Two current-carrying wires, each having radius r

I. I. Magnetic flux. <. >. D. For D > 10r, and height above ground > 10D. Two current-carrying wires, each having radius r. Henries per meter. µ o is the permeability of free space (e.g., air) = 4 π• 10 -7. D. <. >. V. Same two wires, energized by V. Farads per meter.

lawson
Télécharger la présentation

Two current-carrying wires, each having radius r

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. I I Magnetic flux < > D For D > 10r, and height above ground > 10D Two current-carrying wires, each having radius r Henries per meter µo is the permeability of free space (e.g., air) = 4π•10-7

  2. D < > V Same two wires, energized by V Farads per meter εo is the permittivity of free space (e.g., air) = 8.854•10-12

  3. < > D Velocity of propagation of disturbances down a lossless overhead transmission line

  4. If Each Conductor is Actually a Bundle Double Bundle, Each Conductor Has Radius r A Equivalent Radius of the Bundled Conductors

  5. China

  6. 250 km Bus 2 DFW 500 km Bus 6 COAL 300 km Bus 7 WIND 400 km Bus 3 UT Bus 1 HOU 150 km 300 km Bus 4 SA No Wind (Good Wind) 400 km • Summer Peak, 3 kW per person, 20 million people, 60 GW • Winter Peak, 80% of Summer Peak • Spring/Fall Peak, 50% of Summer Peak • Nightime, 50% of Daily Peak • Approx 5% losses Bus 5 VAL • Positive-sequence line constants for each 345kV a-b-c circuit: • R = 0.06 Ω/km per conductor • L = 1 µH/m • C = 12 pF/m • Rating = 800 A per conductor • Two conductors per phase • Three phases per circuit • 200kV line-to-ground • Approx. 1 GW per circuit

  7. 250 km Bus 2 DFW 500 km Bus 6 COAL 300 km Bus 7 WIND 400 km Bus 3 UT Bus 1 HOU 150 km 300 km Bus 4 SA 400 km Bus 5 VAL No wind in West Texas in summer (HOU makes up WIND gen. in summer) • Positive-sequence line constants for each 345kV a-b-c circuit: • R = 0.06 Ω/km per conductor • L = 1 µH/m • C = 12 pF/m • Rating = 800 A per conductor • Two conductors per phase • Three phases per circuit • Each conductor is 200kV line-to-ground • Approx. 1 GW per circuit • Each 100 km of circuit has • R = 3 Ω • ZL = j37.7 Ω • ZC = -j2210 Ω • 3 GW load corresponds to 40Ω on each a-b-c phase • Summer Peak, 3 kW per person, 20 million people, 60 GW • Winter Peak, 80% of Summer Peak • Spring/Fall Peak, 50% of Summer Peak • Nightime, 50% of Daily Peak • Approx 5% losses

  8. Bus 2 DFW Bus 6 COAL Bus 7 WIND Bus 3 UT Bus 1 HOU Bus 4 SA Bus 5 VAL 6 3 ??? ??? ??? ??? 3

  9. Bus 2 DFW Bus 6 COAL Bus 7 WIND Bus 3 UT Bus 1 HOU 3.0 j37.7 Bus 4 SA -j2210 -j2210 Ohms for 1 phase of a 100km three-phase circuit Bus 5 VAL 40 Ω 40 Ω 40 / 2 Ω 40 / 5 Ω 250km 6 500km 3 300km 2 400km 6 2 40 Ω 150km 300km 6 40 / 6 Ω (on each a-b-c phase) 40 / 4 Ω 3 GW load corresponds to 40Ω on each a-b-c phase 400km 3