1 / 9

Upgrade of the Breakers Control Module in 13 kA EE systems

Upgrade of the Breakers Control Module in 13 kA EE systems. Bozhidar Panev TE-MPE-EE 27.03.2014. Overview of the 13kA EE systems. There are 32 EE systems located in UA and RR underground areas. Overview of the 13kA EE systems. Extraction switches. Interface electronics. BCMs. DQRQ.

lorant
Télécharger la présentation

Upgrade of the Breakers Control Module in 13 kA EE systems

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Upgrade of the Breakers Control Modulein 13 kA EE systems Bozhidar Panev TE-MPE-EE 27.03.2014

  2. Overview of the 13kA EE systems • There are 32 EE systems located in UA and RR underground areas.

  3. Overview of the 13kA EE systems Extraction switches Interface electronics BCMs DQRQ R=7.7 or 6.6 mOhms

  4. Powering of the holding coil (230 VDC/8 VDC) • Holding coil function is to close and to keep the breaker closed • In the beginning of the closing process the coil is powered with 230VDC (~22A), then switched to 8VDC (~0.5A). • A few parameters of the holding coil: L = 3 H; R = 10 Ohms • Due to large inductances, electrical arcs will be present during the commutation of the power sources

  5. Power switching relay (230V/8V) of the holding coil(RL4,6,8,10 in BCMs) • Inspection in 2012 found significant erosion of the contacts due to electrical arcs. The risk of burning the holding coil is significant. • As a part of preventive maintenance it has been decided to replace these relays in all EE systems (RB and RQD/F) – 256 relays in total. • New contactor was selected: • More solid contact system • Better contact material - AgSnO2 instead of AgCdO • After 500 cycles  negligible erosion of the contacts was observed

  6. Revision of the holding coil protection • The reason: Two cases in the past when holding coils were overheated and damaged by high current. • Question arises: Does the existing circuit breaker provide effective overload protection? • Circuit breaker parameters: • “Merlin Gerin” series C60N I = 10A; 400V; 2 – poles; reaction curve  C; Breaking capacity = 10kA

  7. Revision of the holding coil protection • Requirements for the protection circuit breaker • In case of continuous powering of the holding coil with 230V  adequate reaction in order to save the coil • Not to trip during “closing” inrush current • React in case of short circuit • The analysis shows: C-curve circuit breaker might react with delay of ~300 sec. • New circuit breaker was selected and tested: “Schneider”(C60HD) I = 6A; D-curve

  8. Test results for the new selected circuit breaker • 200 cycles in P-hall  no trip during “closing” inrush current • At the intentionally created fault mode, which provides continuous powering of the holding coil with 230V, the new selected circuit breaker has shown excellent performance • Overload reaction within 10s after closing ~6 sec

  9. Thank You

More Related