1 / 25

Daniel Bullock Director, Gulf Coast CHP Applications Center Houston Advanced Research Center

Katrina Forum: Sept. 25, 2006. Daniel Bullock Director, Gulf Coast CHP Applications Center Houston Advanced Research Center. Resilient Energy Systems: The CHP Solution. Moving knowledge to action to improve human well-being and the environment. Houston Advanced Research Center.

lael-hardin
Télécharger la présentation

Daniel Bullock Director, Gulf Coast CHP Applications Center Houston Advanced Research Center

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Katrina Forum: Sept. 25, 2006 Daniel Bullock Director, Gulf Coast CHP Applications Center Houston Advanced Research Center Resilient Energy Systems: The CHP Solution Moving knowledge to action to improve human well-being and the environment

  2. Houston Advanced Research Center • Established 1982 • Non-profit scientific research institute • Sustainable development mission • Environmental technology commercialization • Research Management • Air Quality focus • Located in the Woodlands, TX • Website: www.harc.edu

  3. Observations from Hurricanes Katrina & Rita

  4. Observation 1 • Over reliance on the central station electric utility model increased our vulnerability to the hurricanes. • The wood pole T&D system did not survive either Hurricanes Katrina or Rita and the result was prolonged power outages.

  5. Hurricane Rita • T&D Infrastructure Replacements • 981 wood transmission structures • 26 steel lattice transmission structures • 8970 wood distribution poles • 8040 distribution transformers • 18,000 non-Entergy workers helped out • Losses = $380M ($1.5B including Katrina)

  6. Observation 2 Those with power were the ones capable of self-generating electricity • Self generation consisted primarily of backup generators, but also those with cogeneration/CHP plants

  7. Diesel GenSets are Ubiquitous • But they were NOT reliable! • Not in working order when needed • Didn’t hold up throughout the entire outage • Couldn’t be serviced (no parts or labor) • Quickly exhausted on-site fuel supplies • Limited ability to resupply fuel tanks • Systems were undersized • Remotely located units could not be delivered quickly • Located in basements and low lying areas • Poor return on investment

  8. The CHP Solution CHP is DG . . . • An integrated system • Operates around the clock • Provides at least a portion of the electrical load and • Utilizes the thermal energy for: • Cooling • Dehumidification • Water and space heat • Process heat

  9. Conventional Generation vs. CHP Eff. = 49% Eff. = 86%

  10. Hurricanes Katrina and Rita:A Tale of Two Hospitals

  11. Memorial Hermann Baptist HospitalBeaumont, TX • Back up generators started, but could neither power the chillers nor maintain power due to length of outage • The hospital reopened after 22 natural gas engines were brought in from Houston • Most damage to the hospital was related to loss of HVAC -- humidity infiltration resulted in extensive damage to floors, ceiling tiles, medical supplies, and equipment • Hurricane Rita • closed the hospital for a week • caused over $30M in costs and damages

  12. August 29, 2005 Hurricane Katrina Hits Jackson, MS • Connection to MPG Restored • Load Shed performed (1.2 MW disconnected) • Pumping Trucks Supply Water to Physical Plant • Connection to MPG Restored 3 hr 57 hr 1 hr 5 hr • Main Power Grid (MPG) Failed • Alternate Power Grid Enabled • City Water Lost • 52 hrs of 100% operation on CHP • Only Hospital in the Jackson Metro Area to be Nearly 100% Operational!! • Power Reliability Problems • Switched to CHP Operation Only • Elevators on Emergency Generators • Restricted use of MRI Equipment Mississippi Baptist Medical CenterJackson, MS

  13. Value of On-site Generation Mississippi Baptist Medical Center • remained open throughout to treat a high volume of patients • provided emergency clothing, food, and housing for people displaced during the first night of the disaster • received patients from other medical facilities not able to remain open • helped emergency responders establish operations

  14. Observation 3 • Natural gas supplies were generally available throughout on high pressure pipes • Tulane University reported sufficient natural gas pressure to operate their 5 MW campus system

  15. Tulane University CHP Plant • Campus has a 9 MW electrical load • 5 MW gas turbine provided “islanded” power and cooling to critical campus facilities throughout Katrina • Cooling towers damaged, but remained operational • Switched to well water • 2000 ton chiller could not be restarted if tripped • Natural gas pressure available, but turbine switched to diesel (3.5 day supply) due to compressor problem • Rising water forced system off as some switchgear went underwater in the days after levees were breached • University staff looking to add capacity and flood protection

  16. CHP in Louisiana • Existing CHP Capacity (2004): 6 GW • Undeveloped CHP Capacity (2004): • Industrial: 2.6 GW • Commercial: 1.6 GW

  17. Commercial CHP Candidates • Hotels • Prisons • Airports • Hospitals • Universities • Grocery Stores • Wastewater Treatment • Refrigerated Warehouses • Emergency Management Facilities • Homeland Security & Sanctuary Locations • Industrials (Refineries, Chemical plants, Manufacturers)

  18. HIGHEST RELIABILITY OPTION HIGHEST EFFICIENCY OPTION } UTILITY SUPPLIED ELECTRICAL ELECTRICAL ELECTRICAL DEFICIT Sized to meet electrical load THERMAL THERMAL THERMAL Sized to meet thermal load } EXPORT or WASTE EXCESS THERMAL CHP System Design Options FACILITY DEMAND

  19. Observation 4 • Those that relied on regionally staged fuels, materials, parts, and vendors were not well served. • Regional evacuations and localized damage made delivery of power equipment and supplies nearly impossible.

  20. CHP and Energy Resiliency • CHP does NOT rely on wood poles • Natural gas provides reliable fuel to CHP throughout prolonged outages • CHP can power whole facilities • Lights, air conditioning, water purification, sewage, safety systems, high value areas, manufacturing • CHP micro-grids can power city blocks and neighborhoods

  21. Will LA Develop its CHP Potential? Success depends on: • Providing mechanisms and incentives for utilities to participate • Advancing CHP in new applications • Educating engineers, architects, and building owners about the value of CHP • Financing “improved” solutions with insurance and FEMA dollars

  22. Insanity: doing the same thing over and over again and expecting different results. Albert Einstein

  23. For more information: Daniel Bullock Gulf Coast CHP Applications Center (281) 364-6087 dbullock@harc.edu

More Related