"Rotork YTC Volume booster relay, Rotork YTC YT-325 is used in pneumatic control valve which receives positioneru2019s output signal and supply air pressure actuator to reduce response and adjusting time. - Supplies constant air pressure at the rate of 1:1. - By-passing control enhances safety of control valve. - Response to slight changes in input signal, which increases accuracy of output of air pressure to actuator. - Built-in 100 mesh screen filters dusts in the air.<br><br>For any Enquiry Call Us: 91-11-2201-4325, For Bulk Order Email at : Enquiry@ytcindia.com, Our Website :- www.ytcindia.com"<br>

ytcindia
Télécharger la présentation

ROTORK YTC YT-325 VOLUME BOOSTER | YTC INDIA

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. VOLUMEBOOSTERRELAYS YT-320/ 325SERIES PRODUCTMANUAL VERSION1.02

  2. Contents 1.Introduction…………………………………………………………………………………………… 3 1.1Generalinformationfortheusers……………………………………………………………….3 1.2ManufacturerWarranty……………………………………………………………………………3 2.ProductDescription…………………………………………………………………………………..4 2.1General…………………………………………………………………………………………….. 4 2.2 Main Features and Functions ……………………………………………………………………. 4 2.3LabelDescription………………………………………………………………………………….. 4 2.4ProductNumber…………………………………………………………………………………… 4 2.5ProductSpecification………………………………………………………………………………5 2.6PartsandAssembly………………………………………………………………………………..5 2.7OperationLogic…………………………………………………………………………………….6 2.8Dimension………………………………………………………………………………………….. 6 3.Installation……………………………………………………………………………………………….7 3.1Safety………………………………………………………………………………………………..7 3.2YT-320/325Installation……………………………………………………………………………7 3.3InstallationExample………………………………………………………………………………8 4.Maintenance.……………………………………………………………………………………………9 5.Trouble-Shooting……………………………………………………………………………………….9 YT-320/325series

  3. 1.Introduction GeneralInformationfortheusers Thank you for purchasing YoungTechCo., Ltd products. Each product has been fully inspectedafterits production tooffer youthehighestqualityandreliableperformance. Pleaseread the product manual carefullyprior to installingand commissionthe product. 1.1 • For the safety, it is important to follow the instructions in the manual. Young Tech Co., Ltd will not be responsible for any damages causedbyuser’s negligence. • Themanualshouldbeprovidedtothe end-user. • Any modifications or repairs to the product may only be performed if expressed in this manual. • Themanual canbealteredor revisedwithoutanypriornotice.Anychangesin product’s specification, design, and/or any components may not be printed immediately but until the following revision of themanual. • Themanualshouldnotbeduplicatedorreproduced foranypurposewithoutprior approval fromYoungTech Co., Ltd, Gimpo-si, SouthKorea. 1.2 ManufacturerWarranty • Forthesafety,itisimportanttofollowtheinstructionsinthemanual.Manufacturerwill notbe responsible for any damagescaused by user’s negligence. • Manufacturerwillnotberesponsibleforanydamagesoraccidentsasaresultofany alterationormodificationoftheproductanditsparts.Ifanyalterationormodifications • are necessary,please contactYoungTechCo.,Ltddirectly. • Manufacturerwarrantstheproductfromthedateoforiginalpurchaseoftheproductfor one(1) year, except asotherwisestated. • Manufacturerwarrantywillnotcoverproductsthathavebeensubjectedtoabuse, • accidents, alterations, modifications, tampering, negligence, misuse, faulty installation, lack of reasonable care, repair or service in any way that is not contemplated in the documentation for the product,orif the modelor serial numberhasbeenaltered, tamperedwith,defacedorremoved;damagesthatoccursinshipment,duetoactof God,failuredue topowersurge,orcosmeticdamage.Improperorincorrectly performedmaintenance will voidthis limited warranty. • Fordetailed warranty information,pleasecontactYoungTechCo.,Ltd– South Korea. YT-320/325series

  4. 2.ProductDescription General Volumeboosterrelay,YT-310/YT-315,isusedinpneumaticcontrolvalvewhichreceives the output signal from positioned and supply air pressure to actuator to reduce opening and closingtime of thevalve. 2.1 2.2 MainFeaturesandFunctions • Constant air pressure at theratio of 1:1 • By-passcontrol enhancessafety of thecontrolvalve operation. • Responsetoslightchangesininputsignal,whichincreasesaccuracyoftheoutput pressuretoactuator. • Internal100 meshscreenfilters smalldust entering into the product. • SIL3certified 2.3 LabelDescription Fig.1:YT-320/ 325BodyLabel Model: Max.Sup.: MaxSig/OutPress.: ProductNo.: Indicatesthemodel number Indicates maximumsupplypressurerange. Indicatesmaximum signal/ output level. Indicatesthelotnumber. 2.4 ProductNumber YT-320/325series

  5. 2.5 ProductSpecification Testedunderambienttemperatureof20’C,absolutepressureof760mmHg,andhumidityof65%.Pleasecontact YoungTechCo.,Ltdfordetailedtesting specification. PartsandAssembly 2.6 YT-320/325series

  6. 2.7 OperationLogic Assupplypressurefromregulatorisconnectedtosupplyportandsignalpressureis connectedtosupplyport,upperdiaphragm(○3)anddiaphragmassemblywillgetpushed down.Astheyarebeingpusheddown,theypushstem(○7)andsupplypressurewillbe exhaustedtooutputport.Asoutputandsupplypressureisequalized,stem(○7)willbe movedtokeepsignalandoutputpressuretheratioof1:1.Ifoutputpressureishigherthan signalpressure,diaphragmassemblywillberaised,andoutputpressureintheexhaustring (○4)willbeexhaustedthroughexhaustport.Thesensitivityofoutputpressuretosignal pressure can beadjusted by setting adjustbolt (○1). 2.8 Dimension YT-320/325series

  7. 3.Installation Safety When installinga unit, please ensure toread and followsafety instructions. 3.1 • Check unit’s specificationand ensure touse asspecified. • Use bypass valve or other supportive equipment to avoid entiresystem “shut down”. • Ensuretousefilter regulator. • Use manometer to monitorthe pressure level whensetting the pressurelevel. YT-320/325Installation YT-320/325canbeinstalledwithorwithoutabracketdependingonthefieldrequirement. Pleaserefer toYT-320/ 325 dimension to build appropriate bracket, if required. 3.2 YT-320/325series

  8. 3.3 InstallationExample Doubleactinglinearactuator Singleactingrotaryactuator YT-320/325series

  9. 4.Maintenance YT-320/325 requires regular maintenance. Please refer to below repair kit part list. It is suggested to replace allthree parts at thesame time to guarantee the life cycle ofthe product. 4.1 • Upperdiaphragmassembly: • Lowerdiaphragm: • O-rings: 1each each each • Trouble-Shooting • Please followtrouble-shootingwhen the productisnot functioning properly. • Novalveresponsetosignaltoa positioner. • Pleasecheckifsupplypressureisstablefromregulatortopositionerand/orto volumebooster. • Please checkifairpressureisbeingexhausted from positioner’sexhaustport. • Pleasecheckif signal and exhaust portsof thevolume booster are beingcleared. • Unstablevalve operationwhensignalhasbeen sent toapositioner. • Pleasereduce valve packing and/or valvefriction level. • Pleasecheck current actuatorsize and check if volume booster sizeis suitable. • Huntingoccurswhensignalhas beensenttoapositioner. • Pleasereduce valve packing and/or valvefriction level. • Pleasecheck current actuatorsize and check if volume boostersize issuitable. • Pleaseturnadjust screwcounter-clockwisetoreduce sensitivity. • Slowvalveoperation afterinstallingavolumebooster. • Pleasecheckif regulatorpressure is toolow. • Pleasecheck if supply piping totheactuator has beenblocked orclogged. • Pleasecheckifthereisanyleakage. • Pleaseturnadjustscrewclockwise toenhance sensitivity. YT-320/325series