1 / 19

- teknologi

- teknologi. PROFIBUS protokollene Kabling Installasjon, DP- and PA-noder Datarepresentasjon på bussen Utveksling av data, master / slave Syklustid, DP Mono-master-system Konfigurering GSD : Elektronisk datablad. Layer. Bruker. Applikasjon. (7). (3)-(6). Fieldbus Data Link (FDL).

roger
Télécharger la présentation

- teknologi

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. - teknologi PROFIBUS protokollene Kabling Installasjon, DP- and PA-noder Datarepresentasjon på bussen Utveksling av data, master / slave Syklustid, DP Mono-master-system Konfigurering GSD : Elektronisk datablad

  2. Layer Bruker Applikasjon (7) (3)-(6) Fieldbus Data Link (FDL) Data Link IEC grensesnitt* (2) Fysisk RS-485 / Fiberoptikk IEC 61158-2 (1) PROFIBUS protokollene FMS DP PA Applikasjonaprofiler DP-Funksjoner Fieldbus Message Specification (FMS) Ikke brukt DIN E 19245 partl 4 EN 50 170 PROFIBUS guidelines

  3. Kabel 2 ledere skjerm

  4. Pinnetilordning

  5. 390  RxD/TxD-P (3) (3) RxD/TxD-P DGND (5) (5) DGND 220  VP (6) (6) VP RxD/TxD-N (8) (8) RxD/TxD-N 390  Terminering, RS485 VP (6) Station 1 Station 2 Data line B RxD/TxD-P (3) Data line A RxD/TxD-N (8) Shield DGND (5)

  6. 390  390  220  220  390  390  Installasjon, DP-noder Første stasjon Siste stasjon Bussterminering Bussterminering VP VP Datalinje B B B Datalinje A A A DGND DGND A B A B B A B A Stasjon 2 Stasjon 3

  7. Installasjon, PA-noder Buss- terminering Buss- terminering Spenningstilførsel 100 100 1 F 1 F Maks 32 PA-stasjoner ……

  8. LSB MSB LSB Den minste data-pakke OCTET 1. octet 2. octet Idle Start 1 2 3 4 5 6 7 8 Parity Stop Start Bit sequense:

  9. bit 6 bit 2 bit 4 DatarepresentasjonIEC – 6 1158-2 (PA) 0 1 0 1 1 1 I0+9mA I0 I0-9mA t bit 1 bit 3 bit 5

  10. Stasjoner, repeatere og segmenter Terminering Terminering Repeater Stasjon 1 2 3 30 31 Terminering Repeater 33 32 62 61

  11. Token ring Logiskl token ring Aktive stasjoner, MASTERE PC PLC PLC PROFIBUS Passive stasjoner , SLAVER

  12. DP-Slave DP-Slave Utveksling av data, master/slave Request Slave  Master DP-Master Data Data Master  Slave DP-Master Status

  13. SD4 DA SA SD1 DA SA FC FCS ED De 3 vanligste PROFIBUS-telegrammene SDx = Start Delimiter x DA = Destination Address SA = Source Address FC = Function Code FCS = Frame Check Sequence ED = End Delimiter LE = Length LEr = Repeated Length DSAP = Destination Service Access Point SSAP = Source Service Access Point DU = Data Unit 1.) Token Passing 2.) FDL Status Request Telegram 3.) Data Telegram SD2 LE LEr SD2 DA SA FC DSAP SSAP DU FCS ED Head Tale

  14. Datatransmisjon ved 1.5 MBaud Tbit = transmisjonstid for 1 bit = 0.6667s OCTET : 11 Tbit = 7.3 s Token Passing : 33 Tbit = 22 s Status / Request : 66 Tbit = 44 s Data : Head (9 octets) + Tale (2 octets) + Data (n octets) 2 bytes data : 13 x 11 Tbit = 143 Tbit = 95.3 s • ” Idle time ” for master : typisk 75 Tbit = 50 s • ” Station delay time ” for slave : typisk 11 Tbit = 7.3 s • Totalt, 2 bytes data : (33+66+143+75+11)Tbit = 0.219 ms

  15. Syklustid, DP Mono-master-system Buss syklustid [ms] Hver slave : 2 bytes inn / 2 bytes ut 500 kBit/s 1.5 MBit/s 12 MBit/s Antall slaver

  16. Systemkonfigurering GSD GSD GSD GSD GSD GSD PROFIBUS Konfigurering PROFIBUS Konfigureringsprogram Electronisk datablad (GSD - filer) PLS PLC

  17. GSD-fil (WINblock stasjon) ; WIWB0250.GSD ; Geraetestammdatei fuer PROFIBUS DP WINbloc 8 DI P ; Art.No. 827516 ; Weidmueller GmbH + Co, Postfach 2807, 33058Paderborn ; Serviceline 05252 960-555, Fax 05252 960116 ; Mailbox GSD, Siemens Typdateien: 05231 141555 ; Name:Gast kein Password ; ; Version: 1.6 Stand: 10.6.97 Km ;================================ ; #Profibus_DP GSD_Revision = 1 Vendor_Name = "Weidmueller Interface" Model_Name = "WINbloc 8DI" Revision = "V1.6" Ident_Number = 0x250 ;

  18. GSD-filforts. Protocol_Ident = 0 Station_Type = 0 FMS_supp = 0 Hardware_Release = "Ver.4" Software_Release = "00" ; 9.6_supp = 1 19.2_supp = 1 O.s.v 12M_supp = 1 ; MaxTsdr_9.6 = 60 MaxTsdr_19.2 = 60 O.s.v MaxTsdr_12M = 800 ; Redundancy = 0 Repeater_Ctrl_Sig = 2 24V_Pins = 0 ; Implementation_Type = "LSPM2" Bitmap_Device = "winblocn" Bitmap_Diag = "winblocs" ;

  19. GSD-fil forts. ; Slavespezifische Werte ; OrderNumber = "827516" Periphery = "WINbloc" Freeze_Mode_supp = 1 Sync_Mode_supp = 1 Auto_Baud_supp = 1 Set_Slave_Add_supp = 0 Min_Slave_Intervall = 1 Modular_Station = 0 Modul_Offset = 0 Fail_Safe = 0 Slave_Family = 3@TdF@WINbloc ; Max_Diag_Data_Len = 13 User_Prm_Data_Len = 0x05 User_Prm_Data = 0x00,0x00,0x00,0x00,0x00 Module = "DP-Kompaktgeraet 8 I" 0x00,0x10 EndModule

More Related