PV impacts on Suburban Networks LCNF Annual Conference - Cardiff Thursday 25th October 2012 Understanding Networks – an early presentation of data Philip Bale Western Power Distribution Innovation and Low Carbon Networks Engineer 01332 827448/07525241432 pbale@westernpower.co.uk
PV impacts on Suburban Networks Connection of Photo Voltaic Panels The Feed in Tariff resulted in a dramatic increase in the number of distribution network connected Solar PV panels. G83 connections This was particularly prevalent in particular suburban networks, expedited by Local Authorities installing generation on their housing stock Concern over the connection of PV generation to the LV network. The LV network has historically operated with very limited network monitoring and operates based on well known diversified load profiles. Significant amounts of PV in one area resulted in a increased number of assumptions being made. Number of connections
Network Monitoring • Monitoring in Nottingham • Aspley and Broxtowe – EDMI MK6E meters • Meadows – EMDI MK6E meters and portable sub.net monitors • Analysis - Does a high concentration of Solar PV have an impact on: • Network Voltage tolerances • Thermal Limits • Voltage Fluctuations and Flicker • Voltage and Current imbalance • Voltage and Current harmonics • Power Factor
Network Voltage tolerances Blue – LV busbar voltage Frinton Road Aspley, Red – 11kV Tx1 & Tx2 voltage Cinderhill Primary substation Voltage Voltage (kV) Time
Thermal Limits & Current Imbalance • Tunstall Crescent - Three Phase current over a two week period • Average current during the two week period • L1 – 68.96A • L2 – 99.12A • L3 – 125.89A Voltage Time
Voltage and Current harmonics Voltage and current waveforms The effect of current harmonics on the waveform
Voltage Total Harmonic Distortion Total Harmonic Voltage distortions – one week period of sites in Aspley and Broxtowe 8th - 14th October 2012 Frinton Road Tunstal Crescent Voltage Hilcot Drive Lindbridge Road Time
Contribution of Solar PV for demand Measured current - Blue Solar radiation - Red Estimated demand being masked by generation - Green Time
PV’s in Suburbia • Early Learning • Voltage profile at the substation • Current imbalance of network feeders • Current and Voltage Harmonics – including waveforms • Voltage harmonics – Total Harmonic Distortion • Contribution from Solar PV to demand