SOLUTION FOR THE WEAK LINK HIGH VOLTAGE BOLTED COUPLERS AND ADAPTORS

SOLUTION FOR THE WEAK LINK HIGH VOLTAGE BOLTED COUPLERS AND ADAPTORS. HIGH VOLTAGE COUPLERS REGARDED AROUND THE WORLD AS THE WEAK LINK. WHY?. Couplers have been Failing in Service Failures were Unpredictable Cause of Failures Unknown. ASSOCIATED PROBLEMS. Decrease in Safety and Health

kenaz
Télécharger la présentation

SOLUTION FOR THE WEAK LINK HIGH VOLTAGE BOLTED COUPLERS AND ADAPTORS

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. SOLUTION FOR THE WEAK LINK HIGH VOLTAGE BOLTED COUPLERS AND ADAPTORS

  2. HIGH VOLTAGE COUPLERS REGARDED AROUND THE WORLD AS THE WEAK LINK WHY? • Couplers have been Failing in Service • Failures were Unpredictable • Cause of Failures Unknown ASSOCIATED PROBLEMS • Decrease in Safety and Health • Decrease Production • Increase Operation Costs

  3. ACARP REPORT ON THE FAILURE OF 11kV PLUGS AND ADAPTORS • Australian Mining • Industry Concerned • Invested Through ACARP

  4. 1 2 3 5 6 4 EXAMPLES OF FAILED COUPLERS IN SERVICE

  5. SHORT CREATING DEAD SHORT

  6. RESEARCHING COUPLERS GLOBELY Research showed that all the designs were very similar. These similarities were: • Insulators were all of a tower design • When closed, all suffered from air being trapped around the • insulator profile • The same design flaws were present in all types of couplers USA Canada Australia South Africa

  7. ACARP PROJECT C5032 Research into the Failure of 11kV Plugs and Adaptors used in Underground Coal Mines Quote: Executive Summary: “A number of design weaknesses were identified that lead to the generation of partial discharges within the assembled plug and adaptor”

  8. DESIGN FLAWS FOUND

  9. AIR AIR AND PARTIAL DISCHARGE • Large Volume Of Air Trapped Inside Coupler Enclosure • High Discharge Creates Corona • Corona Converts Air To Ozone • Ozone Is A Conductor • Phase To Phase Flashover PARTIAL DISCHARGE

  10. Insulating Material Silicon Insert SOLUTIONS • Insulating Material Developed to Extinguish Tracking • Remove Air with Silicon Rubber Insert

  11. NO TRIPS OR ANY SIGNS OF FAULT

  12. EARTH PHASE EARTH PHASE EARTH PHASE EARTH PHASE SEGREGATION BY EARTH Mining Industry Standard

  13. A Phase to Ground Fault was created with conductive paint Earth Star Placed Between Phases FIRST SOLUTION A Through Fault Test was then performed on this solution to see how it would perform in the field

  14. PHASE 1 EARTH PHASE 2 PHASE 3 REASON FOR FAILURE

  15. Equipotential Lines Good Earth Star Equipotential Lines Good Equipotential Lines Crushed Up Individually Screened Cable FINDING A SUCCESSFUL SOLUTION .

  16. EXPELS ALL AIR BODY SEGREGATES PHASES SEPARATE INSULATORS SOLUTION New Design expels all air in face of coupler and phases are segregated by ground

  17. EARTH ALL TYPE TESTS PERFORMED WERE WITHIN CABLE SPECIFICATIONS COUPLERS HOMOGENEOUS WITH CABLE

  18. COMPARISON

  19. ACARP PROJECT C5032 Research into the Failure of 11kV Plugs and Adaptors used in Underground Coal Mines Quote : NEW DESIGN “Given the nature of the new design and the high voltage stress management issues that it addresses, it is expected that other manufacturers will follow this lead and produce their own variations of the design. “

  20. ANALYZING THE DESIGN ADVANTAGES PEACE OF MIND Increased Safety Increased Reliability Increased Productivity Increased Security