Understanding HVAC Fundamentals: Psychrometrics, Heat Transfer, and Energy Efficiency
This homework assignment delves into critical HVAC concepts, focusing on psychrometrics, heat transfer, and energy efficiency. Students will review both sensible and latent heat, explore the thermal comfort represented in psychrometric charts, and calculate heat loss and gain due to conduction. The assignment involves practical scenarios, such as the effects of air conditioning on humidity levels and the calculation of heating and cooling loads essential for building energy efficiency. Emphasis will be placed on using equations for air transport and understanding the implications for sustainability.
Understanding HVAC Fundamentals: Psychrometrics, Heat Transfer, and Energy Efficiency
E N D
Presentation Transcript
Homework 1 • Interest - HVAC • Lighting • Electrical • Sustainability • Acoustics • Concerns
Objectives • Review Psychrometrics • Sensible and latent heat • Define thermal comfort in Psychrometric chart • Equations for energy transport by air • Calculate heat loss and gain due to conduction • Use knowledge of heat transfer to calculate heating and cooling loads
Which situation has highest RH? • Summer day in Austin, TX • Winter day in Aspen, CO • The air downstream of a cooling coil • Summer day in Seattle, WA
Sensible vs. Latent Heat latent sensible
Changing the mass of water in an air sample always • Causes you to move vertically on the psychrometric chart • Changes the absolute humidity of the sample • Changes the relative humidity of the sample • Causes you to move horizontally on the psychrometric chart • A. and B.
Example Cooling with a oversized air conditioner • How much moisture is removed? • A central air conditioner fan blows 1500 CFM of 80 °F air @ 50 % RH through a coil. • The thermostat is satisfied when the air coming off the coil reaches 65 °F.
If you know the dew point temperature (td) and the dry bulb temperature (t) for a sample of air • You can’t get the statepoint because the problem is overspecified (you know the RH = 100%, t and td). • You get the state point by the intersection of the t and td lines. • You get the state point by moving horizontally from td until you intersect the t line • You get the state point by moving vertically from td until you intersect the t line
Examples: 1) You heat one pounds of air air A (T=50F, W=0.009 lbW/lbDA) to point T=80F and humidify it to RH 70%. What is the sensible, latent and total heat added to the one pound of air. 2) One pound of air D(T=90F, RH=30%) is humidified by adiabatic humidifier to 90% relative humidity. What is the temperature at the end of humidification process and how much water is added to the air.
Psychrometric Chart • Make sure chart is appropriate for your environment • Figure out what two quantities you know • Understand their slopes on the chart • Find the intersection • Watch for saturation
Homework Assignment 2 • Use the psychrometric chart • Pay attention to units in calculations • Values for Δh and Δw per mass unit of dry air • Differences in nomenclature
Equations for sensible energy transport by air • Energy per unit of mass Δhsensible = cp×ΔT [Btu/lb] cp - specific heat for air (for air 0.24 Btu/lb°F) • Heat transfer (rate) Qs = m × cp×ΔT [Btu/h] m - mass flow rate [lb/min, lb/h], m = V ×r V – volume flow rate [ft3/min or CFM] r – airdensity (0.076lb/ft3) Qs = 1.1 × CFM ×ΔT (only for IP unit system)
Equations for latent energy transport by air • Energy per unit of mass Δhlatent = Δw×hfg[Btu/lbda] hfg - specific energy of water phase change (1000 Btu/lbw) • Heat transfer (rate) Ql = m ×Δw×hfg [Btu/h] Ql = 1000 × WaterFloowRate (only for IP units)
Total energy transport calculation using enthalpies from chat • Energy per unit of mass Δh=h1-h2[Btu/lbda] • Heat transfer (rate) Qtotal = m ×Δh[Btu/h] Qtotal = Qsensible + Qlatent
Why do we calculate heating and cooling loads? Heating and Cooling Loads • To estimate amount of energy used for heating and cooling by a building • To size heating and cooling equipment for a building • Because my supervisor request that
Introduction to Heat Transfer • Conduction • Components • Convection • Air flows (sensible and latent) • Radiation • Solar gains (cooling only) • Increased conduction (cooling only) • Phase change • Water vapor/steam • Internal gains (cooling only) • Sensible and latent
1-D Conduction l k A 90 °F 70 °F U U-Value[W/(m2 °C)] U = k/l k conductivity [W/(m °C)] l length [m] Q heat transfer rate [W] ΔT temperature difference [°C] A surface area [m2] Q = UAΔT
Material k Values 1At 300 K Table 2-3Tao and Janis (k=λ) values in [Btu in/(h ft2 F)]
Wall assembly l1 l2 • R = l/k • Q = (A/Rtotal)ΔT • Add resistances in series • Add U-values in parallel k1 k2 90 °F 70 °F R1 R2 Tout Tmid Tin
Surface Air Film h - convection coefficient - surface conductance [W/m2, Btu/(h ft2)] • Direction/orientation • Air speed • Table 2-5 Tao and Janis Tout Tin Rsurface= 1/h Ri Ro R1 R2 Rtotal= ΣRi Tout Tin
What if more than one surface? l1 l2 k1, A1 k2, A2 Qtotal = Q1,2 + Q3 Q1,2 A2 = A1 U1,2 = 1/R 1,2=1/(R1+R2) k3, A3 Q1,2 = A1U1,2ΔT Q3 Q3 = A3U3ΔT l3
Relationship between temperature and heat loss U1A1 U2A2 U3(A3+A5) U4A4 U5A5 A2 A3 A1 A4 Tin Tout A5 A6 Qtotal= Σ(UiAi)·ΔT
Which of the following statements about a material is true? • A high U-value is a good insulator, and a high R-value is a good conductor. • A high U-value is a good conductor, and a high R-value is a good insulator. • A high U-value is a good insulator, and a high R-value is a good insulator. • A high U-value is a good conductor, and a high R-value is a good conductor.
Example • Consider a 1 ft × 1 ft × 1 ft box • Two of the sides are 2” thick extruded expanded polystyrene foam • The other four sides are 2” thick plywood • The inside of the box needs to be maintained at 120 °F • The air around the box is still and at 80 °F • How much heating do you need?
The Moral of the Story • Calculate R-values for each series path • Convert them to U-values • Find the appropriate area for each U-value • Multiply U-valuei by Areai • Sum UAi • Calculate Q = Σ(UAi)ΔT
Heat transfer in the building Not only conduction and convection !
Infiltration • Air transport Sensible energy Previously defined • Q = m× cp × ΔT [BTU/hr, W] • ΔT= T indoor – T outdoor • or Q = 1.1BTU/(hr CFM °F)× V × ΔT [BTU/hr]
Latent Infiltration and Ventilation • Can either track enthalpy and temperature and separate latent and sensible later: • Q total= m× Δh [BTU/hr, W] • Q latent = Q total - Q sensible = m× Δh - m× cp × ΔT • Or, track humidity ratio: • Q latent = m× Δw ×hfg
Ventilation Example • Supply 500 CFM of outside air to our classroom • Outside 90 °F 61% RH • Inside 75 °F 40% RH • What is the latent load from ventilation? • Q latent = m×hfg× Δw • Q = ρ × V×hfg× Δw • Q = 0.076 lbair/ft3 × 500 ft3/min × 1076 BTU/lb × (0.01867 lbH2O/lbair - .00759 lbH2O/lbair) × 60 min/hr • Q = 26.3 kBTU/hr
What is the difference between ventilation and infiltration? • Ventilation refers to the total amount of air entering a space, and infiltration refers only to air that unintentionally enters. • Ventilation is intended air entry into a space. Infiltration is unintended air entry. • Infiltration is uncontrolled ventilation.
Where do you get information about amount of ventilation required? • ASHRAE Standard 62 • Table 2 • Hotly debated – many addenda and changes • Tao and Janis Table 2.9A
Ground Contact • Receives less attention: • 3-D conduction problem • Ground temperature is often much closer to indoor air temperature • Use F- value for slab floor [BTU/(hr °F ft)] • Note different units from U-value • Multiply by slab edge length • Add to ΣUA • Still need to include basement wall area • Tao and Janis Tables 2.10 and 2.11 More details in ASHRAE handbook -Chapter 29
Conclusions • Conduction and convection principles can be used to calculate heat loss for individual components • Convection principles used to account for infiltration and ventilation • Readings: Tao and Janis 2.4-2.6.4