1 / 24

Service Section Technical Training

Service Section Technical Training. Air Conditioning Troubleshooting. Air Conditioning System. An air conditioning system can be divided into 2 main functioning groups. Electrical circuit Refrigerant circuit. Air Conditioning System.

ojan
Télécharger la présentation

Service Section Technical Training

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Service Section Technical Training

  2. Air Conditioning Troubleshooting

  3. Air Conditioning System An air conditioning system can be divided into 2 main functioning groups • Electrical circuit • Refrigerant circuit

  4. Air Conditioning System To troubleshoot a system, one must have to adopt “divide and conquer” technique • Divide the “Big” problem into multiple smaller problems • Solve each of the problem individually • Put electrical problem in first priority • A main point to take note is that if a system do not start, the faulty must be from electrical fault

  5. Troubleshooting electrical faults Always ask a lot of questions and do not make assumption before we check • Is the power supply being switch on / being connected ? • Is the wiring being done properly? • Is the wire loose ? • Is there any signal coming from controller or thermostat ?

  6. Troubleshooting electrical faults 1) Unit will not start • Main power supply fail ? Voltage fluctuation ? • Blown fuse or varistor ? • Faulty transformer ? • Loose connections ? • Shorted or broken wires ? • Safety device opens ? • No signal from thermostat/controller ? • Faulty thermostat ?

  7. Troubleshooting electrical faults 2) Some components do not start • Loose connections ? • Shorted or broken wires ? • No signal from thermostat/controller ? • Faulty magnetic contactor ?

  8. Troubleshooting electrical faults 3) Controller/thermostat • A clear understanding of the functional specification of the controller/thermostat is crucial. • Setting of the controller/thermostat must be obtained. • Operating temperatures must be obtained (exp: room, return air, ambient, water, etc.)

  9. Troubleshooting refrigerant faults Some of the major problems found in a air conditioning system • The air conditioner runs but shortly stops • The air conditioner short cycles with insufficient cooling • The air conditioner runs continuously with insufficient cooling

  10. Troubleshooting refrigerant faults Three main conditions in the air conditioners that are operating but not cooling satisfactorily are • High discharge pressure • Low suction pressure • High suction pressure

  11. Troubleshooting refrigerant faults 1) High discharge pressure • Dirty or partially blocked condenser • Air or other non-condensable gases in refrigeration cycle • Overcharge of refrigerant • Insufficient condensing medium • High temperature condensing medium • Short cycling of condensing air

  12. Troubleshooting refrigerant faults 2) Low suction pressure • Insufficient air or heat load on evaporator coil • Resistance against refrigerant flow • Shortage of refrigerant • Faulty capillary tube or expansion valve

  13. Troubleshooting refrigerant faults 3) High suction pressure • Heavy load conditions • Unit undersized for application • Low superheat adjustment • Improper expansion valve adjustment • Poor installation of feeler bulb • inefficient compressor

  14. Troubleshooting refrigerant faults Some of the problems of refrigerant system can be diagnose through the use of pressure gauge and also an ammeter

  15. H.P L.P AMP Troubleshooting electrical faults Pressure and running current reading • Both high and low pressure are very high • Running current increase extremely Main causes of troubles • Refrigerant overcharged >> Wet operation * In case refrigerant overcharged excessively, high pressure switch or overcurrent relay functions

  16. H.P L.P AMP Troubleshooting electrical faults Pressure and running current reading • Discharge pressure is very high • Suction pressure is a little higher than normal • Running current increases Main causes of troubles • Insufficient condensing medium * Dirty condenser * Partially blocked condenser * Malfunction of condenser fan or fan motor * Reverse revolution of condenser fan * Short cycling of condensing air * High temperature condensing air

  17. H.P L.P AMP Troubleshooting electrical faults Pressure and running current reading • Discharge pressure is a little higher than normal • Suction pressure is very high • Running current increases Main causes of troubles • Unit undersized for application • Heavy load condition * High suction air temperature >> superheated operation • Excessive air flow rate • Excessively opened expansion valve >> wet operation * Poor installation of feeler bulb * Low superheat adjustment

  18. H.P L.P AMP Troubleshooting electrical faults Pressure and running current reading • Discharge pressure is a little lower than normal • Suction pressure is very low • Running current decreases * Frost grows on evaporator coil Main causes of troubles • Shortage of refrigerant • Restricted refrigerant flow >> superheated operation * Expansion valve or capillary tube obstructed * Dryer or filter clogged with dirt * Valve in liquid line partially closed * Obstruction in liquid line * Leaking power element on expansion valve

  19. H.P L.P AMP Troubleshooting electrical faults Pressure and running current reading • Discharge pressure is a little lower than normal • Suction pressure is very low • Running current decreases * Frost grows on evaporator coil Main causes of troubles (continue) • Insufficient heating medium >> wet operation * Poor evaporating air flow rate - Dirty air filter - Slippage of fan belt - Reverse revolution of evaporator fan - Short cycling of cooling air * Light load condition - Low suction air temperature

  20. H.P L.P AMP Troubleshooting electrical faults Pressure and running current reading • Discharge pressure is a little lower than normal • Suction pressure is very high • Running current decreases Main causes of troubles • Malfunction of compressor >> super heated operation

  21. H.P L.P AMP Troubleshooting electrical faults Pressure and running current reading • Both high and low pressures are very low • Running current decreases extremely Main causes of troubles • Extreme refrigerant shortage >> super heated operation

  22. Wet operation Liquid refrigerant comes back to the compressor Liquid compression Insufficient lubrication (washed out) Refrigerant is dissolved in oil Motor coil insulation is being eroded Oil foaming Vane or valve failure Motor coil failure Bearing failure

  23. Super heated operation Suction and discharge gas temperature is higher than the normal Oil temperature becomes higher Carbonization of oil Oil viscosity drops Insufficient cooling for motor coil Incomplete seat action Insufficient lubrication Motor coil failure Bearing failure

  24. Thank you

More Related