1 / 39

CLASSIC ACOUSTICS AND TOA PRESENTS THE VENAS VOICE EVACUATION SYSTEM

CLASSIC ACOUSTICS AND TOA PRESENTS THE VENAS VOICE EVACUATION SYSTEM. VM-2000. VM-2120, VM-2240 Mixer Amplifier. Features & Functions. General Features 1. INPUTS: 2 BGM Inputs 3 Mic/Line Inputs 1 Telephone Input Remote Microphone Input (for up to 4 RM-200M) 100V Speaker Line

olive
Télécharger la présentation

CLASSIC ACOUSTICS AND TOA PRESENTS THE VENAS VOICE EVACUATION SYSTEM

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. CLASSIC ACOUSTICS AND TOA PRESENTS THE VENAS VOICE EVACUATION SYSTEM

  2. VM-2000 VM-2120, VM-2240 • Mixer Amplifier Features & Functions

  3. General Features 1 INPUTS: • 2 BGM Inputs • 3 Mic/Line Inputs • 1 Telephone Input • Remote Microphone Input (for up to 4 RM-200M) • 100V Speaker Line • Power Amplifier Input

  4. General Features 2 OUTPUTS: • Speaker Line Outputs: • 120W: VM-2120, 240W: VM-2240 • 100 volts (70 or 50 volt by simple modification) • 1 Direct • 5 Zones (with ON/OFF Switch and Attenuator) • (50V and 70V can be achieved by internal re-wiring) • 1 Line Output pre-master • 1 Line Output post-master • 1 Recording Output

  5. General Features 3 • 5 priority levels are provided: • Emergency: highest priority • 4 priority levels (1 - 4) • Remote-Controlled Power-ON • the VM is always in stand-by mode, to be switched on by external equipment (e.g. central system in emergency case) • Emergency Power (24V DC) Inlet • Cascading 9 VM-2000 • 9 VM-2000 can be combined to obtain up to45 zones and more output power

  6. General Features 4 • Optional Surveillance Functions: • Monitoring • Speaker Line • Amplifier • CPU • the Communication with Remote Microphone • Failure Indication on Remote Microphone and VM • Optional Voice Message Functions: • 7 Messages • 5 for commercial purpose • 2 for emergency purpose • 1 Chime

  7. Emergency and Fault Indication LED Level meter Mic/Line Inputs Master volume Zone buttons Power switch(stand-by) BGM Inputs Zone Attenuators All-call button Appearance Front Emergency and Fault Indication LED Emergency and Fault Indication LED Emergency and Fault Indication LED Emergency and Fault Indication LED EMERGENCY FAULT

  8. Line inputs+ outputs Surveillancemodule BGM inputs w. level Voice message module AC mains 24V DC Mic/lineinputs Link remote mics, VM Speakerconnector Control I/O Telephone input,priority control in Volume telephone, chime, remote mic Setting DIPswitches Appearance Rear

  9. TREBLE BASS BGM BGM Inputs 2 BGM Inputs • 2 RCA/Cinch connectors (Stereo  Mono) • 2 attenuator for each channel (pre-adjustment) • Volume, bass & treble control • Mute-level can be set: • -∞∞, -28, 0 dB: to allow just mixing, keeping BGM present during paging or to switch off • BGM has always lowest priority (priority level 4) • Assignment to Zones • The BGM signal can be routed to the zones selected by the front panel’s zone switches

  10. Control inputs on clamp terminal Inputs 1-3 (1) 3 MIC/LINE Inputs (Inputs 1~3) • combined XLR / phone jacks, balanced • Input 1 with additional DIN jack • control input included • Volume, bass & treble control • Selectable sensivity: • microphone (-60 dBV) or line signal (-10 dBV • Phantom power: • can be switched on or off for all simultaneously when set to microphone sensivity Rear

  11. Inputs 1-3 (2) Control Settings • Selectable priority: • When using control inputs: priority level 1 or 2 can be selected • When not using control inputs: priority level 3 is provided • Channels of the same priority level, can be set either to Last-in-first-out (LIFO) or first-in-first-out (FIFO) • Assignment to Zones • - in priority level 1 or 2, the inputs can be assigned to certain zones • - in priority level 3, the inputs will be routed to the zones selected by the front panel’s zone switches • Mixing • In priority level 2, mixing can be selected • In priority level 3, mixing is provided • Pre-Announcement Chime • Priority level 1 and 2 provide automatic pre-chime • On input 3, the pre-chime can be switched off PCB

  12. Telephone Input 1 Telephone Input • Push-in terminal block (balanced) with control input • Sensivity: -10 dBV • Connection to a PABX system with an audio output and control signal output • Priority level 1 or 2 • Pre-announcement chime • can be set ON or OFF Rear PCB

  13. VM-2000 (master) RJ45 Remote Microphone RM-200M Connection of up to 4 remote microphones • parallel connection in „daisy chain“ • using RJ45 connectors and category 5 cables (4 pairs with shield) * external power supply necessary for more than 1 remote microphone(AD-4800 ER, part code 100-07-291-80)

  14. External Speaker Input 1 External Speaker input • on push-in screw terminal • to switch the connected speakers to an external power amplifier • e.g. to connect the speakers to a central system • e.g. to connect the speakers to a stand-by amplifier in case of amplifier failure • the external signal will be switched directly to the speaker lines • the attenuators will be bypassed Rear

  15. Line Level Outputs 3 Line Level Outputs • Recording Output • pre-master, for recording independent of master volume, level: 0 dBV • Line Output • pre-master, for connecting additional amplifiers without master volume control of VM , level: 0 dBV • Pre (amplifier) Output • post-master, for connecting additional amplifiers with master volume control on VM, or to connect the slave VM, level: 0 dBV Rear

  16. Speaker Line Outputs 1 Direct and 5 Zone Outputs • Plug-in screw connector • for easy connection and maintenance • Output level: 100V • 70V and 50V by internal re-wiring • direct output without attenuator • zone outputs with attenuators • 6 steps: -20, -15, -10, -6, -3, 0 dB • Attenuator control output • to bypass external attenuators Rear

  17. > 100 ms Control I/O Port: Inputs (1) Remote Control by external Equipment or Switches (manual control): • Activation will be made by closing or opening a contact • in some cases a control can be activated by a pulse • in other cases a control can be activated with a level signal break make Rear

  18. OFF ON pre-chime post-chime Control I/O Port: Inputs (2) Remote Control by external Equipment or Switches (manual control): • Switching ON and OFF the VM • Start/Stop of Emergency mode • Activation of external speaker signal input • Start pre-recorded messages (if EV-200 installed) • Chime activation • Westminster chime activation • (external) Fault (to be indicated on the fault LED)

  19. Control I/O Port: Outputs Remote Control of external Equipment or Indicators (LED, buzzer) • AC mains failure • DC failure • Power status • Communication (with remote microphone) fault • General Fault • Emergency mode active • EV-200 fault (when EV-200 installed)

  20. Combination of 9 VM‘s Nine VM-2000s can be combined • to increase the output power • to increase the number of zones up to 45 • one unit will be master, the others all slaves • the voice announcement module needs to be installed only in the master unit • the remote microphone(s) will be connected to the master unit only • Full access to each desired zone of the slave units through the master unit

  21. VM-2000 + RM-200M + EV200: 5-zone system with 5-voice message VM-2000 + RM-200M: 5-zone system VM-2000 + VM-2000 + RM-200M: 10-zone system 2x VM-2000 + RM-200M + RM-210 + EV-200: 10-zone system with 5-voice message EV-200 EV-200 Combinations

  22. Priorities • Absolute Priority • 5 priority levels are provided: • Emergency: highest priority • 4 priority levels (1 - 4) • Relative Priority • when inputs of the same priority level (1 or 2) are activated at the same time, valid for all inputs with control • last-in-first-out (LIFO) and first-in-first-out (FIFO) • unit no. Priority only for RM-200M and messages 1 - 5 • Mixing • in priority level 2: “priority 2 mixing” is set • in priority level 3

  23. Priority: Audio Output Levels • Audio Levels at different Priority Levels • Emergency : max. level at speaker • bypass of master volume and zone attenuators, activation of external attenuator control • priority level 1 & 2: max. level output XXX • bypass of master volume and zone attenuators • when “priority 2” is set to “mixing”: no bypass of master volume and zone attenuators for inputs of priority level 2 • priority levels 3 and 4: level as set • no bypass of master volume and zone attenuators

  24. Emergency • The VM-2000 is a package amplifier providing VA (Voice Alarm) functions • So, it can be set into the Emergency Mode by: • depressing the remote microphones emergency key • external control: • - starting the ALERT function • - starting the EVACUATION function • The Emergency mode can be stopped only by external control ! • To avoid switching off easily

  25. RM-200M Remote Microphone

  26. Features of the RM-200M • Elegant and modern design, slink gooseneck microphone • selection for up to 10 zones • Two group selection buttons • All-call selection button • talk button in PTT or ON/OFF mode • protected emergency button, starting evacuation sequence • pre- and post-announcement chime selectable • Start of 5 pre-recorded messages • key extension RM-210 available • up to 4 remote microphones can be connected

  27. Labels: can be inserted under the surface Zone / messageindication Zone / messageselector key Power indicator Failure indicator A C Emergency indicator Emergency key Group 1 key Group 1 indicator B Group 2 key Group 2 indicator All-call key All-call indicator d d RM-200M RM-210 In-use indicator Busy indicator: Talk button Appearance Top (1) Remote microphone RM-200M Key extension RM-210 Flashing green: RM-200M can interrupt the busy unit Flashing orange: RM-200M can not operate

  28. C:when using EV-200 and two VM-2000 :message selector A: always zone 1-5 selection A C B:when using EV-200:message 1-5 selector, when using two VM-2000:zone 6-10 selection B d d RM-200M RM-210 Appearance Top (2)

  29. Extensionconnector Function setting switch EXTERNALMIC IN LINK SP MIC DC POWER IN24V - 200 mA DC powerinput jack RJ45 linkconnector External microphone input jack Microphone volume control Appearance Rear & Side • Connectors and Adjustment

  30. Linkage RM-200M and RM-210 • Bottom side Turn the bottom up Connect the link cable fix the linkage bracket B fix the linkage bracket A

  31. Mounting in Desk Prepare a hole Place in the remote microphone Fix the RM with screwsfrom the bottom side

  32. SV-200 Surveillance Board

  33. Features • Monitoring of • speaker lines on • short circuit • break • earth leakage • power amplifier on proper operation • Output of detected failures • on the VM-2000 • on the remote microphone(s) RM-200M • on output connector

  34. SURVEILLANCE I/O SP LINEIMPEDANCE SET CHECK Appearance SET button: after connecting the speakers, depress here for initial measurement CHECK button: manual start of measuring to check the speaker lines

  35. EV-200 Voice Announcement Board

  36. Features Playback of pre-recorded messages • 2 Emergency messages • 5 commercial messages • 1 chime • control via remote microphone or by external equipment (e.g. timer) • sound files on compact flash memory card • message length depends only on the card‘s size • recording and editing of the messages on EV-350

  37. CPU RUN COMPACTFLASH CARD ACCESS Appearance • CPU Status Indicator CPU status indicator Eject button Card access indicator CF card slot volume control • Card Access Indicator normal operation: flashes Card access: flashes abnormal operation: steadily on failure: steadily on no operation: extinguished

  38. Memory Card In EV-200 usable memory cards: Type: CompactFlash cards model: SDCFB-8/-16/-32/-48/-64/-96 manufacturer: SanDisk capacity: 8 MB - 96 MB for recording with EV-350R: CF-adapter(e.g. SanDisk type SDCF-03)

  39. THANK YOU