of the regulation. The workplace must have adequate exit routes and exits to use in an emergency Review 29 CFR 1910 Subpart E - Means of Egress. 1a. Exit routes and exits.

jenna
Télécharger la présentation

Exits

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Exits

  2. Purpose of the regulation • The workplace must have adequate exit routes and exits to use in an emergency • Review 29 CFR 1910 Subpart E - Means of Egress 1a

  3. Exit routes and exits • Exit routes are continuous and unobstructed paths of exit from any point within a workplace to a safe area 2a

  4. Exit routes and exits • Exit routes consist of the following three parts: • Access to the exit • The exit • Way from the exit to the outside 2b

  5. Exit routes and exits • Exit routes include all vertical and horizontal areas: • Stairs • Ramps • Aisles 2c

  6. Exit routes and exits • An exit is the portion of the exit route that generally is separated from other areas to provide a protected way of travel out of the workplace 2d

  7. Exit route and exit requirements • At least two exit routes that are remote from each other must be available • Single exit routes are allowed in some cases 3a

  8. Exit route and exit requirements • Other means of escape should be available if there is only one exit route • Fire escapes • Accessible windows • More than two exit routes may be needed in some cases 3b

  9. Exit route and exit requirements • When determining the number of exit routes needed, consider: • the size of the building • building occupancy • the arrangement of the workplace 3c

  10. Fire-resistance requirements for exits • There must be a separation between the exit and the rest of the workplace • Exits must be protected by a self-closing fire door 4a

  11. Fire-resistance requirements for exits • The fire door must be approved by a nationally recognized testing laboratory • Fire doors must not be blocked open 4b

  12. Exit routes must be kept safe • Exit routes must be kept free of obstructing material or equipment • Exit routes must have adequate lighting • Stairs or ramps can be part of the exit route 5a

  13. Exit routes must be kept safe • The purpose of the exit route is to reach an exit • Exit routes cannot lead employees toward a dead end, or through a room that can be locked 5b

  14. Exit routes must be kept safe • Exit routes must be free of highly flammable furnishings or decorations • Signs along the exit route indicate the direction of travel to the nearest exit 5c

  15. Requirements to ensure that exits are safe • Exits must lead directly outside or to an open space with access to the outside • The area beyond the exit has to have enough room for the people most likely to use the exit 6a

  16. Requirements to ensure that exits are safe • Exit doors must be easy to open without keys or special instructions • Exit doors cannot have any alarm/device that would restrict emergency use of the exit should the device fail 6b

  17. Requirements to ensure that exits are safe • When exit route stairs continue beyond the floor where people exit, there must be doors or partitions at the exit discharge floor • A side-hinged exit door must be used to connect any room to an exit route 6c

  18. Requirements to ensure that exits are safe • Doors must swing out from the room into the exit route if a room: • may be occupied by more than 50 people; or • contains highly flammable or explosive materials 6d

  19. Exit routes must have adequate capacity & size • Exit routes must be able to support the maximum-permitted occupant load for each floor of the building • The exit route’s capacity must not decrease along the direction of exit travel 7a

  20. Exit routes must have adequate capacity & size • Exit routes must be at least: • 6 feet, 8 inches high • 28 inches wide 7b

  21. Exit routes must have adequate capacity & size • Exits must be wider if necessary to accommodate the occupant load • Minimum sizes must be met even if objects project into the exit route 7c

  22. Requirements for outdoor exit routes • Outdoor exits must meet the same requirements as indoor exit routes • Outdoor exit routes must have guardrails to protect unenclosed sides 8a

  23. Requirements for outdoor exit routes • Routes must be covered if accumulation of snow or ice is likely 8b

  24. Requirements for outdoor exit routes • Routes must be reasonably straight with smooth, solid, substantially level floors • Routes must have no dead ends longer than 20 feet 8c

  25. Exit routes must be marked • Each exit must be clearly visible and marked with a sign that says: 9a

  26. Exit routes must be marked • The line of sight to the exit must be free of displays and objects • Exit signs must be properly illuminated 9b

  27. Exit routes must be marked • Exit doors must be free of decorations or other signs that obscure visibility • Doorways/passageways that could be mistaken for an exit must be marked: 9c

  28. Requirements for alarm systems • Workplaces must have operable employee alarm systems • Alarms must have distinctive signals to warn employees of fire or other emergencies 10a

  29. Maintenance requirements • When the workplace contains fire retardant paints/coatings, fire retardant properties must be maintained 11a

  30. Maintenance requirements • Keep the following in proper working order: • Sprinkler systems • Alarm systems • Fire doors • Exit lighting • Other safeguards to protect employees 11b

  31. Maintaining exits during construction/repair • Exits must be available before employees are allowed in a workplace under construction • Fire protection must be provided if employees are in a workplace during repair activities 12a

  32. Maintaining exits during construction/repair • When flammable/explosive materials are used during construction: • employees may not be exposed to hazards that are otherwise not present • employee escape may not be impeded by the use of these materials 12b

More Related