1 / 29

LEGIONELLA AWARENESS COURSE

LEGIONELLA AWARENESS COURSE. COURSE OBJECTIVES. To enable you to be aware of issues associated with Legionella within the UoP & be able to assist in the delivery of the Management Plan. . LEGIONELLOSIS. Legionella = water-borne bacteria Naturally widespread in the environment

leanna
Télécharger la présentation

LEGIONELLA AWARENESS COURSE

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. LEGIONELLA AWARENESS COURSE

  2. COURSE OBJECTIVES To enable you to be aware of issues associated with Legionella within the UoP & be able to assist in the delivery of the Management Plan.

  3. LEGIONELLOSIS • Legionella = water-borne bacteria • Naturally widespread in the environment • Over 50 different species identified • 20 known to cause disease in man • Legionella pneumophila • Legionnaire’s Disease • Pontiac Fever / Lochgoilhead Fever

  4. Legionella sp. under UV illumination Legionella pneumophila

  5. LEGIONELLA • Temperature range 20 - 50°C • Proliferates at 37 °C • Requires nutrients • Slow moving / stagnant water • Poorly managed water system = perfect environment

  6. SYMPTOMS • Head & muscle ache • Tightness in chest • Dry cough • Sickness & diarrhoea • Confusion / delirium • Coma • Death

  7. ‘AT RISK’ GROUPS

  8. CHAIN OF EVENTS Bacteria present in water system Slow moving / stagnant water Adequate food source Temperature range 20-50°C Aerosol formed People present

  9. RISK AREAS • Hot & Cold Water Systems • Cooling Towers & Air Conditioning • Storage Cisterns • Calorifiers • Deadlegs • Showers • Spa pools • LEV’s/ Fume Cupboards

  10. Showers Operate at desired temps Poor hygiene Infrequently used Prone to scaling Create aerosol

  11. Showers

  12. Any Questions ?

  13. Hot and cold water systems Cause the most cases

  14. Cold Water Storage Tanks

  15. Dirty Tanks = clean & disinfection

  16. Types of Water Heaters

  17. Legionella Control Regulation & Legislation

  18. Legislation • Health & Safety at Work etc Act 1974 (HSAWA) • Management of Health & Safety at Work Regulations 1999 (MHSWR) • Control of Substances Hazardous to Health Regulations 2002 (COSHH) • The Notification of Cooling Towers and Evaporative Condensers 1992 • The Control of Legionella Bacteria in Water Systems Approved Code of Practice & Guidance 2001 ACoP L8 • Reporting of Injuries, Diseases and Dangerous Occurrences Regulations 1995 (RIDDOR)

  19. Approved Code of Practice • Identification and assessment of risk • Prepare a scheme for preventing or controlling the risk • Implement, manage and monitor precautions • Keep records • Appoint a person to be managerially responsible

  20. Risk Assessment & Control Measures Why does it matter ? The HSE views Legionnaires’ Disease as preventable • To satisfy regulation and legislation • To show due diligence • To protect employees and public

  21. When Should It Be Repeated? • At least every 2 years or when NO longer valid e.g. • Changes to the use of the building. • Availability of new information. • Control measures are no longer effective. • Case of LD associated with system. • Changes to the system or its use.

  22. Typical Written Scheme: H & C Water Systems Checks • Monthly – temperature checks • Quarterly - shower cleaning • Six monthly - CWS Tank temperatures • Annually - CWS Tank inspections, calorifier checks • Other systems as required • Weekly - flushing little used outlets

  23. Management & Training • Inadequate management, lack of training and poor communication have all been identified as contributory factors in outbreaks of Legionnaires Disease. • Those who are appointed to carry out control measures and strategies should be suitably informed, instructed, properly trained and their competency assessed.

  24. Appropriate Records • Responsible persons • Significant findings of the risk assessment • Written scheme of actions and control measures • Results of any monitoring, inspection, test or check carried out

  25. Typical Log Book Records • Training records • Lines of communication • Current state of operation • Signature of person that did the work • Plans or schematic drawings • Visit log for engineers/contractors

  26. Schematics Example

  27. Why keep Records? • To demonstrate compliance with the law • Show what control measures are being taken • Monitor water temperatures, system cleanliness, bacteria levels (if appropriate) • Show trend analysis learn more about the systems • Review performance • Provide evidence of reducing the risk

  28. Any Questions ?