POWER QUALITY

POWER QUALITY. -- Bhanu Bhushan -- < a3bhanu@gmail.com > August, 2011. How close is the supply voltage waveform to sinusoidal, and how close are the supply voltage and frequency to the rated ?

Télécharger la présentation

POWER QUALITY

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. POWER QUALITY -- Bhanu Bhushan -- < a3bhanu@gmail.com > August, 2011

  2. How close is the supply voltage waveform to sinusoidal, and how close are the supply voltage and frequency to the rated ? • What Power Quality do we actually have ? What Power Quality do we really need ? What all can be done to improve it ?

  3. POWER QUALITYin a wider, Indian perspective GRID - Level & CONSUMER - Level SUPPLY CONTINUITY FREQUENCY VOLTAGE

  4. SUPPLY INTERRUPTIONS a) LOAD - SHEDDING due to own or others’ over-drawal : Maximize generation, and allow over-drawal, as long as grid can sustain it, and it is paid for. b) LOAD - SHEDDING to curtail over-loading or under-voltage : If too frequent, ask for system augmentation, additional capacitors.

  5. c) TRIPPING due to a fault or equipment failure : Minimize outage duration, : Reliable protection, Auto-reclosing, : Ask for building redundancies. FREQUENCY : covered in another session.

  6. VOLTAGE PROBLEMS • HIGH / LOW : Can be corrected by transformer tap-changing and reactive compensation : shunt / series capacitors, reactors, SVC, MVAR generation change. • SWELLS & SAGS, SPIKES & DIPS, FLICKER : Caused by switching on / off of large loads, capacitor banks, electric furnaces, welding machines.

  7. PHASE UNBALANCE : Caused by single - phase or unbalanced loads (e.g. railway traction), pole - discrepancy, break in a phase (conductor snapping), break in neutral, hanging faults, non-transposition. • WAVE FORM DISTORTIONS (HARMONICS and DC offset) : caused by HVDC, SVC, FACTS, Converters, UPS, power / speed controllers, computers, TVs, chargers, printers, tube-lights, CFLs, fan regulators, electronic ballasts,

  8. communication equipment, arc furnaces, welding, railway traction, etc. Circuit breaker and isolator operation (switching transients), L.A., transformer magnetizing current inrush, lightning, Faults and their clearance, insulator flash- over, corona, faulty grounding. Wave-form distortion may be transient or sustained.

  9. 9

  10. Adverse effects : Over-heating & noise, resonance, telephone interference, hum, capacitor failure, mal-operation of control device and medical equipment. POSSIBLE SOLUTIONS : Circuit segregation, harmonic filters, U.P.S. DAMPING by synchronous and induction machines.

  11. 11

  12. Simple examples around us : • Ceiling fan regulators • Tube lights • Lap-tops & peripherals • Domestic inverters

  13. Ceiling fans -- 1- ph Induction motors, shaded - pole or split - winding, inverted. Fan regulators -- 3 different types: i) Choke : weighty, costly, low PF ii) Resistor : energy loss, heating iii) Electronic : voltage and current distortions, harmful on both sides.

  14. 18

  15. Supply voltage and fan current, regulated by old resistance type regulator, at full-speed

  16. Supply voltage and fan current, regulated by old resistance type regulator, at low speed

  17. Fan current, regulated by electronic regulator, at full speed

  18. Fan current, regulated by electronic regulator, at low speed

  19. Harmonics in fan current, at low speed, with electronic regulator

  20. Voltage wave form, after electronic regulator

  21. Harmonics in fan voltage, at low speed

  22. Tube lights : non-linear discharge lamps. Smoothening & PF improvement by choke and capacitor. Not a serious problem. Electronic ballasts : V & I distortions ?

  23. Tube light current waveform

  24. Lap-tops & peripherals : AC / DC adapters draw non-sinusoidal current. Domestic inverters : Battery charging current is always non-sinusoidal. INDUSTRIAL U.P.S.

  25. 29

  26. 30

  27. 31

  28. Voltage Wave form – UPS output

  29. Harmonics in UPS output voltage

  30. IEEE Standard 519 - 1992 Recommended Practices and Requirements for Harmonic Control in Electrical Power Systems A use of harmonics: Harmonic restraint in transformer differential relays.

  31. SOLAR FLARES --- transient fluctuations in Earth’s magnetic field (geomagnetic storms) --- potential difference between different points on Earth’s surface --- DC enters one transformer neutral and exits at another -- half-cycle saturation of transformer cores --- unwanted trippings & grid disturbance. 35