An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. MentePC สิงหาคม 2555

  2. MentePC 1. OVERVIEW 2. SPECIFICATIONS/WORKING ENVIRONMENT 3. INSTALLATION 4. MAIN FUNCTIONS 4-1 REAL TIME MONITORING 4-2 RECORDED DATA MONITORING 4-3 EEPROM DATA MONITORING 4-4 READING OF SAVED DATA DATA LOGGING 5. HOW TO USE “MentePC” 6. Abnormal cases during PC maintenance

  3. 1. Overview MentePC 1.1 This program is for monitoring the operation data from the outdoor unit by connecting the personal computer to the control PCB of KXE4/KXRE4, KXE6/KXRE6 and Inverter PAC outdoor unit and can save the data in a file (.csv). 1.2 What are the usage of MentePC in the field? (1) Testing/Commissioning : (a) To check the addresses of indoor units and outdoor combinations units. (b) To check the operation of outdoor unit (Temperature, pressure, current and etc.) (c) To check the operations of multiple indoor units (d) To judge if the system operation have passed the criteria of standard running operation (2) After sales servicing (a) To assist in troubleshooting irregular stop witherror codes (b) To assist and provide additional information to other claims without error codes

  4. MentePC 2. Specification/Working Environment 2.1 Communication Specifications: Interface : RS-232C (Cross Cable) Synchronized Method : Half-duplex asynchronous communication Transmission Speed : 19200 bps Data Format : Start bit 1 bit + data 8 bits + parity 1 bit (even) = stop bit 1 bit 2.2 Working Environment This program is created with Excel macros, and thus, will run only on a personal computer in which Microsoft Excel is installed. Operation has been confirmed with the following combination of PC, OS and Excel versions.

  5. MentePC 3. Installation • Execute “MentePC_V**.EXE” in a random folder. • The program will be automatically extracted and developedin the following manner. MentePC_V**. DATA DATA Conversion.xls (data conversion table) RAM DATA **** (Setting file for each model) MessageData (Multi languages DATA) MentePC_V**.xls(Execution file)

  6. MentePC 3. Installation Set the date for windows Select “Control Panel” >> “Regional Options” >> “Date” Change the date to “MM/dd/yyyy” with the “Short date format” under the Date setting. MM/dd/yyyy

  7. MentePC 3. Installation Set decimal point Note: If the decimal point is “,”(comma), MentePC can not read and write the Log Data files normally, because it can not distinguish the separator from the decimal point. Decimalpoint 『. 』 dot

  8. MentePC 3. Installation Date Format Compatibility: If the date format of the logged data does not match with PC setting, Excel can not recognise the date and can’t draw the graphs. In this case, check the date format of the logged data file and set “Regional Options” of PC format. Can’t draw the graphs. MM/dd/yyyy

  9. MentePC 3. Installation Separator Setting: If the setting of the separator is NOT comma “,”(comma) in the PC, Excel can not recognise the separator, in this case set the separator into comma.. The separator use in the logging files is always “,”(comma).

  10. MentePC 3. Installation Digit Symbol 『 , 』  comma List Separator 『 , 』  comma

  11. MentePC 3. Installation Connecting methods (1) For KX multi series Connect the outdoor control PCB and personal computer's serial port with a 232C serial cable. Use a cross cable with a D-SUB 9-pin female connector for connection to the outdoor control PCB, and a connector matching the personal computer's serial port (USB). (USB)

  12. MentePC 3. Installation Connecting methods (2) For Inverter Single PAC series Connect the CNV connector on the outdoor control PCB and personal computer’s USB port through the MentePC converter (Optional part) as shown in following figure.. USB cable to connect MentePC converter and personal computer should be prepared locally. Be sure to install USB driver software to the personal computer according to the instruction manual attached to the locally procured USB cable.

  13. MentePC 3. Installation Connecting to combination units <ON-SITE CHECK> (1) Check the operating data Outdoor unit (Master & Slave), Indoor unit (2) If an error code appears, investigate and fix the problem at that time. In case of combination outdoor unit If there are 1 USB port to 4 RC232C ports interface on your MentePC cable, you can connect four cables to a master units and a slave units. MentePC can monitor both units individually at an instance.

  14. MentePC 4. Main Functions MODE SELECTION (Outdoor unit model) 4-1 Real time monitoring Time interval can be changed from 1 to 60 seconds 4-2 Record data monitoringThe data for 30 min before an error occurred can be observed 4-3 EEPROM data monitoringThe data at the instance of an error can be observed. 4-4 Saved data read Stored data can be read and shown in some graphs.

  15. MentePC 4. Main Functions Data Logging Capacity Software version Outdoor unit information Power source frequency Address Assigned indoor unit & capacity Pressure High pressure Low pressure Temperature Heat exchanger Discharge pipe Under dome Power Module Sub cooling coil Suction pipe Outdoor air

  16. CT1 CT2 Power source voltage Pressure switch Dip switch Solenoid valve Crank case heater Fan speed EEV opening angle Compressor speed AC Fan CS Td HP LP Tc Defrost Oil return PT SCR Oil balancing Pressure control value & etc. MentePC 4. Main Functions Data Logging Current & Voltage Switch input Output Control & protection status

  17. MentePC 4. Main Functions Data Logging Indoor Unit information Capacity Address Local remote Status EEV EEV Opening Demand/Decision Hz Temperature Heat exchanger ThiR1,2,3 Thi-A

  18. MentePC 4. Main Functions 4.1 Real Time Monitoring (current time) (1)The operation data at the current time is displayed at a 1-second to 60-second cycle, and is saved. (2)This function is also useful for troubleshooting. (3)Commissioning data can be supplied using this function. Outdoor unit information This data is received at the beginning of communication. Log data

  19. MentePC 4. Main Functions 4.1 Real Time Monitoring (current time) Latest 600 set of data is plotted on the graph (In case sampling time is 1 second, the graph shows the operation of last 10 minutes.) OFF ON

  20. MentePC 4. Main Functions 4.1 Real Time Monitoring (current time) (1) Maximum 4 graphs can be shown at the same time. (2) The graph items can be selected with pull-down menu.

  21. MentePC 4. Main Functions 4.2 Record Data Monitoring (1) The operation data for 30 minutes before an error occurred can be displayed and saved. (2)The control PCB stores the operation data into its RAM area every 1 minute. Totally last 30 set of data remain in the RAM. When some kind of error occurs, the last 30 set of data still remains. Caution ! If the power of the outdoor unit is switched off, the data are lost. Please take the data first before power off for troubleshooting. Error For 30 min The data renewed automatically If the end-user restart the air-conditioner by using a remote-controller after abnormal stop, the data will be also renewed in 30 minutes.

  22. MentePC 4. Main Functions 4.2 Record Data Monitoring Sample operating graph ERROR OCCURED

  23. MentePC 4. Main Functions 4.3 Monitoring EEPROM Data (1) Control PCB stores the operation data set into its EEPROM (non-volatile memory) at the moment of an error. (2) The data set remains even if the power is switched off. (3) Last two data sets can remain. The previous ones are erased and over-written. (4) The part of data set can be checked with a remote-controller. ERROR #1 ERROR #2 ERROR #3 DATA #3 ←Remaining data set in EEPROM DATA #2 You can get some hints for troubleshooting from this data set after a restart by power off !

  24. MentePC 4. Main Functions 4.3 Monitoring EEPROM Data Sample data Outdoor unit information This data is received at the beginning of communication. Log data

  25. MentePC 4. Main Functions 4.4 Reading Saved Data (1) The data stored in PC at the site can be read with MentePC again. (2) Maximum 4 graphs can be shown at the same time. (3) The graph items can be selected with pull-down menu.

  26. MentePC 4. Main Functions 4.4 Reading Saved Data Sample graph OFF ON

  27. MentePC 5. How to use “MentePC” Running the Program a) Double Click the Excel File “MentePC_V4.2_01”

  28. MentePC 5. How to use “MentePC” b) The Macro Execution Selection screen will open. Click on “Enable Macro” Note: In some cases the Excel Macro is protected. Change the setting of Excel (Tools/Options/General) c) The Language Choice screen will open. Select a suitable language and click on “OK” Select the appropriate language

  29. MentePC 5. How to use “MentePC” d) Non- liability agreement e) The Mode Selection screen will open. Select the mode to be executed, and click on the “OK” button Monitoring Real Time Monitoring Stored Data Monitoring EEPROM Data Reading Saved Data f) If the input is mistaken on any of the selection screens, click on the button at the upper right to quit the program once and then start up again.

  30. MentePC Real Time Monitoring 1) Type any name for identification then click on the “OK” button You can omit the name. The data file will be named “R” + “the name you type” + “year” + “month” + “day” + ‘hour” + “minute” + “****” + “.csv” Note: “****” is determined by the last 4 letters of Setting File to be described. Example : RMACO201108231527KE6C.csv Typed name: MACO Date: August 23rd, 2011 Time: 15.27 Setting file: RAMDATA_KE6C.xls Note: In case of Real Time Monitoring, the file name will automatically start with “R” on the save file. This dialogue box can also be omitted/skip by clicking “OK”

  31. MentePC Rule of File-naming X???YYYYMMDDhhmm****.csv X = R:Real time, S:Stored data, E:EEPROM ??? = User option YYYY=Year, MM=Month, DD=Day,hh=hour, mm=minute **** = _KX6, KE6C, KR6C, _KX4, _KR4, K4AC, KR4C, …. How do you define your option ? <Sample definition> Measurement or Address check M:Measurement of operation data, A:Address check Master or Slave M:Master outdoor unit, S:Slave outdoor unit Project name System(circuit) name ex. MM-WBL3F-SL1-16-3.3#B Measurement of operation data Master outdoor unit System name (SuperLynk 1, Outdoor unit address 16, 3rd floor, No.3, B:Indoor unit 17-32) Project name (ex. Watabe BuiLding)

  32. MentePC Real Time Monitoring 2) Browse for the Folder and select the directory.

  33. MentePC Real Time Monitoring 3) Select combination of units to be monitored and click “OK” button. Note: This selection is not available on some kind of model. In such case this selection can be skipped. 4) Select the data reception cycle, and then click the OK button. 1/5/10/20/30/40/50/60sec

  34. MentePC Real Time Monitoring 5) Select the assigned communication port No. from COM1 to COM8, and then click on the “OK” button Choose the correct COM Port of your serial cable connection. Normally use COM1 but for USB port confirm the port from the “Control Panel” – “System”-”Device Manager” 6) Confirm the communication port with “Control Panel” >> “System” >> “Device Manager” >> “Port”

  35. MentePC Real Time Monitoring 7) Select the RAMDATA for the particular model you are monitoring. For FDC400KXE6 use RAMDATA_KE6C.xls

  36. MentePC MentePC RAMDATA Files

  37. MentePC Real Time Monitoring 8) The three worksheets “RAMDATA”, “LOGDATA” and “GRAPH” will open in case of Outdoor unit. The six worksheets “RAMDATA”, “RAMDATA_INDOOR”, “LOGDATA”, “LOGDATA_INDOOR”, “GRAPH” and “GRAPH_INDOOR” will open in case of Outdoor and Indoor unit. When the command button on the upper left is clicked on, the reception will start, and the data will appear in the worksheet. Reception will end when is clicked on. Start receiving End receiving

  38. MentePC Monitoring Stored Data 1) Type any name for identification then click on the “OK” button You can omit the name. The data file will be named “R” + “the name you type” + “year” + “month” + “day” + ‘hour” + “minute” + “****” + “.csv” Note: “****” is determined by the last 4 letters of Setting File to be described. Example : SMACO201108231527KE6C.csv Typed name: MACO Date: August 23rd, 2011 Time: 15.27 Setting file: RAMDATA_KE6C.xls Note: In case of Monitoring Stored Data, the file name will automatically start with “S” on the save file. This dialogue box can also be omitted/skip by clicking “OK”

  39. MentePC Monitoring Stored Data 2) Browse for the Folder and select the directory.

  40. MentePC Monitoring Stored Data 3) Select combination of units to be monitored and click “OK” button. Note: This selection is not available on some kind of model. In such case this selection can be skipped. 4) Select the data reception cycle, and then click the OK button. 1/5/10/20/30/40/50/60sec

  41. MentePC Monitoring Stored Data 5) Select the assigned communication port No. from COM1 to COM8, and then click on the “OK” button Choose the correct COM Port of your serial cable connection. Normally use COM1 but for USB port confirm the port from the “Control Panel” – “System”-”Device Manager” 6) Select the RAMDATA for the particular model you are monitoring. For FDC400KXE6 use RAMDATA_KE6C.xls

  42. MentePC Monitoring Stored Data 7) The three worksheets “RAMDATA”, “LOGDATA” and “GRAPH” will open. When the command button on the upper left is clicked on, the reception will start, and the data will appear in the worksheet. Depending on the PC performance, it may take approx 30 seconds to receive the data. Start receiving 8) A reception completed message will appear when the data reception is fished. Click on “OK”

  43. MentePC Monitoring Stored Data The time axis in the “GRAPH” worksheet is displayed between 0:00 to 0:30 30 minutes The logged data is saved under the file name determined section 1 in the folder “LOG” Quit the program by clicking on or the button. Program end

  44. MentePC Monitoring EEPROM Data 1) Type any name for identification then click on the “OK” button You can omit the name. The data file will be named “R” + “the name you type” + “year” + “month” + “day” + ‘hour” + “minute” + “****” + “.csv” Note: “****” is determined by the last 4 letters of Setting File to be described. Example : EMACO201108231527KE6C.csv Typed name: MACO Date: August 23rd, 2011 Time: 15.27 Setting file: RAMDATA_KE6C.xls Note: In case of Monitoring EEPROM Data, the file name will automatically start with “E” on the save file. This dialogue box can also be omitted/skip by clicking “OK”

  45. MentePC Monitoring EEPROM Data 2) Select the assigned communication port No. from COM1 to COM8, and then click on the “OK” button Choose the correct COM Port of your serial cable connection. Normally use COM1 but for USB port confirm the port from the “Control Panel” – “System”-”Device Manager” 3) Select the RAMDATA for the particular model are you monitoring. For FDC400KXE6 use RAMDATA_KE6C.xls

  46. MentePC Monitoring Stored Data 3) The worksheet “EEPDATA” will appear. When the command button on the upper left is clicked on, the reception will start, and the data will appear in the worksheet. It may take several seconds to receive the data. Start receiving Note: In case of Monitoring EEPROM Data, there is no graph available but only worksheet “EEPDATA”. This will provide hint for troubleshooting. 4) A reception completed message will appear when the data reception is fished. Click on “OK”

  47. MentePC Reading Save Data 1) Select the file, and click on the “Open” button. * It may take several minutes to read in the data depending on the data size and PC performance.

  48. MentePC Reading Save Data 2) To change the read file, click on “Change Read File” in the command bar. 3) Quit the program by clicking on “Program end” or the button.

  49. MentePC EEV’s coil abnormal EEV’s coil abnormal Cannot control EEV During full open status Cooling EEV’s coil abnormal Cannot control EEV During full close status Not Cooling Normal EEV normal control