UNDERGROUND CABLES

UNDERGROUND CABLES. Introduction p.399. Generally electric Cables consists of Conductors : Stranded copper or aluminum conductors (as illustrated in OHTL) Insulation : to insulate the conductors from direct contact or contact with earth External protection: against ……….

mikaia
Télécharger la présentation

UNDERGROUND CABLES

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. UNDERGROUND CABLES

  2. Introductionp.399 • Generally electric Cables consists of Conductors :Stranded copper or aluminum conductors (as illustrated in OHTL) Insulation: to insulate the conductors from direct contact or contact with earth External protection: against………

  3. Overhead Lines Versus Underground Cables p. 464 1- The insulation cost is more in case of cables as compared to O.H.T Lines and depends on operating voltage of cable. kV : 0.4 11 33 66 132 220 400 Cost ratio: 2 3 5 7 9 13 24 2- The erection cost of O.H.T lines is much less than the underground cables. 3- Inductive reactance of O.H.T. Lines is more, so the voltage regulation is better in case of underground cables (Low voltage drop).

  4. 4- Capacitance and charging current is high in case of underground cables. C Xc = 1/ωC Charging current (Ich)= V/Xc = ωC.V For long distance power transmission, the charging current is very high results in over voltages problems. Its not recommended to transfer power for a long distance using underground cables. 5- Current carrying capacity is more in case of O.H.T Lines conductors (better cooling conditions) for the same power transmission. Therefore, low cross sectional area and cost for O.H.T Lines conductors.

  5. 6- Underground cables give greater safety, so it can be used in: • Big cities and densely populated area. • Submarine crossing. • Power stations and substations. • Airports.

  6. Cable Construction 1- Conductors (Cores) ● Stranded aluminum or copper conductors ● Conductors with high conductivity and low resistance. 2- Insulation: to insulate the conductors from direct contact or contact with earth. 3- Screening (Insulator shielding): semi-conductor material to uniformly distribute the electric field on insulator.

  7. 4- filling material. 5- Metallic sheath: A sheath made of lead or aluminum or cupper is applied over the insulation to prevent moisture or chemicals from entering the insulation. 6- Armour: (درع) Bars of steel to increase the mechanical strength of cable. 7- Outer cover to protect the metal parts of cables ( rubber).

  8. 22kv Medium Voltage Underground XLPE Power Cable

  9. 11kv Copper Core and Shield Power Cable 25mm http://jpcable99.en.made-in-china.com/product/KMVEouLAhBRW/China-11kv-Copper-Core-and-Shield-Power-Cable-25mm.html

  10. 500 Kv High Voltage XLPE Cable (YJLW02/ YJLW03)

  11. Types of Cables Insulating materials Performance p. 400 Insulator material should have: • High insulation resistance (MΩ-GΩ). • High dielectric strength. • Good mechanical strength. • High moisture resistance (non-hygroscopic) • Withstand temperature rise. • Not affected by chemical

  12. Types p. 400 1- Vulcanized Rubber Insulations: Rubber is used in cables with rated voltage 600- 33 kV. Two main groups: General Purpose Special Purpose Four Main Types: Butyl rubber Silicon rubber Neoprene rubber Styrene rubber

  13. 2- Polymer Insulations: 2.1 PVC (Poly Vinyl Chloride) • rated voltage 3.3 kV. • Grades of PVC: General Purpose Type Hard Grade Type Heat resisting Type 2.2 Polythene (Polyethylene) • XLPE (البولى ايثلين التشابكى)rated voltage up to 275 kV.

  14. 3- Paper insulated : 3.1 Paper insulator: rated voltage V up to 66 kV 3.2 Oil- impregnated paper is used in solid type cables up to 69 kV and in pressure cables (gas or oil pressure ) up to 345 kV.

  15. Types of Cables p.466 1- Number of Cores: • Single- Core Cables. • Multi-Core Cables

  16. 2- According to Insulating Material • Paper Cables • Polymer Cables PVC – XLPE • Rubber Cables EPR - PR

  17. 3- According to Voltage Level • High and Extra High voltage Cables H.V: 33 – 230 kV EHV: V > 230 kV • Medium Voltage Cables V: 1- 33 kV • Low Voltage Cables V up to 1 kV.

  18. 4- According to Utilization of Cables • Transmission and Distribution Cables XLPE Cables- Paper cables • Installation Cables التمديدات PVC • Submarine Cables البحرية Rubber cables -Industrial Cables المنشآت الصناعية ●PVC up to 3.3 kV ● XLPE up to 11 kV

  19. Electrical Characteristics of Cables p. 408

  20. Electric Stress in Single-Core Cables p. 408 D= q/(2πx) E = D/ε = q/(2πεx) q: Charge on conductor surface (C/m) D: Electric flux density at a radius x (C/m2) E: Electric field (potential gradient), or electric stress, or dielectric stress. ε: Permittivity (ε = ε0. εr) εr: relative permittivity or dielectric constant.

  21. r: conductor radius. R: Outside radius of insulation or inside radius of sheath. V: potential difference between conductor and sheath (Operating voltage of cable). Dielectric Strength: Maximum voltage that dielectric can withstand before it breakdown. Average Stress: Is the amount of voltage across the insulation material divided by the thickness of the insulator.

  22. Emax= E at x = r = V/(r.lnR/r) Emin = E at x = R = V/(R.lnR/r) For a given V and R, there is a conductor radius that gives the minimum stress at the conductor surface. In order to get the smallest value of Emax: dEmax/dr =0.0 ln(R/r)=1 R/r=e=2.718

  23. Insulation thickness is: R-r = 1.718 r Emax = V/r (as: ln(R/r)=1) Where r is the optimum conductor radius that satisfies (R/r=2.718)

  24. Example A single- core conductor cable of 5 km long has a conductor diameter of 2cm and an inside diameter of sheath 5 cm. The cable is used at 24.9 kV and 50 Hz. Calculate the following: a- Maximum and minimum values of electric stress. b- Optimum value of conductor radius that results in smallest value of maximum stress.

  25. a- Emax = V/(r.ln(R/r)) = 27.17 kV/cm Emin = V/(R.ln(R/r)) = 10.87 kV/cm b- Optimum conductor radius r is: R/r = 2.718 r= R/2.718= 0.92 cm The minimum value of Emax: = V/r = 24.9/0.92=27.07 kV/cm