Math in HVAC. Presented by Mike Veeder HVAC instructor Columbia Greene Questar. Whole House Heat Loss question #1. Determine design temp difference Find total square foot of windows and doors Find gross walls Subtract windows and doors from gross walls to find net walls

teneil
Télécharger la présentation

Math in HVAC

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Math in HVAC Presented by Mike Veeder HVAC instructor Columbia Greene Questar

  2. Whole House Heat Lossquestion #1 • Determine design temp difference • Find total square foot of windows and doors • Find gross walls • Subtract windows and doors from gross walls to find net walls • Determine exposed ceiling area • Find floor area

  3. Multiply each by U factor • Add all btu’s/degree Fahrenheit • Multiply by temp difference • Multiply by 15% for duct losses • Arrive at heating btu loss for house

  4. Calculate annual heat lossQuestion #2 • BTU annual = BTUH x HDD x 24hr/day x .75

  5. BTU annual = 875 x 6860 x 24 x .75 • Annual heat loss is 108,045,000 btus

  6. Propane • Determine how many gallons of propane burned per year • Gal/yr = annual btu / 92,000btu / gal • Gal/yr = 108,045,000/92,000 • Gal/yr = 1174 gal • Cost/yr = 1174 gal x $2.60/gal • Cost/yr = $3052.40 x stack loss of furnace • Cost/yr = $3662.88

  7. Electricity • Determine the amount of electricity used on a annual basis • Watt/yr = btu annual / 3.41 btu/watt • Watt/yr = 108,045,000/3.41 • Watt/yr = 31,684,750 / 1000 • KW/yr =31,684 x .14/kw • Yearly cost of electric is $4435.87

  8. Calculate BTU output of a Heat PumpQuestion 5 • BTU=1.08 x cfm x delta “T” • CFM= FPM x .66 x sq. ft of duct area

  9. Determine cfm of a Geothermal Heat pumpQuestion #4 • CFM = fpm x .66 x sq. ft • CFM = 606 fpm x .66 x 2 • CFM = 800 cfm • Btu = 1.08 x cfm x delta “t” • Btu = 1.08x 800 x (92 – 65) • Btu = 23,328 btu

  10. Geothermal loop performanceQuestion #6 • Loop filled with 20% Methanol • Btu = 485 x gpm x Delta “t” • Btu = 485 x 6 x (40 – 32) • Btu = 23,280 btu

  11. BPI Building Airflow Standard(BAS) • Living Space Area = 1500 sq. ft. • Basement area = 700 sq. ft. • Ceiling height = 8 ft. • # of Occupants = 4 • # of stories above grade = 2 • Location = Albany, NY

  12. Calculate ventilation required for building • Airflow(b) = .35 x volume/60 • Volume = 8 x (1500 + 700) = 17,600 cu. ft. • Airflow(b) = .35 x 17,600 / 60 • Airflow(b) = 102 cfm

  13. Calculate ventilation required for people • Airflow(p) = 15 x # of occupants • Airflow(p) = 15 x 4 = 60 cfm

  14. Using the higher airflow requirement • Convert cfm to cfm50 • Minimum cfm50 = airflow x N • N = LBL conversion factor • Minimium cfm50 = 102 cfm x 15.4 = 1570 cfm50

  15. When we read the cfm50 from the blower door, 1570 is what is recommended for infiltration for this house

  16. Determine course of action for home • Cfm50 x .7 = minimum ventilation • 1570 cfm50 x .7 = 1099 cfm50

  17. If the blower door reads: • Above 1570 cfm then the house is too loose and you would recommend air sealing

  18. If the blower door reads: • Between 1570 cfm50 and 1099 cfm50, then the house is within the normal range for infiltration and ventilation

  19. If the blower door reads: • Below 1099 cfm50 then you need to mechanically ventilate the house using a hrv or equivalent device. The house is too tight at this point.

  20. My class after a math lesson

  21. Thanks for your attention !! • Any questions??????????