1 / 12

Our Experience in Reducing Water Losses by Regulating Pressure in Water Supply Systems

Our Experience in Reducing Water Losses by Regulating Pressure in Water Supply Systems. Prof. Dr. Dipl .- E ng . Gancho Dimitrov Head of Department: Water Supply, Sewage and Purification of Water at at the University of Architecture, Civil Engineering and Geodesy, Sofia, Bulgaria.

olisa
Télécharger la présentation

Our Experience in Reducing Water Losses by Regulating Pressure in Water Supply Systems

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Our Experience in Reducing Water Losses by Regulating Pressure in Water Supply Systems Prof. Dr. Dipl.-Eng. GanchoDimitrov Head of Department: Water Supply, Sewage and Purification of Water at at the University of Architecture, Civil Engineering and Geodesy, Sofia, Bulgaria November 2011, Dubai, UAE

  2. Pressure Reduction • the reduction of water loss and water consumption • the reduction of the accident rate • abolition of restrictions on traffic in the streets • the reduction of operating costs • the substantial reduction in investment • the removal of less amounts of water from the water sources • providing the necessary ecological balance of ecosystems In our experience pressure control in water supply networks is an effective measure for :

  3. Types of pressure control, and our research results • By maintaining constant pressure after the control valve • By maintaining constant pressure after the control valve through water consumption or for specific periods of time; • Maintaining a minimum pressure through the critical point of the water supply network. • individual zones in 45 residences, 120 control valves • reduction of water losses from 15% to 50% of the average water consumption • success in reducing accidents by 50% to 90%

  4. Case Studies: Pressure Management • Total length of water network: 38 127 m • House connections:1 327 • Number of people: 23 209 • Maximum pressure: 9.1 bar • Pressure regulator: DN 300 • Output pressure: 5 bar DMA 1, 2009

  5. Results Fig.1 Change in water consumption at the beginning of the zone b) period from 14-22 June after adjusting pressure. a) period from 12-19 January 2007 before installing the pressure valve;

  6. Case Studies: Pressure Management • Total length of water network: 75 834 m • House connections: 6 550 • Number of people: 27 400 • Pressure regulator: DN 600 • Outlet pressure by night: 3,5 bar • Outlet pressure by day: 5,0 bar DMA 2, 2007

  7. Results Fig. 2 Change in water consumption at the beginning of the zone for the period from 10-15 August 2007 Fig. 3 Change in water pressure at the beginning of the zone for the period from 10-15 August 2007

  8. Results Fig. 4 shaft with valves and pressure reducing valve with a diameter of DN 600 with two operation modes (with 5 bar pressure and 3,5 bar) Effect: • Reduction: • Water losses by 20% • Number of accidents by 75% • Investment recovery period – • 1 year

  9. Case Studies: Pressure Management • Total length of water mains: 104 818 m • Number of people: 100 000 • Pressure regulators: DN 600 and DN 400 • Input pressure: 4,7 bar • Output pressure: 3,7 bar DMA 3, 2010

  10. Results Fig. 5 Installation - Main control valve with DN600 with a bypass line Effects • Reduction: • Water loss reduction 1,2 mln m3/ per year • Number of accidents by 50% • Investment recovery period - 1 year

  11. CONCLUSIONS • Pressure control is a relatively efficient way to reduce water losses and especially the number of accidents. • Investment recovery period for pressure regulating is very short (from a few months to 1 year). • Reduction of water losses by pressure control has a multiplier effect. It reduces operational costs and investments for new pipelines, pumping stations, treatment plants, and natural wastewater.

  12. Thank you for your attention! for questions and contact: Prof. Dr. Dipl.-Eng. GantchoDimitrov E-Mail: info@wato.bg Mobile: +359 888 305525 Web: www.WATO.bg