1 / 15

Advanced Direct Evaporative Pre-Cooling for Air Cooled Condensers (DEPACC)

Advanced Direct Evaporative Pre-Cooling for Air Cooled Condensers (DEPACC). Program Overview Technology Overview Energy Savings Customer Benefits. What is DEPACC? – Program Overview.

quito
Télécharger la présentation

Advanced Direct Evaporative Pre-Cooling for Air Cooled Condensers (DEPACC)

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Advanced Direct Evaporative Pre-Cooling for Air Cooled Condensers (DEPACC) Program Overview Technology Overview Energy Savings Customer Benefits

  2. What is DEPACC? – Program Overview • Technology: Direct Evaporative Pre-Cooling for Air Cooled Condensers used with unitary DX air conditioning equipment, typically RTUs • New for 2014 – All Air-cooled Chillers • Program: Prescriptive incentive program to increase the adoption of evaporative pre-condensing as a retrofit measure • Part of the existing Xcel Cooling Efficiency Program • Preapproval is not required • Any nonresidential • Dedicated data centers must apply through custom process • Minimal system size is 10 tons • Incentive is $100/ton

  3. DEPACC – Technology Overview • Evaporative pre-cooling: • Cools hot outside air before cooling the condenser coils • AC system operates as if it were 20O or more cooler at the coil than ambient dry bulb • Typical results in 15 – 30% improvement in cooling energy efficiency

  4. Two Types of Systems Mist with saturated membrane – no sump or recirculation Saturated membrane with sump and recirculation

  5. Qualified Solutions Once Through Systems Recirculation Systems 5

  6. System Providers & Installations Dual Cool by Integrated Comfort Inc., distributed by ATEC/Indirex HydrEVAP by RCF Inc., distributed by ATEC/Indirex Smart Mist by Cloudburst EVAPORCOOL by Evaporcool Inc. distributed by Evaporcool

  7. Program Eligibility Requirements • DX RTU and Air-Cooled Chillers • System Size not less than 10 tons cooling capacity • Evaporative pre-condensing system must provide a minimum of 75% temperature reduction of the potential total wet bulb depression available at all ambient conditions when the compressor operates. • DEPACC system shall be configured such that no water mist or spray to contact or accumulate on the condenser coils. • DEPACC system must include a mechanical or chemical water treatment system to prevent scaling • System should be equipped with controls that limit water use • Dedicated data center facilities are ineligible as prescriptive measure and must use Xcel custom measure process

  8. Targeted Building Types • Program Savings per ton of cooling are correlated with building use type and location • Hospitals, Lodging & Offices yield highest savings

  9. Targeted Equipment – RTUs Key Variables • Water available on the roof • Size of the equipment • Roof accessibility for contractor Larger Systems are somewhat better • Installed cost per unit diminishes as system size increases

  10. Breadth of Energy Bill Savings • Cost Savings: • $44 to $115 / ton annual savings • Simple Payback: • Less than 2 years

  11. Representative Project Energy Savings Denver Office Building 150,000 sf 320 tons Cooling (4-80 ton RTU’s) Peak Summer Week 40% Cooling Energy Savings Annual 19% Cooling Energy Savings 2,400 kWh / week average

  12. Representative Project Energy Savings Denver Office Building 150,000 sf 320 tons Cooling (4-80 ton RTU’s) Peak Summer Week 15% Total Building Energy Savings Annual 4% Total Building Energy Savings 2,400 kWh / week average Savings

  13. What are the Customer Benefits? • DEPACC program can deliver good ROI and reliable savings • Typical 1-2 YR Simple Paybacks • Proven improvements in Air Conditioner performance • Cooler low side temperatures which allow for colder conditioned air • Reduce energy consumption 15-20% • Reduce energy peak demand typically 15-35% • Help protect coils from damage and debris build-up • Simplifies & Reduces condenser coil cleaning • Enhances life of the DX unit • Reducing head pressure • Protects contamination of condenser coils • Can reduce the need for over-designing new and existing building

  14. Project Scoping Initial Customer Qualification Screen: • System equal to or larger than nominal 10 tons of cooling • Building type and location Project Delivery • Customer or HVAC Service Contractor obtain equipment information • Contact DEPACC system provider for equipment pricing • Utility bill records & tariff information if available • Prepare Economic ProForma: Energy at Risk or other tool • Execute Installation Contract & submit for rebate • Contact Cypress for assistance

  15. Contact Us www.precoolandsave.com DEPACCsupport@cyp-res.com (877) 811-8700