1 / 29

4 th Quarter 2013 Transmission Stakeholder Planning Meeting

4 th Quarter 2013 Transmission Stakeholder Planning Meeting. Reno, NV December 18, 2013. Transmission Stakeholder Planning Input Meeting. Agenda Regulatory Filings Update Integrated Resource Plan Update SB 123- NVision Stakeholder Input. Regulatory Filings Update One Company Filing

sean-fox
Télécharger la présentation

4 th Quarter 2013 Transmission Stakeholder Planning Meeting

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 4th Quarter 2013 Transmission Stakeholder Planning Meeting Reno, NV December 18, 2013

  2. Transmission Stakeholder Planning Input Meeting • Agenda • Regulatory Filings Update • Integrated Resource Plan Update • SB 123- NVision • Stakeholder Input

  3. Regulatory Filings Update One Company Filing One Company Rate Case Tariff Changes NPC Rate Case Settlement FERC Order 1000

  4. One Company Filing Docket EC13-113 • NVE filed an Application For Approval of Internal Reorganization May 31, 2013 • Sierra Pacific to merge into Nevada Power. • The surviving entity will be renamed NV Energy Operating Company. • The transaction to be effective January 1, 2014 or the in-service date of ON Line. • FERC issued an order on November 26, 2013 authorizing the transaction.

  5. Combined FERC Rate CaseSummary: Docket ER13-1605 • NVE filed a combined rate case May 31, • One set of rates for NV Energy Operating Company (the combined company) • ON Line costs included • Expected completion – December 2013 • Rates effective January 1, 2014 • Transmission and NITS rate to be $3.57 per kW month • ROE – 10.50% • Loss for combined BAA updated 1.57% • Updated rates for Sch. 1, 2, 3, 5, 6, 7, 8, 11 & NITS

  6. FERC Rate Case Summary (Cont.) • The case is currently in settlement proceedings at FERC. • Next settlement conference is scheduled for Thursday, January 16, 2014 at FERC.

  7. Tariff ChangesDocket ER13-1607 • Tariff for NV Energy Operating Company requested to be effective Jan. 1, 2014 • Tariff updated to reflect one BAA (SPPC / NEVP to be combined to NVE on 1/1/14)

  8. NPC FERC Rate Case Summary Docket ER13-255 • NPC filed a stand-alone rate case October 31, 2012. • On December 31, 2012 FERC accepted the filing and suspended the rates for five months to be effective June 1, 2013. • The December 31, 2012 order also established hearing and settlement judge proceedings. • Settlement was reached and NPC filed the settlement November 27, 2013. • On December 5, 2013 the Chief Judge granted a Motion for Interim Rate Relief effective November 1, 2013.

  9. ER13-255 Settlement Rates

  10. FERC Order 1000 • On July 21, 2011, the Federal Energy Regulatory Commission (“FERC”) issued Order No. 1000, Transmission Planning and Cost Allocation by Transmission Owning and Operating Public Utilities (“Order 1000”), which became effective on October 11, 2011 • Four areas of reform: • Regional transmission planning • Interregional transmission planning coordination • Right of First Refusal (ROFR) – N/A to Nevada • Cost Allocation

  11. FERC Order 1000 Planning Requirements • Public Utility Transmission Providers (“TPs”) required to participate in a regional planning process that satisfies Order 890 principles (coordination, openness, transparency, information exchange, comparability, dispute resolution and economic planning) and produces a regional transmission plan • Each region to produce a regional plan reflecting solutions that meet the region’s needs more efficiently or cost effectively • Local and Regional transmission planning processes must consider transmission needs driven by “Public Policy Requirements” established by state or federal laws or regulations • TPs in each pair of neighboring planning regions must coordinate to determine if more efficient or cost-effective solutions are available

  12. What Order No. 1000 Does Not Require • Order is process, not outcome, oriented • FERC did not prescribe the exact manner for public utilities to develop the regional transmission planning process, but rather only set forth principles for public utilities, in consultation with stakeholders, to develop a transmission planning process for their regions (P157) • FERC did not require that the regional transmission planning process create/establish obligations to build or commitments to construct transmission facilities – rather Order 1000 simply sets forth principles public utilities need to consider in developing a regional transmission planning process (P159)

  13. FERC Order on WestConnect Compliance Filing issued March 22, 2013 • FERC concluded that the WestConnect filing partially complied with the requirements of Order No. 1000and directed further compliance filings: • State that WestConnect has an obligation to identify transmission solutions in the regional transmission planning process that more efficiently or cost-effectively meet transmission needs • Address Order No. 1000’s requirement to consider transmission needs driven by public policy requirements • Provide that regional cost allocations are binding on identified beneficiaries.

  14. Integrated Resource Plan (IRP) Status

  15. Nevada Power Company Load Forecast

  16. Sierra Pacific Power Company Load Forecast

  17. 2013 Actual vs Forecast System Peak Load

  18. Nevada Power Company Integrated Resource Plan (IRP) Status • 2012 IRP filed June 2012 (Docket 12-06053) • Planning period: 2013 – 2032 • PUCN Final Order December 24, 2012 • PUCN approval was not requested for any new transmission projects

  19. Nevada Power IRP Transmission Projects ON Line Transmission Project

  20. ON Line versus Major WECC Paths

  21. On-Line Project • SCOPE • 235-mile 500 kV transmission line Robinson-Harry Allen • Robinson Summit 500/345 kV substation • Falcon-Gonder Fold • Series compensation on the existing Falcon – Gonder 345 kV line • Harry Allen Terminal • SPPC and NPC Balancing areas will be consolidated post ON- Line • Budget revised from $510 million to $552 million • In-service date of the project has been delayed to December 31, 2013

  22. Sierra Pacific Power Company Integrated Resource Plan (IRP) Status • 2013 IRP filed July 1, 2013 (Docket 13-07005) • Planning period: 2014 – 2033 • Requested approval for new transmission projects

  23. Sierra IRP Project Status Cont. Bordertown to Cal Sub 120 kV Line • The project was approved by the PUCN in 2007 and includes the construction of a 345/120 kV transformer at Bordertown Substation and a new 120 kV line from Bordertown substation to California Substation. • Project would provide additional transmission support to the West Reno transmission system for outages of a North Valley Road transformer and N-1-1 outages of the 120 kV transmission system. • To date Sierra has not obtained the required permits for this line and permitting work is continuing. The in-service date for this project has been moved from 2012 to 2016.

  24. Sierra IRP Project Status Cont. 345 KV Voltage Support Project • Add 75 MVA 345 kV capacitor bank at North Valley Road substation and Mira Loma substation • Mira Loma in service date is December 2013 • Valley Road in service date is February 2014

  25. Sierra IRP Project Status Cont. Hycroft Mine Load Addition / Oreana 345/120 kV Substation • New 345/120 kV substation with a 280 MVA transformer • Expand existing Dun Glen Switching Station • Rebuild 119 & 162 lines to Bundled 954 ACSR for approx. 34 miles • Install approx. 48 miles of new Bundled 954 ACSR 120 kV line • Install a new 20 MVar Capacitor banks at Dun Glen and Hycroft

  26. Sierra IRP Project Status Cont. Carlin Trend Master Plan • Carlin Trend Under Voltage Load Shedding Scheme • Second Falcon 345/120 kV Transformer • Coyote Creek 120 kV Breaker Addition • Carlin Trend Transmission Additions

  27. SB123: NVision • “Emission Reduction and Capacity Replacement Plan” • Requires NVE-South to retire or eliminate 800 MW of coal by 2019 (Reid Gardner 1,2&3 2014, Reid Gardner 4 2017 and Navajo 2019) • Requires NVE to replace coal with company owned 550 MW of generation either constructed or acquired • Generation type not specified • Receive cost recovery for decommissioning costs • Consumer protection, cap on rates at 5%

  28. SB123: NVision • Requires annual RFPs for 100 MW of new renewables in 2014, 15, 16 • NVE can participate and compete in RFPs • Requires 50 MW of company-owned renewables to start construction by 2017 • Expect to file a Resource Plan Amendment with the PUCN in the Spring of 2014 with plan to comply with SB123 and required resource additions. • New generation additions may require additional transmission including the addition of the Harry Allen 230/500 kV transformer.

  29. Stakeholder Input- Questions