An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Fire Department Issues & Minimum Requirements for Housing Development Capital City Fire/Rescue Fire Marshal’s Office

  2. Plan Review Process • Sprinkler System Plans (Submit 3 sets of plans) • Fire Suppression Systems • Review apparatus and emergency access • Ensure project meets Fire & Life safety requirements

  3. Fire Code Process 2006 IFC Adopted by CBJ ALASKA STATE FIRE MARSHAL CBJ 2012 IFC To be adopted by State Fire Marshal Spring 2014 + TITLE 19 Amendments Referenced Standard 2009 IFC Currently adopted by State Fire Marshal

  4. Fire Apparatus Access • Fire Apparatus Roads • Minimum width of 20 feet • Dead-End Fire Apparatus • Access Roads Requirements: • 150’ or less No turnaround required • 151’ -500’ 120’ hammerhead, 60’ “Y”, or 96’ diameter cul-de-sac

  5. Apparatus Turnarounds Apparatus Turnarounds

  6. Fire Flow Requirements Hydrant Location, Distribution and Spacing depend upon Fire-Flow Requirement (gpm) Minimum Required Fire-Flow (gpm) depends upon Construction Type & Square Footage Example: A 4,000 sq.ft., Type V-B building has a Fire-Flow of 2,000 gpm. A 2,000 gpm Fire-Flow requires a minimum of 2 hydrants, spaced no more then 450, with a 225’maximum distance on road frontage to a hydrant to a hydrant

  7. Sprinkler Systems NFPA 13 provides protection to not only get people out to safety, but also to control or extinguish the fire – saving the building and its contents. NFPA 13R requirements provide for a level of protection that allows occupants to escape a building in the event of a fire.

  8. Fire Alarm Systems Sprinkler systems with 20 or more heads are required to be monitored by a fire alarm.

  9. Knox Boxes / Fire Entry Knox Box required for any Structure that has a suppression or fire alarm system Knox-Vault meets both shunt trip requirement AND Knox Box requirement for new construction.

  10. Signage Requirements FDC FIRE LANE shall be marked with signage indicating “NO PARKING – FIRE LANE” Any Fire Department Connection shall be marked with FDC sign

  11. Knox Plug Requirement Fire Department Connections shall be protected with approved locking caps

  12. Contact Us: Capital City Fire/Rescue Fire Marshal’s Office 820 Glacier Avenue Juneau, AK 99801 (907) 586-5322 Fire Marshal Dan Jager Deputy Fire Marshal Sven Pearson Visit our webpage on the CBJ Website: http://www.juneau.org/ccfr