Praktikum Relai Proteksi. Pengujian Relai Arus Lebih. PENGUJIAN RELAI ARUS LEBIH. Pengujian Individual Pengujian Fungsi Pengujian Individual : Adalah menguji individu relai untuk Mengetahui apakah relai masih dalam Kondisi standar Pengujian fungsi: Adalah menguji fungsi relai dengan

marlow
Télécharger la présentation

Praktikum Relai Proteksi

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Praktikum Relai Proteksi

  2. Pengujian Relai Arus Lebih

  3. PENGUJIAN RELAI ARUS LEBIH • Pengujian Individual • Pengujian Fungsi • Pengujian Individual : • Adalah menguji individu relai untuk • Mengetahui apakah relai masih dalam • Kondisi standar • Pengujian fungsi: • Adalah menguji fungsi relai dengan • memberikan injeksi pada relai sampai • relai trip

  4. Yang perlu diperhatikan dalam pengujian • Individual adalah : • Internal diagram relai yang diuji • Setting relai yang diuji • Portable Test Set dan perlengkapannya • Item pengujian • Wiring dan prosedur pengujian • Blanko uji untuk mencatat hasil uji • Kesimpulan ( membandingkan hasil uji • dengan data teknk ) • Item Pengujan : • Arus kerja dan Arus kembali • Karakteristik relai (waktu kerja) • Karakteristik Instant

  5. MCGG 82 INDICATOR RESET TMS SETTING CURVE SELECTION INST SETTING 49 50 TIME DELAY TRIP < < 21 13 < < + POWER SUPPLY CIRCUIT INST TRIP Is - Vx 14 22 < CURRENT SETTING Ph INPUT CIRCUIT Ph < RL 1-1 35 33 PHASE FAULT TIME DELAYED TRIP OUTPUT CONTACT 34 INST SETTING CURVE SELECTION TMS SETTING RL 1-2 29 47 48 TIME DELAY TRIP < 30 < 23 < OUTPUT CIRCUIT Ph < INST TRIP RL 2-1 Is 36 24 37 PHASE FAULT INSTATANEOUS TRIP OUTPUT CONTACT < CURRENT SETTING Ph < INPUT CIRCUIT Ph 38 RL 2-2 41 42 TMS SETTING INST SETTING CURVE SELECTION 45 RL 3-1 7 46 TIME DELAY TRIP < 6 < EARTH FAULT TIME DELAYED TRIP OUTPUT CONTACT 25 < < 5 INST TRIP Is RL 3-2 2 26 < INPUT CIRCUIT Ph < CURRENT SETTING Ph 1 OUTPUT CIRCUIT E/F RL 4-1 8 10 TMS SETTING INST SETTING CURVE SELECTION 43 EARTH FAULT INSTATANEOUS TRIP OUTPUT CONTACT 9 RL 4-2 16 44 TIME DELAY TRIP < < 27 < < 15 INST TRIP Is 28 < INPUT CIRCUIT E/F < CURRENT SETTING E/F

  6. A B C E INST INST t t NAME PLATE I > Is I > Is RESET KARAK TERISTIK RELAI OCR / GFR TIPE MCGG 82 IBA DOC

  7. CONTOH CARA SETTING DENGAN MENGGUNAKAN OCR / GFR TIPE MCGG82 @ SETTING ARUS OCR /GFR DENGAN TUNDA WAKTU 0.1 0.05 0.1 0 0.2 0 ARUS SETTING 0.4 0 0.4 0 ARUS NOMINAL RELAI 0.4 0 0.8 0 FAKTOR PABRIK IBA DOC

  8. # MISAL ARUS SETTING Is = 6 A. Is = 1.2 In POSISI SAKLAR : 0.1 0.05 0.1 0 Is = ( 0.1 + 0.1 + 0.2 + 0 + 0 + 0 + 0.8 ) x 5A = 1,2 x 5A = 6 A 0.2 0 0.4 0 0.4 0 0.4 0 0.8 0 IBA DOC

  9. PEMILIHAN KARAKTERISTIK TRIP TEST : CURVA SI : 0 1 0 1 0 1 0 1 0 1 0 1 IBA DOC

  10. KURVA / KARAKTERISTIK @ STANDARD / NORMAL INVERSE ( SI ) @ VERY INVERSE ( VI ) @ EXTREMELY INVERSE ( EI ) @ LONG TIME INVERSE ( LTI ) IBA DOC

  11. SETTING WAKTU MISAL : KARAKTERISTIK EI ARUS GANGGUAN 3 x Is ( I = 3 ) WAKTU KERJA = 1 DETIK PEMILIHAN TMS : POSISI SAKLAR 0,025 0,05 0 0,05 0 0,1 0 0,2 0 0,2 0 0,4 IBA DOC

  12. SETTING INSTANT POSISI SAKLAR 0 1 0 2 0 4 0 8 0 16 0 IBA DOC

  13. ARUS PICK UP [ ARUS AWAL / MULA ] • ARUS MINIMUM YANG MENYEBABKAN RELAI BEKERJA • 2. ARUS DROP OFF [RESET/ KEMBALI ] • ARUS MAKSIMUM YANG MENYEBABKAN RELAI TIDAK • BEKERJA. • 3. RASIO ARUS PICK UP DENGAN DROP OFF I I pick up I reset I beban t t gangguan

  14. PRINSIP PENGUJIAN INDIVIDUAL RELAI ARUS LEBIH 21 TIMER 22 29 23 30 24 START STOP 25 26 27 220 Vac 13 R 28 Vdc 14 A 220 Vac SLIDE TRAFO ISOLASI RANGKAIAN PENGUJIAN

  15. PENGUJIAN RELAI ARUS LEBIH • Alat yang diperlukan • - Relai arus lebih tipe MCGG 82 • - Alat uji model TPR 22CV • - suplai tegamgam AC dan DC • - Kabel konektor • B. Jenis pengujian • - arus kerja dan kembali • - waktu kerja • - karakteristik instant

  16. C. Prosedur pengujian C1. Persiapan 1. Buat rangkaian pengujian seperti gambar 2. Saklar power (2) posisikan pada off dan setel knob pengatur pada posisi berikut; Output A (5) Min Output B (6) Min Selector A (7) 5A Selector B (8) Test condition (9) Other relay Fault witch (10) A-Circuit sw (11) On Voltmeter sw (12) Make-break sw (22) Make (normally opem) Time-Lamp sw (24) off

  17. C2. Pengujian Arus kerja minimum (pick up) dan arus reset (drop off) 1. Power switch putar ke posisi On 2. Posisikan Time/lamp switch pada Lamp 3. Putar knob A searah jarum jam perlahan lahan sampai relai bekerja menutup kontak dan lampu akan menyala 4. Baca nilai arus pada Ammeter A ,ini adalah arus pick up dan catat pada blanko. 5. turunkan arus secara perlahan lahan sampai lampu padam baca dan catat , ini adalah arus reset. 6. Ulangi percobaan diatas untuk besaran setting yang lain (bila setting diubah perhatikan selector A) 7. Bila pengujian telah selesai segera power swutch diputar ke off.

  18. C3. Pengujian karakteristik waktu 01. Periksa masing masing item C1, dan set selector A pada posisi lebih besar dari arus uji. 02. Periksa arus setting relai yang diuji dan tentukan arus uji 200% (jika setting 2A maka arus uji 4A) 03. Hidupkan alat uji dengan memutar power switch ke on 04. Naikan arus uji dengan memutar knob output A sampai Ammeter menunjuk 4A ( catatan operasi harus cepat ) 05. Matikan alat uji dengan memutar power switch ke off 06. Putar time/lamp ewitch ke posisi Time 07. Tekan reset untuk meredet counter 08. Putar power switch ke on, relai akan start dan counter akan mencatat waktu kerja relai 09. Matikan alat uji dengan memutar power switch ke off. 10. Ulangi percobaan diatas untuk untuk arus uji yang lenih besar, misal : 300%, 400%,500%.

  19. + 21 13 A - 14 22 23 Suplai 220V 29 B 1 2 T1 T2 P1 P2 C2 C1 C0 VOLTMETER 220 V CT SEC 24 30 ON ON EXT 25 MAKE TIME 41 C POWER OFF 26 ON 42 OFF FAULT BREAK LAMP OFF INT OFF 27 A SELECTOR TPR 22 CV 1 E/F 28 2 15 V A A 16 OVR UVR 75 V OCR UCR OTHER RELAY MCGG 82 150V 10 A B A B 5 A 300V OFF 1 A OCR / GFR YANG DIUJI TEST CONDITION MIN MAX MIN MAX B SELECTOR RANGKAIAN PENGUJIAN OCR/GFR DENGAN ALAT UJI TPR 22 CV

  20. + 21 13 A A-AC A-AC - V-AC/DC 14 22 23 29 B 24 30 25 41 A-AC C 26 42 27 1 E/F 28 2 15 16 MCGG 82 220V OCR / GFR YANG DIUJI Rangkaian pengujian relai arus lebih tipe MCGG 82 Dengan alat uji tipe Multiamp SR76A

  21. PENGUJIAN RELAI OCR /GFR MCGG 82 HAND TERMINAL RELAI OCR / GFR MCGG 82 ALAT UJI XS92a ABB 13 + 21 Vx - 14 22 23 29 t > 24 30 25 41 t >> 26 42 27 1 to> 28 2 15 to >> 16 RANGKAIAN PENGUJIAN RELAI OCR / GFR TIPE MCGG 82 IBA 2006

  22. PROSEDUR PENGUJIAN PARAMETER FR = 50 DFR= 0 DF = 0 FC = SESUAI JENIS GANGGUAN SQ = PU / DROP A = SQ = 2 IRA = 0 A = 0 TO = 100 AUTO TL = 100 SQ = 1F0 TF = > t set A = 1 IN1 = 1 IN2 = 0 OU1= 0/1 OU2= 0 TI = 2 TT = 0 MOD= UI MT = 1 OP = 0 UI U = 57 V I = . . . A PHI= 90 DU = 0 DI = 0,01 DPH=0 LUH = 220 LUL = 0 LIH = 20A LIL = 0 LPI =359 LPO = 0 UJI PU / DROP OFF START + / - Sambungan ke kontak dilepas Uji waktu kerja [ sambungan ke kontak dipakai] START + 2X 0 ENTER IBA 2006

  23. FC = CODE GANGGUAN 111 = R KE E 112 = S KE E 113 = T KE E 121 = GANGGUAN R S 122 = GANGGUAN ST 123 = GANGGUAN TR IBA 2006

  24. PENGUJIAN RELAI DIFERENSIAL

  25. PENGUJIAN RELAI DIFERENSIAL BIAS • Pengujian Individual • Pengujian Stabilitas • Pengujian Individual : • Adalah menguji individu relai untuk • Mengetahui apakah relai masih dalam • Kondisi standar • Pengujian Stabilitas : • Adalah menguji fungsi relai apakah stabil • Untuk gangguan di luar

  26. Yang perlu diperhatikan dalam pengujian • Individual adalah : • Internal diagram relai yang diuji • Setting relai yang diuji • Portable Test Set dan perlengkapannya • Item pengujian • Wiring dan prosedur pengujian • Blanko uji untuk mencatat hasil uji • Kesimpulan ( membandingkan hasil uji • dengan data teknk ) • Item Pengujan : • Arus kerja minimum dan waktu kerja • Sope Karakteristik relai • Harmonic restraint

  27. PRINSIP PENGUJIAN INDIVIDUAL RELAI DIFERENSIAL BIAS PENGUJIAN ARUS PICK UP MINIMUM (g%) DAN WAKTU KERJA RELAI RELAI TIPE HU START TIMER STOP 10 1 5 220 Vac 3 7 R A 220 Vac SLIDE TRAFO ISOLASI RANGKAIAN PENGUJIAN RELAI DIFERENSIAL BIAS

  28. PRINSIP PENGUJIAN INDIVIDUAL RELAI DIFERENSIAL BIAS PENGUJIAN SLOPE ( V % ) I1 R RELAI TIPE HU A 10 220 Vac 1 5 3 7 I0 R A 220 Vac SLIDE TRAFO ISOLASI RANGKAIAN PENGUJIAN RELAI DIFERENSIAL BIAS

  29. PRINSIP PENGUJIAN INDIVIDUAL RELAI DIFERENSIAL BIAS PENGUJIAN HARMONIC RETRAINT Idc A SUMBER DC RELAI TIPE HU 10 1 5 3 7 S R Iac A 220 Vac SLIDE TRAFO ISOLASI RANGKAIAN PENGUJIAN RELAI DIFERENSIAL BIAS

  30. Pengujian Relai Diferensial tipe D202 BBC A. Alat yang digunakan - relai diferensial tipe D202 BBC - portable test set tipe SR51a multiamp - suplai tegangan 110V dc dan 220V ac - kabel konektor B. Item pengujian - arus kerja minimum (pick up) - waktu kerja relai - karakteristik/slope C. Rangkaian pengujian lihat gambar pengujian relai diferensial D202 dengan alat uji portable test set SR51a.multiamp.

  31. Rangkaian pengujian arus kerja Minimum dan waktu kerrja relai Diferensial D202 BBC 1 17 18 2 19 3 20 5 21 6 22 7 00.000 9 + VOLT RANGE SWITCH 13 11 110 V DC 15 12 - Multi amp Relai yang diuji D202 ABB

  32. Rangkaian pengujian karakteristik slope relai Diferensial D202 BBC 1 17 18 2 19 3 20 5 21 6 INITIATE 22 7 00.010 9 + VOLT RANGE SWITCH 13 11 110 V DC OUTPUT #1/#2 15 12 - Multi amp Relai yang diuji OUTPUT #3

  33. D. Prosedur pengujian D1. posisikan kontrol dari alat uji : 01. saklar ‘power on’. . . . . . . . . . . . . . . . . . Off 02. saklar ‘Timer operation selector’. . . . . . . . . Atas NO MOM , bawah Cont 03. knob ‘Main control’ . . . . . . . . . . . . . . . . . Nol 04 saklar ‘aux. power’ . . . . . . . . . . . . . . . . . INT 05. saklar ‘Range Voltmeter . . . . . . . . . . . . . . 300 V 06. Saklar‘Voltmeter selector’ . . . . . . . . . . . . . EXT.AC 07. Saklar ‘Aux. selector’ . . . . . . . . . . . . . . . . VERN 08. Knob ‘Aux. control’. . . . . . . . . . . . . . . . . Nol 09. Saklar ‘AC range’ . . . . . . . . . . . . . . . . . . 10 A 10. Saklar ‘DCrange’ . . . . . . . . . . . . . . . . . . .5 A 11. Saklar ‘Main Ammeter range’ . . . . . . . . . . . . Lebih besar dari arus uji 12. Saklar ‘Voltage Relay Test’ . . . . . . . . . . . . . Set Norm 13. Saklar ‘ Output #1 / #2 . . . . . . . . . . . . . . . . Output #1 D2. Pengujian pick up 01, Hubungkan alat uji ke sumber tegangan 220 V ac , dan yakinkan bahwa alat uji dalam keadaan off. 02. hubungkan operating dan salah satu restraint relai ke output #1 alat uji ( lihat gambar ) . 03. Hubungkan terminal ‘kontak relai’ alat uji ke kontak trip relai 04. Pilih ‘range Ammeter’ lebih besar dari arus yang diukur/diuji

  34. 05. Posisikan saklar ‘Timer Operation selector’ yang atas pada ‘NO Maint’ • dan yang bawah pada ‘Cont’ • 06. Hidupkan alat uji dan lampu tanda akan menyala , dan tekan saklar ‘initiate’. • 07. Putar knob ‘main control’ untuk menambah arus output sampai relai pick up • dan lampu ‘continuity’ menyala dan catat besarnya arus pada blanko uji. Aux. control dapat untuk mengatur arus lebih halus. • 08. Putar “main control’ atau ‘aux. control’ ke kiri untuk menurunkan arus uji, sampai relai reset dan catat besarnya arus ini pada blanko uji. • 09. Putar ‘Main control’ dan ‘Aux. control’ ke posisi nol, dan matikan alat uji. • D3. Pengujian Karakteristik waktu • 01. Hidupkan alat uji . • 02. Posisikan ‘Timer operation selector’ yang atas pada ‘NO Mom’ dan yang bawah pada posisi ‘Cont’ • 03. Sambil menekan sklar ‘Initiate’ terus ,putar knob ‘Main control’ sampai arus mencapai 1,5 kali arus pick up, setelah itu lepas saklar ‘Initiate’ • 04. Posisikan ‘timer operation slector’ yng atas pada ‘NO Maint’ dan yang bawah pada ‘Timer’, dan tekan saklar ‘Initiate’ • 05. Relai akan bekerja ,timer start dan setelah relai trip maka timer akan stop dan catat waktu kerja nya pada blanko uji. • 06. Posisikan knob ‘main control’ maupun ‘Aux. control’ ke posisi nol dan matikan alat uji.

  35. D4. Pengujian karakteristik / slope 01. Hubungkan kumparan retraint ke output #1 pada tap 0 – 80 V ; 12,5 A 02. Hubungkan kumparan operating ke output #3 , dan common dari kedua output bisa dijadikan satu , lihat gambar penguian . 03. Hubungkan terminal ‘kontak relai’ alat uji ke kontak dari relai yang diuji. 04. Pilih ‘Main range ammeter’ lebih besar dari arus uji 05. Putar ‘aux. selector’ switch pada posisi 24 – AC – 3 06. Saklar ‘timer operation selector’ yang atas pada poisi ‘NO Maint’ dan yang bawah pada ‘cont’ 07. Hidupkan alat uji dan tekan yombol ‘ Initiate ‘ 08. Putar knob ‘main control’ untuk menmbah ‘output #1 (arus retraint), dan ‘aux. control’ untuk menambah arus ‘output #3’ (arus operating), sampai relai kerja. 09. Catat kedua besran arus ini dalam blanko uji, dan ulangi untuk besaran yang lain. 10. Possikan kedua ‘main control’ dan ‘Aux. control’ pada poisi nol, dan matikan alat uji.

  36. PENGUJIAN RELAI DIFERENSIAL TIPE MBCH 12 GEC • Alat yang digunakan • - relai diferensial tipe MBCH 12 GEC • - alat uji ( portable tet set ) tipe TPR 22CV KDK • - sumber tegangan dc dan tegangan suplai 220 V ac • - kabel konektor • Item Pengujian • - Arus kerja mnimum • - waktu kerja relai • - karakteristik / slope • Rangkaian pengujian • perhatikan gambar rangkain pengujian relai difernsial tipe mbch 12 GEC dengan alat uji ( portable test set 0 tipe TPR 22CV KDK

  37. RELAI DIFERENSIAL 2L1-1 1 3 23 T5 5 TRIP OUTPUT 2 2L1-2 I1 2L1 2 4 24 25 T4 6 OUTPUT CIRCUIT I2 TRIP OTHER PHASES 10 T3 26 13 + INPUT CIRCUIT Vx 14 - 12 T2 RESET 9 2L2-1 ALARM 27 11 OPERATE 2L2 1 Idiff 28 T1 INPUT CIRCUIT INTERNAL DIAGRAM RELAI DIFERENSIAL TIPE MBCH 2 BIAS

  38. Prosedur pengujian • 1. Buat rangkaian pengujian seperti gambar • 2. pilih setting dari relai yang akan diuji • 3. Setel posisi kontrol dari alat uji seperti berikut ; • - Power switch off • - A output Min • - B Output Min • - A selector ( 0 – 50 A ) restraint coil • - B Selector (0 – 10 A ) operating coil • - Test Condition Other relay • - Switch Fault off • - A Circuit switch off • - Voltmeter switch off • - Make / Break witch Make • - Time / Lamp off • D1. Pengujian arus kerja minimum • 1. periksa setting relai • 2. posisikan power switch pada posisi On • 3. putar Time / lamp pada posisi Lamp • 4. Naikan arus dngan mengatur B Output dan perhatikan sampai relai • start dan hentikan putaran knob.

  39. Baca arus pada meter B , tepat pada saat lampu check menyala , ini adalah arus kerja mnimum. • Kemudian putar knob output B ke kiri sampai lampu check padam dan ini adalah arus reset. • Putar knob ke posisi nol dan matikan alat uji dengan memutar power swtch ke posisi off. • D2. pengujian waktu kerja • 1. Posisikan saklar / knob seperti butir D3. • 2. putar power switch pada posisi On • 3. Putar knob Output B searah jarum jam sampai meter B • menunjuk arus 200 % dari arus kerja minimum • 4. Posisikan power switch pada off • 5. putar Time / Lamp switch pada posisi Time • 6. tekan Reset untuk mereset counter display • 7. jika power switch diputar ke On , Counter dan relai • yang diuji akan bekerja • 8. jika kontak menutup Counter akan stop dan mencatat • waktu kerja relai dan catat besaran ini pada blanko uji. • 9. Matikan alat uji , posisi saklar power switch ke off.

  40. D2. menguji karakteristik / slope 1. Posisikan saklar / knob seperti butir D3 dan setel ; A selector . . . . . 15 A A circuit switch . . . On Time / Lamp switch . . Lamp 2. Putar power switch pada posisi On 3. putar A output knob sampai meter A menunjuk 5A 4. Putar B output knob pelan pelan sampai relai mulai kerja 5. Baca arus pada meter B bila lampu check kontak menyala , ini adalah arus kerja . 6. ulangi butir 3 s/d 5 untuk arus 10 A 7. bila sudah selesai matikan alat uji , posisikan power switch pada off.

  41. PENGUJIAN INDIVIDUAL RELAI DIFERENSIAL IMPEDANSI TINGGI PENGUJIAN ARUS PICK UP DAN DROP OFF DAN WAKTU KERJA RELAI RELAI MCAG 34 START TIMER STOP 3 1 23 24 25 26 27 28 220 Vac R A 220 Vac SLIDE TRAFO ISOLASI RANGKAIAN PENGUJIAN RELAI DIFERENSIAL IMPEDANSI TINGGI

  42. PENGUJIAN RELAI DIFERENSIAL MCAG34 HAND TERMINAL RELAI DFERENSIAL MCAG34 ALAT UJI XS92a ABB 23 24 25 26 27 28 1 3 RANGKAIAN PENGUJIAN RELAI DIFERENSIAL TIPE MCAG 34 IBA DOC 2003

  43. PROSEDUR PENGUJIAN PARAMETER FR = 50 DFR= 0 DF = 0 FC = SESUAI JENIS GANGGUAN SQ = PU / DROP A = SQ = 2 IRA = 0 A = 0 TO = 100 AUTO TL = 100 SQ = 1F0 TF = > t set A = 1 IN1 = 1 IN2 = 0 OU1= 0/1 OU2= 0 TI = 2 TT = 0 MOD= UI MT = 1 OP = 0 UI U = 57 V I = . . . A PHI= 90 DU = 0 DI = 0,01 DPH=0 LUH = 220 LUL = 0 LIH = 20A LIL = 0 LPI =359 LPO = 0 START - 0 2x ENTER

  44. FC = CODE GANGGUAN 111 = R KE E 112 = S KE E 113 = T KE E 121 = GANGGUAN R S 122 = GANGGUAN ST 123 = GANGGUAN TR

  45. RELAI DIFERENSIAL BIAS PENGUJIAN INDIVIDUAL RELAI DIFERENSIAL IMPEDANSI TINGGI PENGUJIAN TEGANGAN PICK UP DAN DROP OFF DAN WAKTU KERJA RELAI RELAI MFAC 14 START TIMER STOP 3 1 27 28 220 Vac R 220 Vac V SLIDE TRAFO ISOLASI RANGKAIAN PENGUJIAN

  46. TRAFO DAYA YY0 P1 CT1 CT2 P1 P1 P1 U2 U1 I1 I2 PAM S1 S1 A A PENGUJIAN STABILITAS RELAI DIFERENSIAL BIAS

  47. Pengujian Relai Frekuensi Kurang