ITU Workshop on “Greening the Future: Bridging the Standardization Gap on Environmental Sustainability ” (Colombo, Sri Lanka, 3-4 October 2013). Green ICT infrastructure, Green & Sustainable Future. Shuguang Qi, Associate Rapporteur of Q17/SG5, qishuguang@catr.cn.
E N D
ITU Workshop on “Greening the Future: Bridging the Standardization Gap on Environmental Sustainability” (Colombo, Sri Lanka, 3-4 October 2013) Green ICT infrastructure, Green & Sustainable Future Shuguang Qi, Associate Rapporteur of Q17/SG5, qishuguang@catr.cn
Energy Consumption in ICT • Telecommunication Room • Data Center Energy consumption(One example)
Content Green Infrastructure in Data Center Green Infrastructure in Telecommunications
Green Infrastructure in Data center • Cooling for every modules • Flexibility • High-density • High-integrity Modular Data Center-Building Type
Green Infrastructure in Data center • Integrates IT infrastructures in a cargo container • High-density • Overcoming the limitation of the place • Flexible extension Modular Data Center-Container Type
Green Infrastructure in Data center • Output voltage- • AC • UPS Load- • lower than 50% • System Efficiency- • 90%~92% • Maintenance Difficulty- • Hard Power- Traditional AC UPS
Green Infrastructure in Data center • Output voltage- • AC • Modular UPS Load-About 70%~80% • System Efficiency- • 93%~95% • Maintenance Difficulty- • Easy Power- Modular AC UPS
Green Infrastructure in Data center HVDC AC/DC DC/DC Load Battery AC UPS AC/DC Load Battery DC/AC • Power- HVDC • Output voltage range- • DC, voltage range in • ITU-T L.1200: • Target solution 260V-400V; • Transitional solution • 192V-288V. • HVDC Load- • About 70%~80% • System Efficiency- • 93%~95% • Maintenance Difficulty-Easy
Green Infrastructure in Data center Cooling-Cold Aisle cooling method
Green Infrastructure in Data center Cooling-Hot Aisle cooling method
Green Infrastructure in Data center Cooling-Horizontal Direction cooling
Green Infrastructure in Telecommunication • Adjusting the load to the appropriate value • Choose High Efficiency Rectifiers • (1)Normal module Efficiency- • 91%~92% • (2)High efficiency module efficiency-96%~97% • Power-High efficiency Rectifiers & Sleeping Mode
Green Infrastructure in Telecommunication Power-Green energy
Green Infrastructure in Telecommunication • Clean • Quiet • Output voltage-AC/DC • Power Mode-Main Power mode/ Stand by power mode • Hydrogen Fuel Cell system
Green Infrastructure in Telecommunication Battery-High Temperature Battery
Green Infrastructure in Telecommunication Battery- Minimizing energy consumption-Lithium battery
Green Infrastructure in Telecommunication • Capacity-About 7.5kW • COP(average value)-3.0~3.4 • Cooling-Traditional Air Conditioning system
Green Infrastructure in Telecommunication • Capacity • About 5kW-6kW • Working Condition • ⊿T ≈10 ℃ • COP(average value) ≥18 • Cooling-Outdoor cooling
Green Infrastructure in Telecommunication • Capacity • About 4kW-5kW • Working Condition • ⊿T ≈10 ℃ • COP(average value) • 8~12 Cooling-Heat Exchanging & Heat Pipe air conditioner
Green Infrastructure in Telecommunication • Inverter Air Conditioner • Membrane Humidifier Air Conditioner • Glycol Air Conditioner • Refrigerant Pumping-Compressing Dual Cycles Air Conditioner • Phase Change Material Air Conditioner • Other Cooling methods